SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
369859b 2 04.13.15
Wallbox ControlsQS Slider for Quantum®
GRAFIK TTM
Performance
• Power failure memory: should power be
interrupted, the control will return to its previous
state when power is restored.
• Tested to withstand surge voltages without
damage or loss of operation, in accordance with
IEEE C62.41-1991 Recommended Practice on
Surge Voltages in Low-Voltage AC Power Circuits.
• Tested to withstand electrostatic discharge without
damage or memory loss, in accordance with
IEC 61000-4-2.
System Communications and Capacities
• Only works in a Quantum® system
• Performance will degrade if more than 5 units are
being controlled simultaneously per link.
Partitioning
• Supports Quantum® zone chaining feature for
partitioning spaces.
Mounting
• Requires a U.S. wallbox 3 ½ in (89 mm) deep,
2 ¼ in (57 mm) deep minimum, or low-voltage
mounting bracket.
Warranty
• 1 Year Limited Warranty.
For additional Warranty information, please visit
www.lutron.com/TechnicalDocumentLibrary/
369-119_Wallbox_Warranty.pdf
Specifications
Regulatory Approvals
• Designed for IEC PELV / NEC® Class 2
operation only.
• Not a wireless device.
• Compliant with UL® 9D10.
• Compliant with CSA 22.2 No. 14-13.
• Compliant with IEC60669.
Power
• 24-40 V- 30 mA IEC PELV / NEC® Class 2.
Typical Power Consumption
• 0.15 W; 1 Power Draw Unit (PDU).
• Test conditions: QS slider powered at 24 V-,
remote load is off..
Environment
• Ambient Temperature Operating Range:
32°F to 104°F (0°C to 40°C).
• Relative humidity: 0% to 90% non-condensing.
• For indoor use only.
Lighting Sources / Load Types
• Controls lighting sources with smooth, continuous
Square Law dimming.
• Works with any type of lighting zone output in a
Quantum® system excluding 3-channel DMX loads.
• Works with dimmed loads and non-dimmed loads.
Specifications