SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
QS Sensor Module QSM Sensor Interfaces
369242p 3 11.08.19
Specifications
QS Sensor Module (QSM)
Power
• 24 – 36 V-
• Maximum current draw:
- 400 mA (models with wired input)
- 100 mA (models without wired input)
• Power Draw Units (PDU): Refer to the QS Link Power
Draw Units specification submittal (P/N 369405) for
information concerning PDUs on the QS link. Use only
Lutron approved power sources.
• 10-year power failure memory: restores settings and
programming after power interruption.
Regulatory
• Lutron quality systems registered to ISO 9001.
• RoHS compliant
• Wireless receiver (Rx) device. Product has no wireless
transmit functionality.
QSM2 –
• cUL US Listed (U.S.A. and Canada)
•
FCC Compliant. Complies with the limits for a ClassB digital
device, persuant to Part 15 of the FCC Rules (U.S.A.).
• IC Certified. (Canada)
• SCT Certified (Mexico)
QSM3 –
• CE Marked (European Union)
QSM5 –
• WPC Type Approved (India)
QSM7 –
•
FCC Compliant. Complies with the limits for a ClassB digital
device, persuant to Part 15 of the FCC Rules (U.S.A.).
Environment
• Ambient Temperature Operating Range:
32 ºF to 104ºF (0ºC to 40 ºC).
• Relative humidity: less than 90% non-condensing.
• For indoor use only.
Terminals
• Input wiring: 22 AWG to 12 AWG (0.5 mm
2
to 4.0 mm
2
)
• QS link wiring: 22 AWG to 12 AWG (0.5 mm
2
to 4.0 mm
2
)
Mounting
• QSM units should be mounted in the middle of non-
metal ceiling tile or drywall, visible from inside the
space.
• Installation near metal other than a junction box may
reduce RF range.
Wireless Communication
(models with wireless inputs only)
• RF Range: 60 ft (18 m) line of sight or 30 ft (9 m)
through typical construction materials.
• To ensure optimal wireless range, install the QSM in
the ceiling in a visible position from inside the space.
• Radio Powr Savr occupancy / vacancy sensor
(upto10)
• Radio Powr Savr daylight sensor (up to 10)
• Pico wireless control (up to 10)
Wired Inputs
• There are 4 universal wired inputs. Each input can
accept one of the following:
- EcoSystem wallstation (CC- series)
- Occupancy sensor (LOS- series)
- Daylight sensor (EC-DIR- series)
- EcoSystem IR receiver (EC-IR or EC-DIR- series)
- Wired Pico
control (PX- series)
• Use of both the infrared receiver and daylight sensor
on the EC-DIR- series sensors is considered two
wired inputs on a QSM
• Maximum wiring distance = 150 ft (46 m)
• Only wired (LOS- series) and wireless
occupancy / vacancy sensors may be used in
myRoom; no Ecosystem wallstations, daylight
sensors, Ecosystem IR receivers or wired
Picocontrols
QS Link Limits
• The QS link can have up to 100 devices.
• Each QSM counts as 1 device towards the
100device limit.
• Each QSM draws 3 Power Draw Units (PDUs) on the
QS link.
•
Wired sensors add to the PDU draw of a QSM. Refer to
the QS Link Power Draw Units specification submittal
(P/N 369405) for information concerning PDUs.
• QS link maximum wire run length is 2000 ft (610 m).
• See the commercial system rules spec (P/N 369821)
for system specific limitations.