EcoSystem H10-Series Reduced Wattage Fluorescent Dimming Ballasts
369785h 7 11.29.17
EcoSystem H10-Series Wiring Diagrams
EcoSystem Digital Link Overview
• The EcoSystem Digital Link wiring (E1 and E2) connects
the digital ballasts and drivers together to form a lighting
control system.
• Sensors do not directly connect to EcoSystem
H10-Series ballasts.
• No 3-wire phase control with EcoSystem H10-Series
ballasts.
• E1 and E2 (EcoSystem digital link wires) are polarity
insensitive and can be wired in any topology.
• An Energi Savr Node with EcoSystem, GRAFIK Eye QS
control unit with EcoSystem, PowPak dimming module
with EcoSystem, or a Quantum system provides power
for the EcoSystem digital link which supports up to
64digital ballasts or LED drivers, 64occupant sensors,
16daylight sensors and 64 wall stations or IR receivers.
• PowPak dimming module with EcoSystem provides
power for the EcoSystem digital link which supports
up to 32 digital ballasts or LED drivers, 6 occupant
sensors, 1 daylight sensor and 9 Pico wireless
controllers.
• All EcoSystem Digital Link programming is completed by
using the Energi Savr App for Apple iPad, iPod Touch or
iPhone mobile digital devices, PowPak dimming module
with EcoSystem, GRAFIK EyeQS with EcoSystem, or
Quantum systems.
• For complete information, see EcoSystem Design &
Application guide P/N 367-1533 at www.lutron.com
EcoSystem Digital Link Wiring
• Make sure that the supply breaker to the Digital Ballast
and EcoSystem Digital Link Supply is OFF when wiring.
• Connect the two conductors to the two Digital Ballast
terminals E1 and E2 as shown.
• Using two different colors for E1 and E2 will reduce
confusion when wiring several ballasts together.
EHDTXXXMUXRW and -RWN Models Only
• For emergency wiring please see Lutron App Note #106.
• The EcoSystem Digital Link may be wired Class 1 or
IEC PELV/NECR Class 2. Consult applicable electrical
codes for proper wiring practices.
E1
E2
N
L
Digital
Link
E1
E2
N
L
Digital
Link
LINE/
MAINS
LINE/
MAINS
N/C
N/C
Ballast Terminals
Ballast Terminals
To the EcoSystem Digital Link Supply and up
to 64 total ballasts
Notes
• The EcoSystem Digital Link Supply does not have to
be located at the end of the Digital Link.
• EcoSystem Digital Link terminals accept one
18to 16AWG (0.75 to 1.5mm() solid copper wire
perterminal. Use pigtails for larger gauge wires.
• EcoSystem Digital Link length is limited by the wire
gauge used for E1 and E2 as follows:
Wire Gauge
Maximum
Digital Link Length
12 AWG 2200 ft
14 AWG 1400 ft
16 AWG 900 ft
18 AWG 550 ft
Wire Size
Maximum
Digital Link Length
4.0 mm( 825 m
2.5 mm( 515 m
1.5 mm( 310 m
1.0 mm( 205 m
0.75 mm( 155 m