Lutron Systems
HomeWorks (14.0 and higher)
General System Rules
• 1 system can have up to 16 processors
• 1 system can have up to 10,000 switch legs
• Supports 16 concurrent Telnet logins (connected
directly to processor
• Each processor has either one or two links. Links
have a possible configuration of QS link, wireless link,
Power Panel link, or H48 link
– QS Link Rules
· 32 QS links maximum
· 99 QS devices per QS link
· 512 switch legs per link. Switch legs are the
smallest controllable outputs and include:
- Dimmed or switched circuits
- EcoSystem or DALIR digitally addressable
devices (ballasts, drivers, and interfaces)
- A single DMX channel
- Contact closure outputs
- Sivoia QS shade drives
· 100 occupancy sensors
· 100 wall controls (e.g.: Pico, QS Keypad, IR) per
QS link
· QS link is topology free (can be daisy-chained,
T-tapped, starred, etc.)
· Maximum link run of 2000 ft (610 m), using
12AWG (4.0 mm
2
) wires for power pair
· QS link can be extended up to an additional
2000ft (610 m) using the QSPS-10PNL. See
Lutron Spec Submittal P/N 085335 at
www.lutron.com for details
– Power Panel Link Rules (RPMs)
· 32 Power Panel links maximum
· 16 module interfaces per Power Panel link
· 256 switch legs per Power Panel link
· Power panel link must be daisy-chained
· Maximum link run of 2000 ft (610 m), using
12AWG (4.0 mm
2
) wires for power pair
· Panel link can be extended up to 3 times using the
MX-RPTR for a total distance of 8000 ft (2438m)
– Wireless Link Rules
· 15 links: USA, Canada, Mexico
· 6 links: UK, Europe, UAE
· 2 links: China, India, Singapore, Hong Kong
· 15 wireless links maximum*
· 4 repeaters per wireless link
· 95 devices per wireless link
· 100 switch legs per wireless link
· 5 wireless temperature sensors per wireless link
· 2500 ft
2
(250 m
2
) coverage per repeater
· 30 ft (9 m) from any non-repeater to repeater
· 60 ft (18 m) between repeaters
· 1000 ft (305 m) wire run between repeaters for
applications requiring greater distances (pool
house, boat house, guest house, etc.)
– KNet Rules
· 10 N4 interfaces per HomeWorks QS system
- 49 Ketra devices per N4
– N3 Satellite Limitations:
· One N3 is needed for Ketra Linear Fixtures (G2),
with the following limitations:
- 40 ft (12 m) maximum for linear fixture length
(40 1 ft [.31 m] segments)
- 100 ft (31 m) maximum run length (fixture length
plus cable length from N3 to end of last fixture)
· N3 output cable cannot be t-tapped
- One continuous strip of cable/linear fixtures
(no T-tap)
- Fixture runs and cable runs can be broken up
- Linear fixtures must be connected in a specific
orientation, with a distinct "in" and "out" end
– H48/Q96 Link Rules
· 32 H48/Q96 links maximum
· 4 H48/Q96 interfaces per H48/Q96 link
· 1000 ft (305 m) maximum wire run between
processor and H48/Q96 unit(s), daisy chain only
· 500 ft (152 m) maximum wire run off of each
H48bus output, but cannot exceed 1000 ft
(305m) total wire distance
· 48 HomeWorks wired Maestro devices per
H48interface
· 96 Sivoia QED shades per HWI-Q96 Interface
· 256 Sivoia QED shades per H48/Q96 Link
· HWI-Q96 and Sivoia QED shades requires a
license purchase (HQ-HWI-Q96-SW) to allow
activation and transfer
· Link translator (HQ-HWI-LX) required when the
wire run between processors and interfaces on an
H48/Q96 link type exceeds 50 ft (15 m)
(link terminator also required)
(continued on next page…)
* The maximum number of wireless links is not the same in every country.