FC-SENSOR, FC-VSENSOR, FCJ-010, FCJ-ECO
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LutronR PowPak® Fixture Controls
369866d 1 08.19.16
PowPak® Fixture Controls
The PowPak® wireless fixture control is a radio-
frequency (RF) device that controls either the Lutron
®
EcoSystem
® or 0 10 V- electronic fluorescent ballasts
and LED drivers (depending on model). This is based
on RF input from Pico
® wireless controls, Radio Powr
Savr
TM wireless sensors, or wired inputs from the
PowPak
® fixture sensor. The control module mounts to
a fixture or a U.S.-style junction box. Communication
with RF input devices is accomplished using Lutron
®
Clear Connect
® RF Technology. See the Applications
and Selecting the Right Control section for more
details on selecting the appropriate controls for your
application.
The PowPak
® fixture sensor (optional) mounts to the
ceiling or to a fixture and measures light in the space
(daylighting) while detecting people moving within an
area to determine passive infrared occupancy. The
sensor controls the lights to balance light level in the
space, combining convenience, exceptional energy
savings, and ease of installation. The sensor contains
two wires which connect to the PowPak
® wireless
fixture control.
Models Available
Model Number Description
FC-SENSOR PowPak
® fixture sensor (occupancy)
FC-VSENSOR PowPak
® fixture sensor (vacancy)*
FCJ-010
PowPak
® wireless fixture control for 0 –10V- drivers and ballasts
FCJ-ECO PowPak
® wireless fixture control for EcoSystem® drivers and ballasts
PowPak® Wireless Fixture Control
*
* Lights do not turn on automatically with a vacancy sensor. A Pico® wireless control is needed to turn on the lights.
1
FC-SENSOR, FC-VSENSOR, FCJ-010, FCJ-ECO
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LutronR PowPak® Fixture Controls
369866d 2 08.19.16
Suggested applications:
PowPak
® Fixture Sensor:
Great for individual control in cubicles
Maximize energy savings (fixtures in unoccupied
spaces do not turn on)
Simplifies the determination of what’s needed for a job
Radio Powr Savr
TM sensors:
- Cover large areas with a single sensor
- Sensor can mount anywhere in the space
- In order to turn on and off multiple fixtures together
(known as “grouping”), a Radio Powr Savr
TM
occupancy sensor must be used.
- In order to have a row of fixtures dim up or down
together in response to daylight, a Radio Powr Savr
TM
daylight sensor must be used.
Applications and Selecting the Right Control
Daylighting:
Radio Powr Savr
TM vs. PowPak® Fixture Sensor
PowPak
® wireless fixture controls have two options
for daylighting. The PowPak
® fixture sensor can
be used for simple, out-of-the-box daylighting.
The Radio Powr Savr
TM wireless daylight sensor
can be added for the ability to adjust and fine tune
daylighting settings.
Radio Powr Savr
TM daylight sensors provide the
ultimate flexibility in daylighting: target light level
(tuning) and gain value (through calibration) can be
adjusted independently. Daylighting rows / zones
can be setup so that multiple fixtures dim in unison
(also known as “grouping”). Radio Powr Savr
TM
daylight sensors can be placed anywhere since they
are completely wireless, and performance can be
optimized through placement and fine tuning.
PowPak
® fixture sensors are an easy way to add
simple daylighting to a localized area without
requiring setup. PowPak
® fixture sensors are quick
to install with a two-wire connection, and calibrate
automatically. Each PowPak
® fixture sensor should
be mounted within 2 ft (0.6 m) of the fixture it is
controlling.
2
FC-SENSOR, FC-VSENSOR, FCJ-010, FCJ-ECO
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LutronR PowPak® Fixture Controls
369866d 3 08.19.16
Wired:
Maximum of one (1) PowPak
® fixture sensor
occupancy/vacancy/daylighting sensor
Note: Only one PowPak® wireless fixture control
can be used per PowPak® fixture sensor, and only
one PowPak® fixture sensor can be used per
PowPak® wireless fixture control.
Wireless:
Maximum of ten (10) Pico
® wireless controls
Maximum of ten (10) Radio Powr Savr
TM
occupancy sensors
Maximum of one (1) Radio Powr Savr
TM
daylight sensor
Test
Link
Test
Link
Pico® wireless control
(up to 10)
Radio Powr SavrTM
occupancy sensor
(up to 10)
Radio Powr SavrTM
daylight sensor
(1 maximum)
PowPak®
wireless
fixture
control
PowPak
® fixture
sensor
The following can be used per each PowPak® wireless fixture control:
Notes:
When using a Radio Powr Savr
TM daylight sensor in conjunction with both a PowPak® wireless fixture control and
PowPak
® fixture sensor, the Radio Powr SavrTM daylight sensor will provide the daylighting input to the control
module, and the PowPak
® fixture sensor daylighting input will be ignored.
When using a Radio Powr Savr
TM occupancy sensor in conjunction with both a PowPak® wireless fixture control
and PowPak
® fixture sensor, occupancy data from both sensors is used; either one detecting occupancy will turn
the lights on, and the lights turn off only when both sensors have gone vacant (no longer detect occupancy).
Grouping can be accomplished by following the basic procedure described in the install guide found at
www.lutron.com for putting multiple control modules into association mode. This enables a Radio Powr Savr
TM
occupancy sensor or Radio Powr Savr
TM daylight sensor to group and control more than one fixture together.
Radio Powr Savr
TM occupancy sensors can be used with the PowPak® fixture sensor to add coverage area.
3
FC-SENSOR, FC-VSENSOR, FCJ-010, FCJ-ECO
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LutronR PowPak® Fixture Controls
369866d 4 08.19.16
Specifications
PowPak® Fixture Sensor
Regulatory Approvals
Complies with requirements for use in other spaces
used for environmental air (plenums) per
NEC
® 2014 300.22(C)(3)
FC-SENSOR, FC-VSENSOR:
cULus Listed
Power/Load
• Operating voltage: 12 V-
• Operating current: 25 mA
IEC SELV / NEC
® Class 2
Environmental
Ambient operating temperature: 32 °F to 104 °F
(0 °C to 40 °C), 0%–90% humidity, non-condensing;
indoor use only
Warranty
5 Year Limited Warranty. For additional Warranty
information, please visit: www.lutron.com/
TechnicalDocumentLibrary/Sensor_Warranty.pdf
Wiring
Sensor wires are IEC SELV / NEC
® Class 2 rated
Settings
Occupancy sensor timeout (fixture sensor):
15 minutes
Utilizes a green laser pointer (by others, not a LutronR
product) to associate Pico
® wireless controls and
Radio Powr Savr
TM sensors to PowPak® wireless
fixture controls via RF. See LutronR application note
#407 (www.lutron.com/GreenLaserAppNote) for more
information.
– Green laser specifications:
Wave output: constant
Wavelength: 532 nm
Output power: 5 mW maximum
2-wire connection between a PowPak
® fixture sensor
and a PowPak
® wireless fixture control
– The wires are interchangeable to eliminate miswiring
– The sensor comes with 2 ft (0.6 m) of wires
If hanging pendant fixtures, the maximum wire
length between fixture sensor and fixture control is
12ft (3.7 m). Sensor should be mounted no more
than 2 ft (0.6 m) from the fixture.
Sensor
Green Laser
!
WARNING
DANGER
Eye injury and/or blindness hazard; avoid direct eye exposure to laser beam.
Use of laser pointer is NOT recommended for use with LutronR products located near reflective surfaces.
• Do NOT aim or shine laser pointers at any person, pet, vehicle, or aircraft directly, or through reflection by mirrors or
other shiny surfaces. Do NOT view the laser beam through binoculars, magnifying glass, or other optical devices.
Do NOT allow children to use laser pointers.
Read and follow the laser pointer manufacturer’s instructions on safe use. In the event of injury, get
medical attention immediately.
4
FC-SENSOR, FC-VSENSOR, FCJ-010, FCJ-ECO
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LutronR PowPak® Fixture Controls
369866d 5 08.19.16
Specifications (continued)
Features
Occupancy Sensor:
Passive infrared motion detection with exclusive Lutron
®
XCT
TM Technology for major and minor motion detection.
360˚ field-of-view.
Up to 300 ft
2
(27.9 m
2
) major motion coverage and
150 ft
2
(13.9 m
2
) minor motion coverage.
Daylight Sensor:
Daylight sensor has simple, automatic calibration
out-of-the-box.
Designed to give a linear response to changes in
perceived light level.
Detects ambient light level changes from 0 lx to 1600 lx
(0 fc to 150 fc).
Daylight compensation through Lutron
® reliable closed
loop proportional control. For more information, see
www.lutron.com/TechnicalDocumentLibrary/daylighting_
white-paper.pdf
5
FC-SENSOR, FC-VSENSOR, FCJ-010, FCJ-ECO
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LutronR PowPak® Fixture Controls
369866d 6 08.19.16
Specifications (continued)
PowPak® Wireless Fixture Control
Regulatory Approvals
Complies with requirements for use in other spaces
used for environmental air (plenums) per
NEC
® 2014 300.22(C)(3)
Listed in accordance to CAN/ULC S102.2-2010 with
a Flame Spread Rating of 0 and a Smoke Developed
Classification of 40, with a minimum spacing of 6 ft
(1.83 m) off center
Title 20/24 certified lighting control device. Complies with
Title 20 and Title 24 section 110.9
Enables compliance with lighting control requirements in
ASHRAE 90.1 and IECC
FCJ-010, FCJ-ECO:
cULus Listed
IC (Canada)
NOM Certified
FCC Approved. Complies with the limits for a Class B
digital device, pursuant to Part 15 of the FCC Rule
Power / Load
Operating voltage: 120 –277 V~ 50/60 Hz
1 A switching maximum, electronic ballast or LED
driver for 010 V- load
No more than 3 drivers or ballasts
Standby power consumption < 1 W
• Works with all ballasts and drivers that provide a
current source compliant to IEC 60629 Annex E.2,
and whose inrush current does not exceed NEMA410
standards for electronic ballast/driver
FCJ-010
Controls up to 6 mA of 010 V- controlled fixtures.
Controls up to 3 ballasts or drivers (IEC 60929
Annex E.2 requires the ballast or driver to limit the
current draw to 2.0 mA maximum)
010 V- control link on FC-010 automatically
sources or sinks to third-party fixtures
FCJ-ECO
Connects to LutronR EcoSystemR LED drivers or
ballasts.
Controls up to 3 EcoSystem® ballasts or drivers
Multiple ballasts or drivers control only one
combined zone of lighting.
Environmental
Ambient operating temperature: 32 °F to 104 °F
(0°Cto 40 °C), 0%–90% humidity, non-condensing;
indoor use only
Wiring
Control wires can be run as either Class 1 or Class 2
– FCJ-010 (gray and violet wires)
– FCJ-ECO (violet wires)
6
FC-SENSOR, FC-VSENSOR, FCJ-010, FCJ-ECO
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LutronR PowPak® Fixture Controls
369866d 7 08.19.16
Specifications (continued)
Warranty
Please visit: www.lutron.com/TechnicalDocument
Library/369-119_Wallbox_Warranty.pdf
Frequency
431.0– 437.0 MHz (U.S.A., Canada)
Range
Wireless sensors and controls must be located within 60
ft (18 m) line of sight, or 30 ft (9 m), through walls, of the
associated control module.
Utilizes LutronR Clear ConnectR RF Technology
Settings
Low-end trim adjustment (default is 1 V- or ballasts/
drivers minimum for Lutron
® EcoSystem®).
High-end trim adjustment (default is 10 V- or
100 % for Lutron
® EcoSystem® ballasts/drivers).
Minimum Light Level Setting (optional). Certain
applications, such as hallways, may require that the lights
never turn off. For these areas, select the minimum light
level option and the load will lower to programed low-end
level.
Daylighting dims lights down to OFF. Occupancy sensor
must go unoccupied (vacant) in order for the PowPak
®
fixture sensor sensor to turn the lights off.
Occupied light level can be changed via the Radio Powr
Savr
TM occupancy sensor.
Favorite light level can be set using a PicoR wireless
control.
Power failure memory: If power is interrupted, connected
loads will return to the previous level prior to interruption
Mounting
Wireless fixture control mounts to a fixture or a U.S.-style
junction box through a standard 1/2 in (12.7 mm) knockout.
Note: The wireless fixture control needs to be accessible for
some programming steps. Record where
it is mounted so that it can be easily located later.
7
FC-SENSOR, FC-VSENSOR, FCJ-010, FCJ-ECO
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LutronR PowPak® Fixture Controls
369866d 8 08.19.16
Dimensions
Wireless Fixture Control
Measurements shown as: in (mm)
1/2 in or 21 mm trade size
knockout opening
2.82
(72)
1.25
(32)
24
(610)
3.125
(79)
Sensor
Measurements shown as: in (mm)
22 AWG
(0.33 mm
2
)
solid wire
3.42
(87)
3.94
(100)
1.5
(38)
3.368
(86)
0.65
(17)
8
FC-SENSOR, FC-VSENSOR, FCJ-010, FCJ-ECO
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LutronR PowPak® Fixture Controls
369866d 9 08.19.16
Sensor Detection Range
15 ft
(4.6 m)
9 ft
(2.7 m)
3 ft
(0.9 m)
0 3 ft
(0.9 m)
9 ft
(2.7 m)
15 ft
(4.6 m)
300 ft
2
(28 m
2
) major motion
Ceiling
Floor
9 ft
(2.7 m)
15 ft
(4.6 m)
9 ft
(2.7 m)
3 ft
(0.9 m)
0
3 ft
(0.9 m)
9 ft
(2.7 m)
15 ft
(4.6 m)
15 ft
(4.6 m)
9 ft
(2.7 m)
3 ft
(0.9 m)
0 3 ft
(0.9 m)
9 ft
(2.7 m)
15 ft
(4.6 m)
150 ft
2
(14 m
2
) minor
motion when mounted
on a 9 ft (2.7 m) ceiling
9.8 ft
(3 m)
6.9 ft
(2.1 m)
Recommended sensor
mounting height:
8-12 ft (2.4-3.7 m)
Definitions:
Major motion: Movement of a person entering or passing through an area.
Minor motion: Movement of a person occupying an area and engaging in small activities (e.g., reaching for a telephone,
turning the pages of a book, opening a file folder, picking up a coffee cup).
9
FC-SENSOR, FC-VSENSOR, FCJ-010, FCJ-ECO
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LutronR PowPak® Fixture Controls
369866d 10 08.19.16
NOTE: Wireless sensors and controls must be located within 60 ft (18 m) line of sight, or 30 ft (9 m), through walls,
of the associated control module.
30 ft (9 m)
Maximum
PowPak® Wireless Fixture Control
Install the fixture control directly to a fixture or
on a junction box nearest to the fixture. Install the sensor on the
ceiling near the fixture to optimize coverage in the desired area.
NOTE: Avoid mounting the fixture sensor in direct sunlight or
in the light which is cast from the fixture.
Pico® wireless control
Range Diagrams
Fixture Control
Sensor
10
FC-SENSOR, FC-VSENSOR, FCJ-010, FCJ-ECO
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LutronR PowPak® Fixture Controls
369866d 11 08.19.16
Wiring / System Diagram
Switched line
(Red)
Neutral (White)
Junction box or
fixture
1/2 in (21 mm) knockout opening
Conduit nut
From back of sensor
Line / Hot (Black)
Neutral
PicoR wireless control
(up to 10)
PowPak® wireless fixture control
PowPak® fixture sensor
Test
Link
Radio Powr SavrT daylight sensor
(1 maximum)
(Grey)
+ (Violet)
FCJ-010
010 V-
E1 (Violet)
E2 (Violet)
FCJ-ECO
EcoSystemR
polarity-free
digital link
or
0-10 V- or
EcoSystem
® Fixture
Ballast/Driver #1
Ballast/Driver #2
Ballast/Driver #3
Note: Multiple drivers/
ballasts connected
to FCJ-ECO will act
together as a single
zone.
Radio Powr SavrT occupancy sensor
(up to 10)
11