SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
LED Dimming Driver EcoSystemTM 5-Series LED Driver for Europe 5% Dimming
369815b 7 04.24.15
EcoSystem
T
LED Driver Wiring Diagrams
EcoSystemT Digital Link Overview
• The EcoSystemT Digital Link wiring (E1 and E2)
connects the drivers together to form a lighting
control system.
• For EcoSystemT link limits, refer to EcoSystemT
control specifications.
• E1 and E2 (EcoSystemT digital link wires) are polarity
insensitive and can be wired in any topology.
• An Energi Savr NodeT unit with EcoSystem
R,
GRAFIK Eye
R QS control unit with EcoSystemR,
PowPak
R dimming module with EcoSystemR,
Quantum
R system or HomeWorksR QS system
provides power for the EcoSystemT Digital Link and
supports system programming.
• All EcoSystemT Digital Link programming is
completed by using the Energi Savr App for Apple
iPad, iPod Touch or iPhone mobile digital devices,
GRAFIK Eye
R QS with EcoSystemR, PowPakR
dimming module with EcoSystem
R, QuantumR
system or HomeWorks
R QS system.
EcoSystemT Digital Link Wiring
• Driver EcoSystemT Digital Link terminals only accept
one 0.75 mm
2
to 1.50 mm
2
(18 AWG to 16 AWG)
solid copper wire per terminal.
• Make sure that the mains breaker to the driver and
EcoSystemT Digital Link Supply is OFF when wiring.
• Connect the two conductors to the two driver
terminals E1 and E2 as shown.
• To avoid confusion and shorting the link when daisy
chaining several drivers, the use of different color
wires is recommended.
• Consult applicable electrical codes for proper wiring
practices.
Notes
• The EcoSystemT Digital Link Supply does not have
to be located at the end of the Digital Link.
• EcoSystemT Digital Link length is limited by the wire
size used for E1 and E2 as follows:
Wire Size Digital Link Length
(maximum)
4.00 mm
2
(12 AWG) 800 m*
2.50 mm
2
(14 AWG) 500 m*
1.50 mm
2
(16 AWG) 300 m
1.00 mm
2
200 m
0.75 mm
2
(18 AWG) 150 m
To other EcoSystemT
Digital Link
compatible devices
EcoSystemT Digital Link Wiring
Apple, iPad, iPod Touch, and iPhone are trademarks of Apple Inc., registered in the U.S. and other countries.
Ballast Installation Requirements
EcoSystemR H-Series
Socket Wiring:
Use 0,75 mm
2
solid copper or tinned stranded wire. Refer
to ballast label and socket manufacturer for proper strip length.
For proper wiring:
Follow wiring schematic on ballast.
Socket Lead Length Requirements:
2 m
Lamp Type Max. Length of Leads
(ballast to socket)
T5 Linear
T8 Linear
Make sure yellows are wired in parallel, not in series.
Ballast wire strip lengths:
For power, output, and digital terminals (E1, E2).
Solid copper
wire
8 mm
Correct Incorrect
Wiring to two lamps
Lamp Wiring
Note:
Yellows wired
in parallel
BLU
BLU
RED
RED
YEL
YEL
Blue
Ye llow
Red
Ballast Mounting
Correct
Incorrect
Mount ballast flush against fixture to provide best heat transfer. Also,
avoid mounting ballast close to heat source such as fixture cover plate.
Side by side mounting
Lamp Mounting Height Requirements:
Lamp Type Lamp Mounting Height
T8 Linear 3,2 mm to 19,1 mm
T5 Linear 3,2 mm to 12,7 mm
IMPORTANT:
Lamps must never
touch earth plane and
should be placed
without obstruction.
Lamp
Lamp Socket
(side view)
Mounting height
Earthed
metal
Ballast
Lamp
When installing more than one ballast in a fixture, contact Lutron Technical Support
for specific guidelines to maximize performance.
Ballast
Lamp
Ballast
Lamp
Ballast
Lamp
Ballast
Lamp
Ballast
Ballast
Ballast must be electrically earthed for proper
performance and to meet local wiring requirements.
Earthing should be accomplished with mounting
hardware to ensure electrical connection through ballast
enclosure and through fixture.
BalastoBallast
Ballast
Must be at least
150 mm apart.
Warranty
For Lutron ballast warranty, please visit
www.lutron.com/ResourceLibrary/warranty/Limited%20Comm.pdf.
Lutron warranty does not cover costs or damages caused by
misapplication or improper installation.
EcoSystemR Digital Link Wiring
E1
E2
N
L
E1
E2
N
L
Digital
Link
Power Input
(Mains Voltage):
EcoSystem
R
Digital Link
0,75 to 1,5 mm
2
solid copper wire
0,75 to 1,5 mm
2
solid copper wire
NE1LE2
WARNING: Shock hazard.
May result in serious injury or
death. Disconnect power before servicing or installing.
Wire Gauge Digital Link
Length (max)
4,0 mm
2
825 m
2,5 mm
2
515 m
1,5 mm
2
310 m
1,0 mm
2
205 m
0,75 mm
2
155 m
MainsMains
Power Wiring
Rapid Start
(Rotary Locking
Variety)
Rapid Start
(Slide-In Variety)
Sockets
Lutron requires sockets complying with IEC 60400.
Inspect sockets for marks to ensure the socket complies with IEC 60400.
Two examples of these marks are:
E
and
Q
.
Use Rapid Start sockets.
Do NOT use Instant Start sockets.
See Lutron App Note #122.
Lamps
Dimming Performance: For proper dimming performance lamps must be IEC
compliant.
Temperature: Avoid operating with cold air blowing directly on lamps. LutronR ballasts
are designed to strike the lamps when the lamp temperature is at a minimum of 10 ºC.
See lamp manufacturer’s specifications for maximum lamp temperature.
041-342a 02/2012
Lutron, EcoSystem and are registered trademarks of Lutron Electronics Co., Inc.
Technical Assistance
For questions concerning the installation or operation of this product,
call the Lutron Technical Support Center. Please provide exact model
number when calling.
Europe +44.(0)20.7680.4481
Monday-Friday 9:00 to 19:00 GMT
Brazil +55.11.3257.6745
Monday-Friday 8:30 to 17:30 BRT
Outside Europe and Brazil 1.800.523.9466
24 hours per day, 7 days per week
www.lutron.com
Driver
Terminals
* For DALI applications, the maximum permissible link length is 300 m