SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LED Dimming Driver EcoSystem 5-Series LED Driver for Europe 5% Dimming
369815c 1 05.08.19
EcoSystem 5-Series LED Driver
(220240 V~, CE)
EcoSystem 5-Series LED Drivers provide a high
performance solution for any space in any
application, while providing smooth, continuous
dimming down to 5% of output current.
Features
Continuous, flicker-free dimming from 100% to 5%
1
Guaranteed dimming performance when used with
Lutron controls
Compatible with Energi Savr Node EcoSystem
and Energi Savr Node DALI® units, GRAFIK Eye
QS control unit with EcoSystem, GRAFIK Eye
QS control unit with DALI®, PowPak dimming
module with EcoSystem, Quantum systems and
HomeWorks QS systems, allowing for integration
into a planned or existing EcoSystem lighting
control solution
Protected from miswires of input power to
EcoSystem control inputs
Meets IEC 61347-2-13
SELV output
A rated lifetime of 50 000 hours
100% performance tested at factory
RoHS compliant
Non-volatile memory restores all settings after
power failure (EcoSystem control only)
Constant-current reduction dimming
For more information please go to:
www.lutron.com/5SeriesLED
1
Light output at 5% depends on the efficacy of the light engine used with the driver.
EcoSystem LED Driver, case type M
30 mm W x 25 mm H x 359 mm L
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LED Dimming Driver EcoSystem 5-Series LED Driver for Europe 5% Dimming
369815c 2 05.08.19
Specifications
Performance
Dimming Range: 100% to 5%
1
Dimming method: constant-current reduction
Refer to Lutron Application Note #360 (P/N 048360) at
www.lutron.com for details
Operating Voltage: 220–240 V~ 50/60 Hz
Lifetime: 50 000 hours
Patented thermal foldback protection
LED lighting turns on to any dimmed level without
flashing to full brightness
Non-volatile memory restores all driver settings after
power failure (EcoSystem control only)
Power Factor: λ > 0,95 at maximum power
Typical standby power consumption: 0,3 W
Meets Harmonics requirements for IEC-6000-3-2
Output open circuit protected
Output short circuit and overload protected
Turn-on time: < 100 ms typical from electronic off
Environmental
Sound rated: inaudible in 24 dB ambient
Relative Humidity: maximum 90% non-condensing
Operation Range: t
a
= 0 to 50 °C
(Where t
a
is the
temperature of the air directly surrounding the driver)
1
Light output at 5% depends on the efficacy of the light engine
used with the driver.
Regulatory Approvals and Compliance
CE compliant and ENEC certified:
Safety: IEC/EN 61347-2-13
– Emissions: CISPR15/EN55015, IEC 61000-3-2, 3-3
Immunity: IEC/EN 61547,
IEC/EN 61000-4-2, -4-3, -4-4, -4-6, -4-11
Performance: IEC/EN 62384
RoHS 2006 Compliant
Meets IEC 60529, IP20 Rating
DALI® Compliant
Meets the following:
IEC62386-207 ed. 1.0
IEC62386-101 ed. 1.0
IEC62386-102 ed. 1.0
Lutron Quality Systems registered to ISO 9001.2015
Manufacturing facilities employ ESD reduction
practices that comply with the requirements of
ANSI/ESD S20.20
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LED Dimming Driver EcoSystem 5-Series LED Driver for Europe 5% Dimming
369815c 3 05.08.19
Driver Wiring & Mounting
Driver must be grounded by a mounting screw to the
grounded fixture.
Note: Ground termination not provided on driver. Terminate
ground in compliance with local electric codes.
Fixture must be grounded in accordance with local
and national electrical codes.
Terminal blocks on the driver accept one solid wire
per terminal from 0,75 mm
2
to 1,5 mm
2
(18 AWG to
16 AWG).
Maximum driver–toLED light engine wire length
OEM Notes
For best dimming performance, Lutron recommends
electrical insulation with 50 / 60 Hz impedance of at
least 12 MΩ and minimum breakdown voltage of at
least 1 500 V~ between LEDs and fixture chassis.
Maximum number of drivers on miniature circuit
breaker:
– 16 A Type B: 14 drivers
– 16 A Type C: 24 drivers
Wire Gauge
Maximum Lead Length
700 mA to 1,33 A
0,75mm( (18 AWG) 4,5 m
1,5mm( (16 AWG) 7,5 m
2,5mm( (14 AWG) 12 m
4,0mm( (12 AWG) 18 m
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LED Dimming Driver EcoSystem 5-Series LED Driver for Europe 5% Dimming
369815c 4 05.08.19
How to Build a Model Number: EcoSystem 5-Series
LDE55E1CMN - UA xxx
Current Level (for Constant Current):
070 = 0,70A; 071 = 0,71A . . . 133 = 1,33A
example: LDE55E1CMN-UA070
For further assistance selecting your model
number, contact our LED Center of Excellence
at LEDs@lutron.com
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LED Dimming Driver EcoSystem 5-Series LED Driver for Europe 5% Dimming
369815c 5 05.08.19
Load learning
What is load learning?
Each Lutron constant-current LED driver is able to operate over a range of LED load voltages. In order to operate
with optimum efficiency, these drivers continuously sense the LED load voltage and make adjustments to their
internal operation.
When does load learning happen?
Load learning happens continuously and in most cases is imperceptible. However, when a new load is connected
to the driver it will take some time for the LED driver to adapt. A driver may be performing load learning during
R&D/bench testing, production testing, or QwikFig/AirFig configuration when using a real load. If a driver was not
allowed to learn its load during the fixture production process, it may happen when first installed in the final
location.
What does load learning look like?
Depending on the difference in forward voltage of the new load versus the last load the driver learned, one of the
following may be observed:
1. The load may seem to operate properly.
2. The load may turn on at a low light level and remain there for a few seconds before transitioning to full light.
3. The load may turn on for a very brief flash, then go off for a few seconds before turning back on again.
4. There may be no light output at all for up to 20 seconds.
How do I make a driver “learn” a new load?
Although this process will happen on its own during normal usage, Lutron recommends the following procedure
be carried out before attempting to confirm proper operation:
1. Power up the LED driver on the intended load.
2. Once the light seems to be stable at full output, which may take 20 to 30 seconds, leave the driver on for another
20 seconds for the driver to learn the load voltage and commit it to memory.
Note: There is no limit to the number of times a driver can learn a new load.
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LED Dimming Driver EcoSystem 5-Series LED Driver for Europe 5% Dimming
369815c 6 05.08.19
Driver Type Output Dimming Method Output Voltage Output Current Output Power Standards Recognition
Constant Current Driver
(SELV)
Constant Current Reduction
(CCR)
30 – 50 V- 0,70 – 1,33 A 25 – 50 W Meets IEC 61347-2-13
“U” Output Range
Typical Performance Specifications:
Parameter Value Test Conditions
Input Current 0,27 A V
i
= 230 V, t
a
= 25°C, I
o
= 1,0 A, V
o
= 50 V,
Max. Light Output
Power Factor 0,98
THD 13%
Driver Efficiency 86%
THD (%)
THD vs. Output Power
25 30 35 40 45 50
Output Power (W)
25
20
15
0
230 V~
10
5
Efficiency @ Pmax (%)
Efficiency vs. Output Current
0,7 0,85 1,0 1,15 1,3
Output Current (A)
90
85
75
230 V~
80
95
Power Factor
Power Factor vs. Output Power
25 30 35 40 45 50
Output Power (W)
1,00
0,95
0,85
230 V~
0,90
Voltage (V)
Load Compatibility
0,50 0,70 0,90 1,10 1,30 1,50
Output Current (A)
50
40
230 V~
30
60
50 W
25 W
6
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LED Dimming Driver EcoSystem 5-Series LED Driver for Europe 5% Dimming
369815c 7 05.08.19
D
C
B
A
M Case: Case Dimensions
A 359 mm
B 347 mm (mounting center)
C 30 mm
D 25 mm
7
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LED Dimming Driver EcoSystem 5-Series LED Driver for Europe 5% Dimming
369815c 8 05.08.19
EcoSystem LED Driver Wiring Diagrams
EcoSystem Digital Link Overview
The EcoSystem Digital Link wiring (E1 and E2)
connects the drivers together to form a lighting
control system.
For EcoSystem link limits, refer to EcoSystem
control specifications.
E1 and E2 (EcoSystem digital link wires) are polarity
insensitive and can be wired in any topology.
• An Energi Savr Node unit with EcoSystem,
GRAFIK Eye QS control unit with EcoSystem,
PowPak dimming module with EcoSystem,
Quantum system, or HomeWorks QS system
provides power for the EcoSystem Digital Link and
supports system programming.
• All EcoSystem Digital Link programming is
completed by using the Energi Savr App for Apple
iPad, iPod Touch or iPhone mobile digital devices,
GRAFIK Eye QS with EcoSystem, PowPak dimming
module with EcoSystem, Quantum system, or
HomeWorks QS system.
EcoSystem Digital Link Wiring
Driver EcoSystem Digital Link terminals only accept
one 0,75 mm
2
to 1,50 mm
2
(18 AWG to 16 AWG)
solid copper wire per terminal.
Make sure that the mains breaker to the driver and
EcoSystem Digital Link Supply is OFF when wiring.
Connect the two conductors to the two driver
terminals E1 and E2 as shown.
To avoid confusion and shorting the link when daisy
chaining several drivers, the use of different color
wires is recommended.
Consult applicable electrical codes for proper wiring
practices.
Notes
The EcoSystem Digital Link Supply does not have to
be located at the end of the Digital Link.
EcoSystem Digital Link length is limited by the wire
size used for E1 and E2 as follows:
Wire Size Digital Link Length
(maximum)
4,00 mm
2
(12 AWG) 800 m*
2,50 mm
2
(14 AWG) 500 m*
1,50 mm
2
(16 AWG) 300 m
1,00 mm
2
(18 AWG) 200 m
0,75 mm
2
(18 AWG) 150 m
To other EcoSystem
Digital Link
compatible devices
EcoSystem Digital Link Wiring
Ballast Installation Requirements
EcoSystemR H-Series
Socket Wiring:
Use 0,75 mm
2
solid copper or tinned stranded wire. Refer
to ballast label and socket manufacturer for proper strip length.
For proper wiring:
Follow wiring schematic on ballast.
Socket Lead Length Requirements:
2 m
Lamp Type Max. Length of Leads
(ballast to socket)
T5 Linear
T8 Linear
Make sure yellows are wired in parallel, not in series.
Ballast wire strip lengths:
For power, output, and digital terminals (E1, E2).
Solid copper
wire
8 mm
Correct Incorrect
Wiring to two lamps
Lamp Wiring
Note:
Yellows wired
in parallel
BLU
BLU
RED
RED
YEL
YEL
Blue
Ye llow
Red
Ballast Mounting
Correct
Incorrect
Mount ballast flush against fixture to provide best heat transfer. Also,
avoid mounting ballast close to heat source such as fixture cover plate.
Side by side mounting
Lamp Mounting Height Requirements:
Lamp Type Lamp Mounting Height
T8 Linear 3,2 mm to 19,1 mm
T5 Linear 3,2 mm to 12,7 mm
IMPORTANT:
Lamps must never
touch earth plane and
should be placed
without obstruction.
Lamp
Lamp Socket
(side view)
Mounting height
Earthed
metal
Ballast
Lamp
When installing more than one ballast in a fixture, contact Lutron Technical Support
for specific guidelines to maximize performance.
Ballast
Lamp
Ballast
Lamp
Ballast
Lamp
Ballast
Lamp
Ballast
Ballast
Ballast must be electrically earthed for proper
performance and to meet local wiring requirements.
Earthing should be accomplished with mounting
hardware to ensure electrical connection through ballast
enclosure and through fixture.
BalastoBallast
Ballast
Must be at least
150 mm apart.
Warranty
For Lutron ballast warranty, please visit
www.lutron.com/ResourceLibrary/warranty/Limited%20Comm.pdf.
Lutron warranty does not cover costs or damages caused by
misapplication or improper installation.
EcoSystemR Digital Link Wiring
E1
E2
N
L
Digital
Link
E1
E2
N
L
Digital
Link
Power Input
(Mains Voltage):
EcoSystem
R
Digital Link
0,75 to 1,5 mm
2
solid copper wire
0,75 to 1,5 mm
2
solid copper wire
NE1LE2
WARNING: Shock hazard.
May result in serious injury or
death. Disconnect power before servicing or installing.
Wire Gauge Digital Link
Length (max)
4,0 mm
2
825 m
2,5 mm
2
515 m
1,5 mm
2
310 m
1,0 mm
2
205 m
0,75 mm
2
155 m
MainsMains
Power Wiring
Rapid Start
(Rotary Locking
Variety)
Rapid Start
(Slide-In Variety)
Sockets
Lutron requires sockets complying with IEC 60400.
Inspect sockets for marks to ensure the socket complies with IEC 60400.
Two examples of these marks are:
E
and
Q
.
Use Rapid Start sockets.
Do NOT use Instant Start sockets.
See Lutron App Note #122.
Lamps
Dimming Performance: For proper dimming performance lamps must be IEC
compliant.
Temperature: Avoid operating with cold air blowing directly on lamps. LutronR ballasts
are designed to strike the lamps when the lamp temperature is at a minimum of 10 ºC.
See lamp manufacturer’s specifications for maximum lamp temperature.
041-342a 02/2012
Lutron, EcoSystem and are registered trademarks of Lutron Electronics Co., Inc.
Technical Assistance
For questions concerning the installation or operation of this product,
call the Lutron Technical Support Center. Please provide exact model
number when calling.
Europe +44.(0)20.7680.4481
Monday-Friday 9:00 to 19:00 GMT
Brazil +55.11.3257.6745
Monday-Friday 8:30 to 17:30 BRT
Outside Europe and Brazil 1.800.523.9466
24 hours per day, 7 days per week
www.lutron.com
Driver
Terminals
* For DALI® applications, the maximum permissible link length is 300 m
8
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LED Dimming Driver EcoSystem 5-Series LED Driver for Europe 5% Dimming
369815c 9 05.08.19
Hi-lume
A-Series
**
Dimmed Hot
Switched Hot
Neutral
Ground
To
3-wire
Dimming
Control
+V
Ground*
-V
LED
light
engine
Hi-lume
A-Series
**
Dimmed Hot
Neutral
Ground
To ELV
Dimming
Control
+V
Ground*
-V
LED
light
engine
RED
BLUE
YELLOW
BLUE/WHITE
LAMPS
7 ft Max. lead length
P/N 500-13362 Rev. A
NEU
N/C
SH
B/WB/W BLUBLURED YEL YEL
E1
E2
NEUTRAL
SWITCHED HOT
TO
EcoSystem
® H
BUS
E1
E2
Ecosystem® H
Ballast
C
A
L
I
B
R
A
T
I
O
N
P
O
I
N
T
Coopersburg, PA 18036 USA
RED
Programmed Rapid Start
1% Electronic Fluorescent Dimming
Ballast
CLASS 2
BUS
LINE
®
Solid 18 or 16 AWG
wire for power and bus terminals
18 AWG wire only for lamps.
5/16 in
(8 mm)
1-800-523-9466
Copper wire only
Consult lamp manufacturer for lamp seasoning
requirements prior to dimming.
Warranty void if unit is opened.
WARNING: Shock hazard. May result in serious injury or
death. Disconnect power before servicing or installing.
Calibration point temperature not to exceed 65 °C.
Maximum case temperature 75 °C.
Ecosystem® H
TO LINE
VOLTAGE
SOURCE
Pantone
362
500-13362 Rev. A
Label Size: 6.87” x 2.125”
Corner Radius: 0.0625”
Colors:
Pantone
186
Pantone
1585
Pantone
116
Pantone
3005
Pantone
2583
Pantone
Black
Wiring Diagram for EcoSystem Digital Control
ATTENTION
ELECTRICIANS AND CONTRACTORS
Driver Leads
Lead lengths from driver to LED light engine must
not exceed the values in the table.
Wiring
Drivers must be installed per national and local
electrical codes.
Maximum Operating Temperature
Drivers must not exceed the rated calibration point
temperature (t
c
).
ATTENTION
FACILITIES MANAGERS
SERVICE
Warranty
For warranty information, please see
www.lutron.com/ballastdriverwarranty
Replacement Parts
Use replacement parts with exact Lutron model
numbers. Consult Lutron if you have any questions.
Contact Information
For further information, please visit us at
http://www.lutron.com/europe or contact Lutron
Customer Assistance at
+44.(0)20.7702.0657 (Europe)
+1.610.282.3800 (USA Headquarters)
Please provide exact model number when calling.
Neutral
EcoSystem
5-Series
LED Driver
V+ (Red)
LED
light
engine
V- (Black)
To Mains
To
EcoSystem
digital link
Line / Hot
E1
E2
Wire Size
Maximum Lead Length
700 mA to 1,33 A
0,75mm( (18 AWG) 4,5 m
1,5mm( (16 AWG) 7,5 m
2,5mm( (14 AWG) 12 m
4,0mm( (12 AWG) 18 m
)Lutron, Lutron, EcoSystem, Energi Savr Node, GRAFIK Eye, HomeWorks, PowPak, and Quantum are trademarks or registered trademarks of
Lutron Electronics Co., Inc. in the U.S. and other countries.
Apple, iPad, iPod Touch, and iPhone are trademarks of Apple Inc., registered in the U.S. and other countries.
DALI is a registered trademark of ZVEI - Zentralverband Elektrotechnik-undElektronikindustrie e.V.
9