GP Dimming PanelsGRAFIK Systems® Power Equipment
369401e 4 03.25.16
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Standards
•ULRListed(Reference:ULFileE42071).
•ComplieswithCSAorNOM(whereappropriate).
•CaliforniaEnergyCommissionListed
•SeismicCertied(TestMethodAC156.Reference
OSHPDPreapprovalOSP-0215-10).
Power
•Inputpower:120V~and277V~,50/60Hz,phase-
to-neutral.
•BranchCircuitCapacity:
–120V~(upto2000W/VA)
–277V~(4500W/VA)
–Minimumload:25W
•NumberofCircuits:3–144
•BranchCircuitBreakers:ULRratedthermalmagnetic.
AICratings(otherratingsavailable):
–120V~(10,000A)
–277V~(14,000A)
•Lightningstrikeprotection:MeetsANSI/IEEEstandard
62.41-1980. Can withstand voltage surges of up to
6000V~andcurrentsurgesofupto3000A.
•10-yearpowerfailurememory:Automaticallyrestores
lighting to scene selected prior to power interruption.
Sources/Load Types
Operatesthesesourceswithasmoothcontinuous
SquareLawdimmingcurveoronafull-conduction,
non-dimmingbasis:
•Incandescent(Tungsten)/Halogen
•MagneticLow-VoltageTransformer
•LEDdriversspeciedbythemanufacturertowork
with forward-phase dimming controls. *
•Electroniclow-voltagetransformersspeciedbythe
manufacturertoworkwithforward-phasedimming
controls.
•Lutron
®ElectronicFluorescentDimmingBallasts
•MagneticFluorescentLampBallasts
•Optionalmodulesallowforcontrolof0–10V-,DSI,
and PWM load types.
•OperatesHIDsourcesonafull-conduction,
non-dimmingbasis.
Wiring
•Internal:Pre-wiredbyLutron.
•Systemcommunications:Low-voltageIECPELV/NEC
®
Class 2 wiring connects dimming panels to other
components.
•Line(mains)voltage:Feed,load,andcontrolcircuit
wiringonly;nootherwiringorassemblyrequired.
Filter Chokes
•Loadcurrentrisetimeismeasuredata90-degree
conduction angle.
•10–90%ofload-currentwaveform:
–350µSecrisetimeat50%dimmercapacity.
–400µSecrisetimeat100%dimmercapacity.
•0–100%ofload-currentwaveform:
–525µSecrisetimeat50%dimmercapacity.
–600µSecrisetimeat100%dimmercapacity.
•Atnopointinthewaveformcantherateofcurrent
changeexceed300mAperµSec.
•ConsultLutronforhigherrisetimeoptions.
Dimming Cards
•Panelcurrentratingsarelistedforcontinuous
operation;UL®listedspecicallyforeachlightsource.
•RTISS
®ltercircuittechnologycompensatesfor
incominglinevoltagevariations;novisibleickerwith
+/–2%changeinRMSvoltage/cycleand+/–2%Hz
change in frequency/second.
•Arclessrelayair-gapOFFswitches(oneperload
circuit)ensureopenloadcircuitswhenOFFfunction
is selected; eliminate arcing at mechanical contacts
when loads are switched.
Physical Design
•Enclosure:NEMA-Type1(Type2availableonrequest);
IP-20protection;16U.S.GaugeSteel;indooruseonly.
•Weight:30to1300lb(14to590kg).
•Mounting:Surface-mountonly.Allowspacefor
ventilating.
•SeismicCerticationLimits:SDS=2.5g,z/h=1.0,
IP=1.5forwallorwall/oormountedpanels.
SDS=1.5gforoor-mountpanelsonly.Contact
Lutronfordetails.
Environment / Heat Dissipation
•Patented,ribbedaluminumheatsinkbasecoolspanel
byconvection;nofans.
•32°F–104°F(0°C–40°C);relativehumiditylessthan
90%,non-condensing.
Specifications: 120/277 V~
continued on next page…
* LutroncannotguaranteecompatibilitywithuntestedLEDdrivers.RefertotheLEDProductSelectiontoolatwww.lutron.com/ledtoolforalistof
compatibleproducts.