SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
BACnet PIC Statement for Vive
using Vive Version 1.07
Software License
369996d 1 05.09.18
Vive
BACnet® Protocol Implementation Conformance
Statement (PICS)
Date: May 09, 2018
Vendor Name: Lutron Electronics Co., Inc.
Product Name: Vive BACnet Integration
BACnet Applications Software Version: 1.07
Vive Firmware Revision: 1.07
BACnet Protocol Revision: 13
Vendor ID: 176
Product Description
BACnet IP is embedded in the Vive hub. There are two types of
BACnet devices available in Vive:
Vive hubs and area devices. The Vive hubs are main BACnet devices;
typically, one to two Vive hubs per floor of the building. The area
devices are virtual BACnet devices of the Vive hub, typically one per
room of the building. It is normal to have multiple Vive hubs and area
virtual devices in a project.
BACnet Interoperability Building Blocks Supported (Annex K):
K.1.2 BIBB Data Sharing ReadProperty-B (DS-RP-B)
K.1.4 BIBB Data Sharing ReadPropertyMultiple-B (DS-RPM-B)
K.1.8 BIBB Data Sharing WriteProperty-B (DS-WP-B)
K.1.10 BIBB Data Sharing WritePropertyMultiple-B (DS-WPM-B)
K.1.12 BIBB Data Sharing COV-B (DS-COV-B)
K.5.2 BIBB Device Management DynamicDeviceBinding-B (DM-DDB-B)
K.5.4 BIBB Device Management DynamicObjectBinding-B (DM-DOB-B)
K.5.6 BIBB Device Management DeviceCommunicationControl-B (DM-DCC-B)
BACnet Standardized Device Profile (Annex L):
BACnet Application Specific Controller (B-ASC)
Segmentation Capability:
Segmented requests supported? No. Window Size: n/a
Segmented responses supported? No. Window Size: n/a
Non-Standard Application Services:
Non-standard application services are not supported.
BACnet is a registered trademark of ASHRAE.
ASHRAE does not endorse, approve or
test products for compliance with ASHRAE
standards. Compliance of listed products to
the requirements of ASHRAE Standard 135 is
the responsibility of BACnet International (BI).
BTL is a registered trademark of BI.
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
BACnet PIC Statement for Vive
using Vive Version 1.07
Software License
369996d 2 05.09.18
Vive
Standard Object Types Supported:
Device
1. Dynamically creatable using BACnet CreateObject service? No.
2. Dynamically deletable using BACnet DeleteObject service? No.
3. List of optional properties supported: Active_COV_Subscriptions, Description, Location, Profile_Name.
4. List of all properties that are writable where not otherwise required by this standard: None.
5. List of proprietary properties: None.
6. List of any property value range restrictions: None.
Analog Value
1. Dynamically creatable using the BACnet CreateObject service? No.
2. Dynamically deletable using BACnet DeleteObject service? No.
3. List of optional properties supported: COV_Increment (See Table for objects that support this property).
4. List of all properties that are writable where not otherwise required by this standard: None.
5. List of proprietary properties: None.
6. List of any property value range restrictions: See Table.
Binary Value
1. Dynamically creatable using BACnet CreateObject service? No.
2. Dynamically deletable using BACnet DeleteObject service? No.
3. List of optional properties supported: Active_Text, Inactive_Text.
4. List of all properties that are writable where not otherwise required by this standard: None.
5. List of proprietary properties: None.
6. List of any property value range restrictions: See Table.
Multi-State Value
1. Dynamically creatable using BACnet CreateObject service? No.
2. Dynamically deletable using BACnet DeleteObject service? No.
3. List of optional properties supported: State_Text.
4. List of all properties that are writable where not otherwise required by this standard: None.
5. List of proprietary properties: None.
6. List of any property value range restrictions: See Table.
Data Link Layer Options:
Other: These devices are virtual devices and are represented by a six octet address equal to the 48-bit device
instance of the virtual device.
Device Address Binding:
Is static device binding supported? No.
Networking Options:
BACnet / IP Annex J non-BBMD functionality; the Vive is able to register as a foreign device. The Vive hub is able
to initiate original-broadcast-NPDU.
Character Sets Supported:
Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
UTF-8
BACnet Routing:
The Vive hub is a BACnet virtual router. All of the virtual area devices are routed through the main Vive hub.
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
BACnet PIC Statement for Vive
using Vive Version 1.07
Software License
369996d 3 05.09.18
Vive
Object Name Type Instance Read Write COV Units Min
PV
Max PV Inactive
Text (0)
Active
Text (1)
State Text
(Multi-State)
Notes
{SystemName}
{Instance}
DEVICE 22 bit
GUID
X The System Name is the logical
name of one of the Vive hubs that
typically corresponds to a physical
portion of the building such as a
floor. The Instance is the same as
the unique Device ID assigned to
each Vive hub.
Master Load shed
Enabled
BV 2 X X X 0 1 Disabled Enabled This value determines whether all of
the areas in the Vive subsystem are
being controlled via load shedding.
When this value is set to Enabled, for
all areas in the hub that have load
shed allowed, any dimmable lights in
each area that are turned on will
have their light level reduced by the
percentage specified in the Load
shed Goal value. The specified
switched loads will turn off. When
Disabled, the lights will return to
their previous level and the specified
switched loads will return to their
previous state.
Object Name Type Instance Read Write COV Units Min
PV
Max PV Inactive
Text (0)
Active
Text (1)
State Text
(Multi-State)
Notes
{AreaName}
{Instance}
DEVICE 22 bit
GUID
X The Area Name is the logical name
that typically corresponds to a
physical location in a building. The
Instance is the same as the unique
Device ID assigned to each area.
Lighting Level AV 2 X X X % 0 100 The intensity level of all lighting
fixtures in the area. The light level
will be an analog value between 0%
and 100%. If the lighting fixtures in
the area are at different light levels,
this value will be set to the level of
the highest intensity in that area.
This will apply to both switched and
dimmed lighting fixtures. If a
non-zero level is written switched
lighting fixtures will turn on and
dimmed lighting fixtures will go to
that level.
Lighting State BV 3 X X X 0 1 Off On The Lighting State will be On if any
of the lighting fixtures in the area
are in the on state; if all lighting
fixtures are off, the Lighting State
will be set to Off. When written with
On, it will turn all dimmable lighting
loads to 100% and turn all switched
lighting loads on. When written with
Off, it will turn all lighting loads off.
AV = Analog-Value, BV = Binary-Value, MSV = Multi-State-Value
{Area Name} / {SystemName} is a text string defined in the Lutron Vive system configuration software
{Instance} is a number defined in the Lutron Vive system configuration software that is equal to the {Base} number + unique Device ID assigned to each area.
PV = Present-Value
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
BACnet PIC Statement for Vive
using Vive Version 1.07
Software License
369996d 4 05.09.18
Vive
Object Name Type Instance Read Write COV Units Min
PV
Max PV Inactive
Text (0)
Active
Text (1)
State Text
(Multi-State)
Notes
Disable Occupancy BV 7 X X X 0 1 False True When set to True, occupancy
sensors will not affect the lights in
the area. When set to False,
occupancy sensors will affect the
lights in the area as programmed.
Occupancy State MSV 8 X X 1 4 1 = Unoccupied
2 = Occupied
4 = Unknown
A read-only property indicates the
occupancy of the entire area.
Occupied means that at least one
sensor in the area is indicating
occupancy. Unoccupied means that
all of the sensors in the area are
indicating unoccupied. Unknown
indicates that not all of the sensors
in the area have reported their
status.
Unoccupied Level AV 9 X X X % 0 100 The light level to which the dimmed
lights in the area will be set when an
area transitions to unoccupied.
Occupied Level AV 10 X X X % 0 100 The light level to which the dimmed
lights in the area will be set when an
area transitions to occupied.
Load shed Allowed BV 12 X X X 0 1 No Yes When Load shed Allowed is set to
YES, this area will be affected when
Load shed is Enabled. When set to
NO, this area will not be affected
when Load shed is Enabled.
Load shed Goal AV 13 X X X % 0 90 When Load shed is enabled and Load
shed Allowed is set to YES, the light level
will be reduced by the percentage
specified. Range: 0% to 90%
AV = Analog-Value, BV = Binary-Value, MSV = Multi-State-Value
PV = Present-Value
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
BACnet PIC Statement for Vive
using Vive Version 1.07
Software License
369996d 5 05.09.18
Vive
Object Name Type Instance Read Write COV Units Min
PV
Max PV Inactive
Text (0)
Active
Text (1)
State Text
(Multi-State)
Notes
Occupancy Mode MSV 14 X X X N/A 2 5 2 = Automatic
ON, Automatic
OFF
(Read-Write)
3 = Manual ON,
Automatic OFF
(Read-Write)
4 = Not
Applicable
(Read-Only)
5 = Mixed
(Read-Only)
Determines the way that the occupancy
sensors control the lights. When set to
Automatic ON and Automatic OFF, the
sensors will set lights to their occupied
level when occupied and to their
unoccupied level when unoccupied.
When set to Manual ON and Automatic
OFF, the sensors will set lights to the
unoccupied level only when an area
changes to unoccupied. Not Applicable
means that the area is not controlled by
occupancy. Mixed means that the zones
in the area have been configured as a
combination of "Automatic ON and
Automatic OFF" and "Manual ON and
Automatic OFF" modes.
NOTE S:
1. States Not Applicable and Mixed are
read-only states. Writes with those
states will return a value out of range
error.
2. State value 1 is not used and reserved.
Writing 1 results in a value out of range
error.
Total Power AV 18 X X watts 0 none A calculated / measured value that
indicates the total instantaneous
power consumption for all of the
lighting loads in the area.
Maximum Power AV 19 X X watts 0 none The maximum connected lighting
load of the area. This value is the
maximum value that Total Power
can achieve. Maximum Power minus
Total Power equals the power being
saved. This value typically does not
change.
AV = Analog-Value, BV = Binary-Value, MSV = Multi-State-Value
PV = Present-Value
)Lutron, Lutron, and Vive are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries.
BACnet is a registered trademark of the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (ASHRAE).
5