BACnet PIC Statement for Quantum® Area Virtual Devices
using Quantum
® Version 3.0
Software
License
Quantum®
Object Name Type Instance Read Write COV Units Min PV Max PV Inactive
Text (0)
Active
Text (1)
State Text (Multi-State)
{AreaName}
{Instance}
DEVICE {Base} +
{System}
+ 1
X — — — — — — — —
Notes: The Area Name is the logical name that typically corresponds to a physical location in a building. The Instance is the same as the
unique Device ID assigned to each area.
Lighting Level AV 2 X X X % 0 100 — — —
Notes: The intensity level of all lighting fixtures in the area. The lighting level will be an analog value between 0% and 100%. If the lighting
fixtures in the area are at different light levels, this value will be set to the level of the highest intensity in that area.
Lighting State BV 3 X X X — 0 1 Off On —
Notes: The lighting state will be ON if any of the lighting fixtures in the area are in the On state; if all lighting fixtures are off, the lighting state
will be set to OFF.
Lighting Scene MSV 4 X X X — 1 Number
of
scenes
defined
for this
area in
Q-Design
— — {SceneName}
Notes: The lighting preset to which the lighting fixtures in that area are currently set. If the value is set to 1, the Off Scene will be selected,
which will turn all lights to OFF. All other scenes are defined within the Lutron® Quantum® system configuration software. If lights are
currently not set to a valid lighting scene, then the value will be set to an unknown preset level.
Daylighting Enabled BV 5 X X X — 0 1 Disabled Enabled —
Notes: When set to Enabled, any daylight sensors programmed to control that area will limit the light level that the lighting fixtures in the
area can produce. When set to Disabled, daylight sensors will not affect the lighting fixtures in that area. When changed from
Disabled to Enabled the lights go to 100%.
Daylighting Level AV 6 X X X % 0 100 — — —
Notes: When daylighting is Enabled, all light fixtures in the area that are controlled by a daylighting sensor are set to a target value between
0% and 100%. When set to 100%, lights will be at their maximum level. When set to 0%, lights will be at their minimum level.
This value should not be used with switching loads.
Disable Occupancy BV 7 X X X — 0 1 False True —
Notes: When set to True, the area will go to the Occupied level and the occupancy sensors will no longer affect the lights in the area.
AV = Analog-Value, BV = Binary-Value, MSV = Multi-State-Value
{AreaName} is a text string defined in the Lutron® Quantum® system configuration software
{Instance} is a number defined in the Lutron
® Quantum® system configuration software that is equal to the {Base} number + {System} number +1
{Base} is a 22-bit value set in the Lutron
® Quantum® system configuration software (default 1760000)
{System} is an 8-bit value set in the Lutron
® Quantum® system configuration software (0 to 127)
{SceneName} is a text string of the name of each scene that is defined in the Lutron
® Quantum® system configuration software
PV = Present-Value