SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LR-HVAC-230-S
369813a 1 07.02.15
LutronR Room Thermostat
The 230 V~ room thermostat adds temperature
control to the LutronR hotel guestroom control
solution. Controls 2-pipe, 4-pipe, and 3 fan-speed fan
coil units. Compatible with LutronR Guestroom Control
Unit (GCU-HOSP) and integrates into LutronR
HomeWorksR QS system.
Model Number
LR-HVAC-230-S
Available in matte white only
Applications
• Room temperature control (heating or cooling) in
individual rooms and zones by:
2-pipe fan coil units with manual heating/cooling
changeover
2-pipe fan coil units with automatic heating/cooling
changeover
2-pipe fan coil units with electrical heater
4-pipe fan coil units
Compressors in DX-type equipment
Compressors in DX-type equipment with electrical
heater
• Heating/Cooling outputs for any one of the following
applications:
One or two on/off valve actuators
One on/off valve actuator and one 1-stage electrical
heater
One 3-position valve actuator
One 1-stage compressor in DX-type equipment, or
one 1-stage compressor with electrical heater
• Fan control outputs for any one of the following
applications:
One single speed fan
One 3-speed fan
LR-HVAC-230-S
230 V~ Room Thermostat
Features
• Backlit display, remains backlit for 10 seconds after
a button press
• Outputs for on/off or 3-position water valve controls
• Outputs for 3-speed or single speed fans
• Automatic or manual fan speed control
• Built-in room temperature sensor
• Input for external temperature sensor
• Automatic or manual heating/cooling changeover
• Programmable minimum and maximum limits for
room temperature setpoint
• Configurable Economy Mode for energy savings
when room or home is unoccupied
• Configurable Protection Mode for maximum
energy savings when room is unsold, or home is
unoccupied for an extended period of time
• Communicates to LutronR Guestroom Control Unit
GCU-HOSP via 3-wire digital link
• Mounts on recessed rectangular conduit box with
60.3 mm screw centers
• 230 V~ operating voltage
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LR-HVAC-230-S
369813a 2 07.02.15
LutronR Room Thermostat
Specifications
Power supply
Rated voltage: 230 V ~
Frequency: 50/60 Hz
Power consumption: Maximum 7 VA / 3.7 W
Standby power consumption: < 0.5 W
Outputs
Fan control Q1, Q2, Q3-N: 230 V ~
– Rating: Max. 5 A inductive, 2 A resistive
Control output Y11-N / Y21-N (N.O.): 230 V ~
– Rating: Max. 5 A inductive, 2 A resistive
Inputs
Two multifunctional inputs X1 and X2
– Temperature sensor input:
·
Type: QAH11.1 (NTC)
·
Temperature range: 0 °C to 49 °C
·
Cable length: maximum 80 m
– Digital input:
·
Operating action: Selectable (NO / NC)
·
Contact sensing: SELV 0 V- to 5 V- (5 mA
maximum)
·
Parallel connection of several thermostats with
one switch: Maximum 20 thermostats / switch
Insulation against mains voltage (SELV): 4 kV,
reinforced insulation
Function of inputs: X1 and X2 are selectable
External temperature sensor, heating/cooling
changeover sensor, operating mode switchover
contact, dew point monitor contact, enable
electrical heater contact, fault contact
Communications Link
Interface type: RS485
One 0.34 mm
2
to 0.75 mm
2
(22 AWG to 18 AWG)
for common/neutral wire
Two 0.34 mm
2
to 0.75 mm
2
(22 AWG to 18 AWG)
twisted/shielded wire for data link
Maximum 600 m total wire length
Bus current: Maximum 50 mA
Wiring topology: Free wiring topology
Maximum of 32 LR-HVAC-230-S units per link
Operational data
Adjustable switching differential
Heating mode: 2 K default, adjustable from 0.5 K
to 6 K
Cooling mode: 1 K default, adjustable from 0.5 K
to 6 K
Default setpoint settings and range
Comfort: 21 °C default, adjustable from 5 °C to
40 °C
Economy: Default 15 °C heating / 30 °C cooling,
adjustable from 5 °C to 40 °C
Protection: Default is 8 °C heating, OFF for cooling,
adjustable from 5 °C to 40 °C or OFF
Input X1 default setting: Operational mode switchover
Input X2 default setting: External temperature sensor
Built-in room temperature sensor
– Measuring range: 0 °C to 49 °C
– Accuracy at 25 °C: < ± 0.5 K
– Temperature calibration range: ± 3.0 K
Settings and display resolution
– Setpoints: 0.5 °C
– Current temperature value displayed: 0.5 °C
Environmental Conditions
Operation: As per IEC 60721-3-3
– Climatic conditions: Class 3K5
– Temperature: 0 °C to 50 °C
– Humidity: <95% relative humidity, non-condensing
Transport: As per IEC 60721-3-2
– Climatic conditions: Class 2K3
– Temperature: –25 °C to 60 °C
– Humidity: <95% relative humidity
Storage: As per IEC 60721-3-1
– Climatic conditions: Class 1K3
– Temperature: –25 °C to 60 °C
– Humidity: <95% relative humidity
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LR-HVAC-230-S
369813a 3 07.02.15
LutronR Room Thermostat
Specifications (continued)
Standards and Directives
Conformity
– EMC directive: 2004/108/EC
– Low-voltage directive: 2006/95/EC
Restriction of the use of certain hazardous
substances in electrical and electronic equipment
(RoHS): 2011/65/EU
Product standards
Automatic electrical controls for household and
similar use: EN 60730–1
Special requirements for temperature-dependent
controls: EN 60730–2-9
Electronic control type: 2.B (micro-disconnection on
operation)
Home and Building Electronic Systems:
EN 50090-2-2
Electromagnetic compatibility
Emissions (residential) IEC/EN 61000-6-3
Immunity (industrial and residential):
IEC/EN 61000-6-2
Special requirements for temperature-dependent
controls: EN 60730–2-9
Safety class: II as per EN 60730
Pollution class: Normal
Degree of protection of housing: IP 30 as per
EN 60529
General
Connection terminals: one 0.4 mm
2
to 1.5 mm
2
(20 AWG to 16 AWG) solid or prepared stranded wire
Note: For sensors on inputs X1 and X2, the maximum
cable length is 80 m.
Housing front color: RAL 9003 white
Functions
Maintain room temperature via built-in temperature
sensor or external room temperature/return air
temperature sensor
Temperature display options:
– Current room temperature in either °C or °F
– Current room temperature in both °C and °F
– Setpoint temperature in either °C or °F
– Setpoint temperature in both °C and °F
Programmable minimum and maximum limits for
room temperature setpoint
Button lock (automatic, manual, or via digital link)
Two multifunctional inputs that are configurable as
any of the following:
– Operating mode switchover contact (keycard)
– Automatic heating/cooling changeover sensor
External room temperature sensor or return air
temperature sensor
Dew point sensor (typically for chilled ceiling
applications)
Electrical heater enabled
External fault input (e.g. drain pan sensor)
Advanced fan control functions: Fan kick, fan
start, selectable fan operation (enable, disable, or
dependant on heating/cooling mode)
Purge function together with 2-port valve in a 2-pipe
changeover system
• Reminder to clean filters
• Floor heating temperature limit
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LR-HVAC-230-S
369813a 4 07.02.15
LutronR Room Thermostat
Mounting
Mount the room thermostat on a recessed
rectangular conduit box with 60.3 mm screw
centers. Do not mount in niches, or bookshelves,
behind curtains, above or near heat sources, or
in direct sunlight. Mount the room thermostat
approximately 1.5 m above the floor.
The rear of the mounting base contains the screw
terminals.
Mount the room thermostat on a clean, dry, indoor
wall. Do not mount in direct airflow or expose to
water (e.g., drips or splashes).
If there is limited space in the conduit box, use
Siemens mounting bracket ARG70.3 to increase the
headroom by 10 mm.
See the mounting instructions enclosed with the
room thermostat.
The thermostats consist of 2 parts:
• Front panel with electronics, operating elements and
built-in room temperature sensor.
• Mounting base with power electronics.
Wiring
• Install and wire in accordance with all local and
national codes.
• Use proper size cables to wire the thermostat, fan
and valve actuators for 230 V~ mains voltage.
• Use only valve actuators rated for 230 V~.
• The 230 V~ mains supply line must have external
over-current protection with a rated current of no
more than 10 A.
• If the conduit box carries 230 V~ mains voltage,
isolate the SELV inputs (X1-M/X2-M) from mains
voltage.
• Inputs X1-M or X2-M of different units (e.g.
summer / winter switch) may be connected in
parallel with an external switch. Consider overall
maximum contact sensing current for switch rating.
• Isolate communication input wires (e.g., MUX,
_, and COM) from mains voltage.
• Do not use metal conduits or cables that have a
metal sheath.
cm
1.5 m
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LR-HVAC-230-S
369813a 5 07.02.15
LutronR Room Thermostat
N1 Room thermostat
M1 Single speed or 3-speed fan
Y1 Valve actuator, 2-position or 3-position
Y1, Y2 Valve actuator, 2-position
E1 Electric heater
C1, C2 1-stage compressor
F External fuse
S1 Switch
(e.g., keycard, window contact, or presence
detector)
B2 Temperature sensor
(e.g., return air temperature, external room
temperature, or changeover sensor)
MUX RS485 connection
_ RS485 connection
COM RS485 signal common
5(2)A 5 A resistive, 2 A inductive
L
N
10 A
L
N
Y11
Y21
AC 230 V
X1 M
X2
N1
M1
Y1
5(2)A
max.
5(2)A
max.
B2
S2
B1
S1
F
3171A12
Q1 Q2 Q3
IIIIII
CE+CE-
KNX
Y1
5(2)A
max.
E1
5(2)A
max.
5(2)A
max.
Y1
C1
5(2)A
max.
Y1
5(2)A
max.
Y2
5(2)A
max.
C1
5(2)A
max.
E1
5(2)A
max.
C2
5(2)A
max.
COM
MUX
MUX
230 V ~
Connection Diagrams
Application
2-pipe, 2-position
2-pipe, 3-position
2-pipe and
electric heater
4-pipe
1-stage compressor
(heating/cooling)
1-stage compressor and
electric heater
230 V ~
L
N
10 A
L
N
Y11
Y21
AC 230 V
X1 M
X2
N1
M1
Y1
5(2)A
max.
5(2)A
max.
B2
S2
B1
S1
F
3171A12
Q1 Q2 Q3
IIIIII
CE+CE-
KNX
Y1
5(2)A
max.
E1
5(2)A
max.
5(2)A
max.
Y1
C1
5(2)A
max.
Y1
5(2)A
max.
Y2
5(2)A
max.
C1
5(2)A
max.
E1
5(2)A
max.
C2
5(2)A
max.
Y 11
Y 11
Y 11
Y 11
Y 11
Y 21
Y 21
Y 21
Y 21
Y 21
maximum
maximum
maximum
maximum
maximum
maximum
maximum
maximum
maximum
maximum maximum
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LR-HVAC-230-S
369813a 6 07.02.15
LutronR Room Thermostat
Connection Terminals
L, N: Operating voltage 230 V~
Q1: Control output “Fan speed 1 230 V~
Q2: Control output “Fan speed 2 230 V~
Q3: Control output “Fan speed 3 230 V~
Y11,Y21: Control output “Valve” 230 V ~ (N.O., for normally closed
valves), output for compressor or output for electrical heater
X1, X2 Multifunctional input for temperature sensor (e.g. QAH11.1) or
potential-free switch
Factory setting:
X1 = Operating mode switchover contact
X2 = External sensor
(function can be selected via parameter P38/P40).
M Measuring neutral for sensor and switch
MUX RS485 connection
_ RS485 connection
COM RS485 signal common
Connection to the LutronR Control Unit or Processor
X2
X1
M
L
COM
MUX
MUX
N
Y11
N
Y21
Q1 Q2 Q3
GCU-HOSP
HQP6-2
HQP6-MDU
LR-HVAC-230-S
1 pair
0.34 mm
2
to 0.75 mm
2
(22 AWG to 18 AWG)
twisted/shielded pair
IEC PELV/NECR Class 2
0.34 mm
2
to 0.75 mm
2
(22 AWG to 18 AWG) for common
6
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LR-HVAC-230-S
369813a 7 07.02.15
LutronR Room Thermostat
Dimensions (mm)
Front View
60
52
67
Rear View
14
Side View
5
86
86
41
55
54
22
7