DIN Power Module
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom Low Capacity Switching
369841c 4 11.29.18
Specifications
Regulatory Approvals
• UL
® Listed
• cULListed
• NOMCertified
• RoHSCompliant
• IEC/EN60669(220-240V~50/60Hzonly)
• RoHSCompliant
• LutronQualitySystemsregisteredtoISO9001.2015
Power
• SeeModelNumbertableonpage1
• Singleinputfeed
• 4Amaximuminputcurrent
• LightningstrikeprotectionmeetsANSI/IEEEstandard
C62.41andIEC61000-4-5.Canwithstandvoltagesurges
upto6000V~andcurrentsurgesupto3000A.
• Standbypower:<3W
(wireddevicesonQSlinkexcluded)
• Provides4PDUstopowerQSdevicesonQSlink
• ESD-protectionexceedsagencyrequirementsper
IEC-61000-4-2
• QSLinkoutput:24V-
• Forungroundeddeltafeedapplications,contactLutron.
Environment
• Forthermalspecifications,seeMounting section
• Relativehumidity:lessthan90%non-condensing
• Forindooruseonly
Terminals
• Mainswiring: 1.0 mm² to 2.5 mm² (18AWGto12AWG)
(singlewire,solidorstranded)
• CCI/CCOwiring:
0.5 mm² to 2.5 mm² (22AWGto12AWG)
(singlewire,solidorstranded)
• Zonewiring: 1.0 mm² to 2.5 mm² (18AWGto12AWG)
(singlewire,solidorstranded)
• QSLink: 0.5 mm² to 2.5 mm² (22AWGto12AWG)
(singlewire,solidorstranded)
Manual Mode Operation
• Zonebuttonontheunitcanbeusedtoturnloadsonand
off
Output Zone Ratings
• Eachzoneisratedat1Aforswitching.Ratedfor
resistive,inductive,orcapacitivelightingloadsasdefined
byIEC/EN60669,NEMA410.
• Airgapispresentforeachoutputwhenloadis
switched off.
• Nominimumloadperoutput.
• Thismoduleisdesignedtocontrolloadswithratings
asnotedinthetablebelow.Outputscannotbeusedto
control general purpose receptacles.
• Specialconsiderations:
-Whencontrollinglamps,Lutronrecommendsusing
permanentlyinstalledfixtures.
-Ifcontrollingplug-inlamps,installationmustensurea
methodofpreventingnon-ratedloadsbeingplugged
intotheunit.Anexampleisadedicatedreceptacle
with an alternate plug type.
-Controllingloadsoutsidethetablebelowwilldamage
the device and void the warranty.
• Ifattemptingtocontrolgeneralpurposereceptacles,
usetheappropriatethird-partycontactor/powerpack
for the rated load.
• Runaseparateneutralforeachloadcircuit.Acommon
neutral connection is not recommended.
• UnitmaybepoweredbyGroundFaultInterrupter(GFI)
orResidualCurrentCircuitBreakerwithOverload
(RCBO)protectedcircuitifrequired.
• Forapplicationsrequiringhigherwattageratings,use
PHPM-SW-DV-WH,GRX-TVI,orLQSE-4S10-D.
Load Type
Relay Ratings
100–240 V~
Tungsten
1
1A
ACGeneralUse 1A
ElectricDischargeLamp 1A
ElectricBallast
(NEMA410)
1A
Resistive 1A
Inductive 1A
LED 1A
Motor
2
1A
1
Whenusingtungstenloads,lampsshouldbefromareputable
manufacturerandbefused.LutronrecommendsusinganIEC
60127-2compliant2Aexternalfuseforeachoutputthatisusing
tungstenloads.PleaseseeApplicationNote048566for
additional information.
2
Twomotorsmaxpermodule.