Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
Maestro® Occupancy Sensing Switch Switch with Occupancy and Vacancy Sensor
369659a 1 05.31.12
Maestro
®
Occupancy Sensing Switch
Lutron
®
Maestro
®
Occupancy Sensing switches with occupancy and vacancy sensors are lighting
controls with passive infrared sensors that automatically control the lights in an area. These sensors
detect the heat from occupants moving within an area to determine when the space is occupied.
The Occupancy Sensing switch combines a Maestro
®
switch with an occupancy or vacancy sensor.
Family Features
• Passive infrared motion detection with exclusive Lutron
®
XCTTM Technology for fine motion detection
N eutral wire is required
• 180° sensor field-of-view
• Upto30ftx30ft(9mx9m)[900ft
2
(81m
2
)]majormotioncoverageand20ftx20ft(6mx6m)
[400ft
2
(36m
2
)]minormotioncoverage180° field-of-view
• Occupancyversioncanbesettoauto-on/auto-offormanual-on/auto-off
• VacancyversionavailabletomeetCAtitle24requirements
• Adjustabletimeout–1,5,15,or30minutes
• High-lowsensitivityadjustment
• OccupancySensingswitchlightingloads:incandescent,halogen,MLV,ELV,CFL,LED,magneticfluorescent,and
electronic fluorescent
• Workswithasinglestandard3-wayswitchorupto9companionswitches(MA-AS-XX,MSC-AS-XX,MA-AS-277-XX,
orMSC-AS-277-XX**).Standard3-wayswitchcannotbecombinedwithcompanionswitch.Totalblueterminal
wirelengthmaybeupto150ft(46m).
** XX in model number represents color/finish code
Occupancy Sensing switch:
MS-OPS6M2N-DV-XX
Occupancy/vacancy
single-pole/multi-
location120-277V~
Auto-on/auto-offor
manual-on/auto-off
6
Alighting(
120-277V~
)
3
Afan(
120V~ only
)
MS-VPS6M2N-DV-XX
Vacancysingle-pole
multi-location
120-277V~
Manual-on/auto-off
6
Alighting(
120-277V~
)
3
Afan(
120V~ only
)
* For additional Maestro
®
Occupancy Sensing switch options, see Lutron P/N 369270 (model number: MS-OPS6M-DV) and P/N 369488
(MS-OPS2, MS-OPS5M, and MS-OPS6M2-DV).
1
Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
Maestro® Occupancy Sensing Switch Switch with Occupancy and Vacancy Sensor
369659a 2 05.31.12
Colors and Finishes
Gloss Finishes Satin Finishes
Taupe
TP
Turquoise
TQ
Plum
PL
Merlot
MR
Terracotta
TC
Sienna
SI
Midnight
MN
Hot
HT
DesertStone
DS
Duetoprintinglimitations,colorsandnishesshowncannotbeguaranteedtoperfectlymatchactual
product colors.
Eggshell
ES
Biscuit
BI
Snow
SW
Palladium
PD
Greenbriar
GB
Bluestone
BG
Mocha
Stone
MS
Goldstone
GS
Sea Glass
SG
Stone
ST
Limestone
LS
White
WH
Gray
GR
Brown
BR
Ivory
IV
Almond
AL
Black
BL
Light
Almond
LA
2
Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
Maestro® Occupancy Sensing Switch Switch with Occupancy and Vacancy Sensor
369659a 3 05.31.12
Control Voltage Load Type Minimum
Load
Maximum Load Neutral
Connection
Required
Not
Ganged
End of
Gang
Middle of
Gang
MS-OPS6M2N-DV
MS-VPS6M2N-DV
120-277V~
Lighting
1,2
0A 6A 6A 6A YES
120V~ Fan
2
0A
(0HP)
3A
(1/10HP)
3A
(1/10HP)
3A
(1/10HP)
YES
Load Type and Capacity
1
OccupancySensingswitchLoadType:designedforusewithpermanentlyinstalledincandescent,halogen,MLV,ELV,CFL,LED,magnetic
fluorescent,andelectronicfluorescentlightingloads.
2
Whencontrollinglightandfanloadssimultaneously,maximumloadcapacityis3Aat120V~ only.
Additional Information
• ForadditionalMaestro
®
OccupancySensingswitchmodels,pleasesee
LutronP/N369270(modelnumber:MS-OPS6M-DV)andP/N369488(MS-OPS2,MS-OPS5M,andMS-OPS6M2-DV).
• ForusewithMA-ASorforcontrolfrommorethantwolocations,pleaseseeLutronP/N048435.
• Formoreinformationonthemodelnumbersinthisdocument,pleaseseewww.lutron.com/occvacsensors.
• LutronTechnicalHotline:1.800.523.9466.
3
Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
Maestro® Occupancy Sensing Switch Switch with Occupancy and Vacancy Sensor
369659a 4 05.31.12
Specifications
Regulatory Approvals
• ULListedtoU.S.andCanadiansafetyrequirements.
• NOMCertification(pending).
Power
Operatingvoltage:
120-277V~50/60Hz
Key Design Features
• Alllightingloads.
• Crush/tamperresistantlens.
• Smartambientlightdetection.Lightsturnononlyif
ambientlightintheroomislow.Automaticallylearns
user's preferred setting.
• Adaptiveswitchingalgorithmforextendedrelaylife.
• XCTTM Technology for fine motion detection.
Environment
• Ambientoperatingtemperature:32°Fto104°F
(0°Cto40°C),0%-90%humidity,non-condensing.
Indoor use only.
Warranty
• 5YearLimitedWarranty.
ForadditionalWarrantyinformation,pleasevisit
http://www.lutron.com/TechnicalDocumentLibrary/
Sensor_Warranty.pdf
Timeout Options
• 1Minute
• 5Minutes
• 15Minutes
• 30Minutes
Sensitivity Options
• Highsensitivity
• Lowsensitivity
Auto-On Options (MS-OPSmodelsonly)
• “Occupancy”–Auto-On/Auto-Off
• “Vacancy”*–Manual-On/Auto-Off
• “LowLight”–Lightsturnononlyifneeded
(ifambientlightisbelowthreshold)
* Thereisa15-secondgraceperiodthatbeginswhenthelightsare
automaticallyturnedoff,duringwhichthelightswillautomaticallyturn
back on in response to motion. This grace period is provided as a
safety and convenience feature in the event the lights turn off while
theroomisstilloccupied,sothattheuserdoesnotneedtomanually
turnthelightsbackon.After15seconds,thegraceperiodexpires
and the lights must be manually turned on.
Manual Off While Occupied Options
(MS-OPSmodelsonly)
ENABLED
(default setting for MS-OPS6M2N-DV)
•WhentheOccupancySensingswitchismanually
turnedoff,theOccupancySensingswitchwillnot
turn the lights back on automatically while the
room is occupied.
•Oncetheroomisvacated,theAuto-onfeature
returns to normal operation after the timeout
period has expired.
•Thismaybethepreferenceinconferencerooms
or classrooms while viewing presentations. This
feature requires motion to keep the lights off.
DISABLED
•WhentheOccupancySensingswitchismanually
turnedoff,theAuto-onfeaturewillreturntonormal
operationafter25seconds.
•Thismaybethepreferenceiftheuseralways
wants the lights to turn on upon entering and
the lights to turn off when the room is vacant.
4
Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
Maestro® Occupancy Sensing Switch Switch with Occupancy and Vacancy Sensor
369659a 5 05.31.12
Beam Diagrams
Occupancy Sensing switch Placement and Operation
• The ability of the Occupancy Sensing switch to detect motion requires line-of-sight of room occupants.
The Occupancy Sensing switch must have an unobstructed view of the room.
• HotobjectsandmovingaircurrentscanaffecttheperformanceoftheOccupancySensingswitch.
• The performance of the Occupancy Sensing switch depends on a temperature differential between the
ambient room temperature and that of room occupants. Warmer rooms may reduce the ability of the
Occupancy Sensing switch to detect occupants.
Horizontal Beam Diagram
5 ft
(1.5 m)
5 ft
(1.5 m)
0
10 ft
(3 m)
10 ft
(3 m)
15 ft
(4.5 m)
15 ft
(4.5 m)
20 ft
(6 m)
20 ft
(6 m)
25 ft
(7.5 m)
25 ft
(7.5 m)
30 ft
(9 m)
30 ft
(9 m)
Vertical Beam Diagram
5 ft
(1.5 m)
0
10 ft
(3 m)
15 ft
(4.5 m)
20 ft
(6 m)
25 ft
(7.5 m)
30 ft
(9 m)
4 ft
(1.2 m)
Compliant to NEMA WD7 test grid shown below
Tested Coverage Area
10 ft
(3 m)
15 ft
(4.5 m)
20 ft
(6 m)
30 ft
(9 m)
Major Motion 900 ft
2
(81 m
2
) coverage
Major Motion 400 ft
2
(36 m
2
) coverage
5
Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
Maestro® Occupancy Sensing Switch Switch with Occupancy and Vacancy Sensor
369659a 6 05.31.12
Mounting
Wallbox
Sensing
switch
Adapter
Mounting
Screws
Mounting
Screws
Wallplate/Adapterpurchased
separately.
Operation
Sensor Lens
Tapswitch
Tapon/off
Occupancy Sensing switch
Sensor LED (behindlens)
PulsestoacknowledgemotionwhentheloadisON.
6
Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
Maestro® Occupancy Sensing Switch Switch with Occupancy and Vacancy Sensor
369659a 7 05.31.12
Occupancy Sensing switches can be ganged without derating.
Ganging and Derating
Dimensions
Measurementsshownas:in(mm)
Front View
Side View
5/16
(8)
1/8
(3)
1
1
8
(30)
4
11
16
(119)
2
15
16
(75)
7
Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
Maestro® Occupancy Sensing Switch Switch with Occupancy and Vacancy Sensor
369659a 8 05.31.12
Single Location Installation (120-277 V~)
1, 3
-OPS6M2N-DV,-VPS6M2N-DV
Wiring Diagram 1
Occupancy
sensing switch
120-277V~
50/60Hz
White
Ground
Hot/Live
Neutral
Load
Blue
1
Bare
Black Black
Wiring Diagrams:
3-way Installation with Standard Mechanical Switch (120 V~)
2, 4
-OPS6M2N-DV,-VPS6M2N-DV
Black
Blue
White
Ground
Occupancy
sensing switch
Green
Ground
120V~
50/60Hz
Hot/Live
Neutral
Load
Standard mechanical
switch
Black
Jumper wire
Bare
Different
color
screw
(Common)
Black
Blue
Green
Ground
Occupancy
sensing switch
White
Ground
120V~
50/60Hz
Hot/Live
Neutral
Load
Standard mechanical
switch
Black
Jumper wire
Bare
Different
color
screw
(Common)
OR
Wiring Diagram 2
1
Whenusingcontrolsinsinglelocationinstallations,tightentheblueterminalorcapbluewire.Do notconnecttheblueterminal/wiretoanyotherwireortoground.
2
Only one Occupancy Sensing switch can be used per multi-location circuit.
3
Fanloadappliesto120V~only(Notfor277V~)
4
Asinglestandard3-wayswitchorupto9companionswitchesmaybeconnectedtoanOccupancySensingswitch.Standard3-wayswitchcannotbe
combinedwithcompanionswitch.Totalblueterminalwirelengthmaybeupto150ft(46m).
8
Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
Maestro® Occupancy Sensing Switch Switch with Occupancy and Vacancy Sensor
369659a 9 05.31.12
3-way Installation with Standard Mechanical Switch (277 V~)
1, 2, 3
-OPS6M2N-DV,-VPS6M2N-DV
Black
Blue
White
Ground
Occupancy
sensing switch
Green
Ground
277V~
50/60Hz
Hot/Live
Neutral
Load
Standard mechanical
switch
Black
Jumper wire
Bare
Different
color
screw
(Common)
Black
Blue
Green
Ground
Occupancy
sensing switch
White
Ground
277V~
50/60Hz
Hot/Live
Load
Standard mechanical
switch
Black
Jumper wire
Bare
Different
color
screw
(Common)
OR
Wiring Diagram 3
Wiring Diagrams: (continued)
Wiring Diagram 4
Multi-Location Installation (120 V~)
1, 2, 3, 4
-OPS6M2N-DV,-VPS6M2N-DVwithMA-ASorMSC-AS
Blue
White
Ground
Occupancy
sensing switch
4
Black
Ground
120V~
50/60Hz
Brass Brass
Black
Blue Blue
Green Green
Ground
Hot/Live
Neutral
Load
MA-AS or
MSC-AS
MA-AS or
MSC-AS
Bare
Black Black
Neutral
1
Asinglestandard3-wayswitchorupto9companionswitchesmaybeconnectedtoanOccupancySensingswitch.Standard3-wayswitchcannotbe
combinedwithcompanionswitch.Totalblueterminalwirelengthmaybeupto150ft(46m)
2
Only one Occupancy Sensing switch can be used per multi-location circuit.
3
Fanloadappliesto120V~only(Notfor277V~).
4
Note:Canbeinstalledinanylocation.
4
9
Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
Maestro® Occupancy Sensing Switch Switch with Occupancy and Vacancy Sensor
369659a 10 05.31.12
Wiring Diagram 5
Multi-Location Installation (277 V~)
1, 2,3, 4
-OPS6M2N-DV,-VPS6M2N-DVwithMA-AS-277orMSC-AS-277
Occupancy
sensing switch
4
Black
Blue
White
Ground
Black
Blue
Green
Ground
277V~
50/60Hz
Black
Blue
Green
Ground
Hot/Live
Neutral
Load
RedRed
Bare
Black
MA-AS-277 or
MSC-AS-277
MA-AS-277 or
MSC-AS-277
1
Asinglestandard3-wayswitchorupto9companionswitchesmaybeconnectedtoanOccupancySensingswitch.Standard3-wayswitchcannotbe
combinedwithcompanionswitch.Totalblueterminalwirelengthmaybeupto150ft(46m)
2
Only one Occupancy Sensing switch can be used per multi-location circuit.
3
Fanloadappliesto120V~only(Notfor277V~).
4
Note:Canbeinstalledinanylocation.
4
10