myRoom DIN Power Module Low Capacity Phase Adaptive
369849h 5 11.29.18
Specifications (continued)
Output Zone Ratings
•
No Derating is required if all the conditions below are met:
– Calibration point maximum is 70 ºC (158 ºF)
– Room ambient temperature is between 0 ºC and 30 ºC
(32 ºF and 86 ºF).
– Panel ambient temperature, within 20 mm (0.80 in) of
unit, is between 0 ºC and 50 ºC (32 ºF and 122 ºF).
• 25 W (100 – 120 V~) / 50 W (220 – 240 V~): Derating
on all zones is required for a single module in a non-
ventilated enclosure if the room ambient temperature is
between 30 ºC and 40 ºC (86 ºF and 104 ºF).
• 50 W (100 – 120 V~) / 100 W (220 – 240 V~): Derating
on all zones is required in a multiple row non-ventilated
enclosure if the temperature is between 30 ºC and
40 ºC (86 ºF and 104 ºF).
• Each zone has a 5 W (incandescent) minimum
load requirement. For LED compatibility details,
see www.lutron.com/LEDTool and
Application Note #557 (P/N 048557) at www.lutron.com.
• When programmed to “auto” mode, the unit starts in
reverse-phase and if an incompatible load is detected,
it will convert to forward-phase.
• Does not support non-dimmable loads.
• One load type per zone.
• This module is designed to control loads with ratings
as noted in the table below. Outputs cannot be used to
control general purpose receptacles.
A
Refer to www.lutron.com/LEDtool for compatibility with dimmable CFL / LED light sources.
B
Only use iron core transformers intended for use with an electronic switch or dimmer per Clause 8.3 of IEC / EN 60669-2-1.
C
Actual lamp wattage.
Each zone is rated for the following wattage and load types
A
:
Load Type
Zones 1 – 4
100 V~ 120 V~ 220 V~ 230 V~ 240 V~
Incandescent / Halogen 100 W 120 W 220 W 230 W 240 W
Electronic Low-Voltage 100 W 120 W 220 W 230 W 240 W
Magnetic Low-Voltage
B
100 VA (75 W
C
) 120 VA (90 W
C
) 220 VA (165 W
C
) 230 VA (172 W
C
) 240 VA (180 W
C
)
Neon / Cold Cathode
B
100 VA (75 W
C
) 120 VA (90 W
C
) 220 VA (165 W
C
) 230 VA (172 W
C
) 240 VA (180 W
C
)
Hi-lume A-Series LTE N/A 120 VA 1-6 drivers N/A N/A N/A
• Special considerations:
– Outputs are not compatible with load-side switching
(i.e., breakers, switches, lamps with integral switch
control, etc.)
– When controlling lamps, Lutron recommends using
permanently installed fixtures. Output should not be
used to control general purpose receptacles. Doing
so will void the warranty.
– If controlling plug-in lamps, installation must ensure a
method of preventing non-rated loads being plugged
into the unit. An example is a dedicated receptacle
with an alternate plug load such as a Duplex Dimming
Receptacle (NTR-15-DDTR-) and Dimming Lamp Plug
(RP-FDU-10-). Lamps must not be switched using the
controls integral to the lamp.
– Controlling loads outside the parameters listed in the
table below may damage the device and void the
warranty.
• Run a separate neutral for each load circuit. A
common neutral connection is not recommended.
• Unit may be powered by Ground Fault Interrupter (GFI)
or Residual Current Circuit Breaker with Overload
(RCBO) protected circuit if required. Load circuit wiring
(from breaker to unit to load) must be run in its own
non-metallic conduit, or nuisance tripping may occur.
• For applications requiring 0 –10 V- control, use
10 V- Interface (GRX-TVI).
• For applications requiring higher wattage ratings, use
multiple individual circuits and group them into a single
zone via software, or use a PHPM-PA for 120 V~
installations.
• Maximum wire length between Phase Adaptive Power
Module and the load must be less than 30.5 m (100 ft).