SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak
Relay Module with Softswitch® Energi TriPak
Series Wireless Lighting Control
369-428f 1 04.03.12
PowPak
Relay Module with Softswitch®
The PowPak
Relay Module with Softswitch® is a radio frequency (RF)
device that uses Lutron patented Softswitch® technology to control up
to 16A of general-purpose load based on input from Pico® controls
and Radio Powr Savr
occupancy and daylight sensors. An optional,
low-voltage dry contact closure output is available to communicate
occupancy status to 3rd-party systems such as HVAC controllers.
Communication with RF input devices, such as Pico® controls and
Radio Powr Savr
sensors, is accomplished using Lutron Clear
Connect® RF Technology.
Features
•Softswitch®: Lutron patented technology prevents arcing of relay
contacts, extending product lifetime
•Variousoperatingvoltagesavailablerefertomodelnumberchart
below for details on voltage requirements
•Capableofswitching16Aofgeneral-purposeloads
•Optionallow-voltagedrycontactclosureoutputprovidesintegration
to building management systems, HVAC, VAV, etc.
•ReceiveswirelessinputsfromuptoninePico® controls, six Radio
Powr Savr
occupancy/vacancy sensors, and one Radio Powr Savr
daylight sensor
•UtilizesLutronClearConnect®RFTechnologyrefertomodel
number chart below for frequency band data
•Mountstoajunctionboxthroughastandardhalf-inch(NPTtradesize)
knockout
•Complieswithrequirementsforuseinacompartment
handlingenvironmentalair(plenum)perNEC® 2011 300.22(C)(3)


Description Model Number Operating
Voltage
Frequency Band Region
PowPak
Relay
Module with
Softswitch®
RMJ-16R-DV-B 120/277 V~ 431.0–437.0MHz U.S.A.,Canada,Mexico
URMJ-16R-DVB 120/277 V~ 431.0–437.0MHz U.S.A.,Canada,Mexico
(BAA Compliant)
RMQ-16R-DV-B 220 -240 V ~ 433.05–434.79MHz Hong Kong
RMM-16R-DV-B 220 -240 V ~
868.125–868.475MHz
China and Singapore
PowPak
Relay
Module with
Softswitch® and
Occupancy-Status
CCO
RMJ-16RCCO1-DV-B 120/277 V~ 431.0–437.0MHz U.S.A.,Canada,Mexico
URMJ-16RCCO1-DVB 120/277 V~ 431.0–437.0MHz U.S.A.,Canada,Mexico
RMQ-16RCCO1-DV-B 220 -240 V ~ 433.05–434.79MHz Hong Kong
RMM-16RCCO1-DV-B 220 -240 V ~
868.125–868.475MHz
China and Singapore
NOTE: Contact Lutron for frequency band compatibility for your geographic region if it is not indicated above.
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak
Relay Module with Softswitch® Energi TriPak
Series Wireless Lighting Control
369-428f 2 04.03.12
Specifications
Regulatory Approvals
RMJ- models only
•ULListed
•UL2043PlenumRated
•FCCapproved.ComplieswiththelimitsforaClassB
device, pursuant to Part 15 of the FCC rules.
•CSAandIC
•COFETEL
•NOM
Power
•Operatingvoltage:
RMJ & URMJ- models 120 /277 V~ 50 / 60Hz
RMQ- models 220-240 V~ 50 / 60Hz
RMM- models 220-240 V~ 50 / 60Hz
System Communication
•OperatesusingClearConnect® RF Technology for
reliable wireless communication; refer to model
number chart on page 1 for band frequency details
•RFrangeis30ft(10m)
Environment
•Ambientoperatingtemperature:32°Fto131°F
(0°Cto55°C)
•0%to90%humidity,non-condensing
•Forindooruseonly
Softswitch®
•PatentedSoftswitch® circuit eliminates relay arcing at
mechanical contacts
•Extendsrelaylifetoanaverageof1millioncycles
•Outputisnon-latching
Load
•Maximumload:16Ageneralpurpose.Nominimum
load requirements.
•Loadtypesinclude(butarenotlimitedto):
Incandescent,MLV,ELV,Resistive,Inductive,
Magneticuorescent,Electronicuorescent
•Motorrating:
RMJ & URMJ- models 0.5 HP (120V~), 1.5 HP (277V~)
RMQ- models 1.5 HP (220-240V~)
RMM- models 1.5 HP (220-240V~)
Key Design Features
•LEDstatusindicatorshowscurrentloadstatusand
provides programming feedback
•Powerfailurememory:Ifpowerisinterrupted,
connected loads will return to the previous level prior
to interruption
•DaylightingcanbeoverriddenbypressingtheON
button on any associated Pico®
Daylighting will be re-enabled after 2 hours or after
the area becomes unoccupied
Contact Closure Output (CCO version only)
•Providesoccupancystatusto3rd-partyequipment
such as building management systems, HVAC, and
VAV controllers
•Providesbothnormallyopen(NO)andnormally
closed(NC)drycontacts
•Maintainedoutputtype
•CCOterminalsaccept20to16AWG(0.5 to 1.5 mm
2
)
solid or stranded wire
•Outputislatching
•Notforvoltagesgreaterthan24V
Switching
Voltage
0-24 V-
0-24 V~
24 V-
max.
Inductive
Load
CCO
Output
NO
NC
COM
Flyback
Diode
(required for
inductive
loads)
Resistive
Load
1.0 A
0.5 A
R
+
-
•TheCCOisnotratedtocontrolunclamped,
inductiveloads.Inductiveloadsinclude,butarenot
limited to, relays, solenoids, and motors. To control
these types of equipment, a flyback diode must be
used (DC voltages only). See diagram below. For
moreinformation,pleaseseeApplicationNote#434
(p/n 048434).
Switching
Voltage
0-24 V-
0-24 V~
24 V-
max.
Inductive
Load
CCO
Output
NO
NC
COM
Flyback
Diode
(required for
inductive
loads)
Resistive
Load
1.0 A
0.5 A
R
+
-
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak
Relay Module with Softswitch® Energi TriPak
Series Wireless Lighting Control
369-428f 3 04.03.12
Test
System Diagram
Radio Powr Savr
OccupancySensor(upto6)
Radio Powr Savr
Daylight Sensor (up to 1)
Pico® Control (up to 9)
To 3rd-Party
Equipment
To power source
and load
Wiring Diagram
HOT
NEUTRAL
SWITCHED HOT
LOAD
COM
NO
NC
To 3rd-Party
Equipment
Occupancy-Status CCO
(RM__-16RCCO1-DV-B only)
Junction Box
Black
Red
White
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak
Relay Module with Softswitch® Energi TriPak
Series Wireless Lighting Control
369-428f 4 04.03.12
Wiring Diagram
Conduit Nut
White
(Neutral)
Black
(Hot)
Red
(Switched Hot)
NOTE:WhenwiringCCOto3rd-partysys-
tems,use20to16AWG(0.5to1.5mm
2
) solid
or stranded wire.
To 3rd Party Equipment
To Load
NO
(NormallyOpen)
NC
(NormallyClosed)
COM
(Common)
PowPak
InstallationInsideJunctionBox
(Dimming Module RMJ-ECO32-DV-B shown)
Antenna
BOXABOXB
Insomeapplications,aPowPak
modulecanbeinstalledinsidea4inx4in(102mmx102mm)junctionbox.For
informationabouthowtoperformthisinstallation,pleaseseeApplicationNote#423(p/n048423).
CCOoperationaffectedonlybyassociatedoccupancyorvacancysensors.
Room Occupied: NO=CloseNC=Open
Room Unoccupied: NO=OpenNC=Close
Input Voltage
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak
Relay Module with Softswitch® Energi TriPak
Series Wireless Lighting Control
369-428f 5 04.03.12
Dimensions
Dimensions are shown as: in (mm)
Range Diagram
•ContactLutronrstforapplicationsusingfoil-backedormetallicceilingtiles.
1.25
(31.8)
2.82
(71.6)
3.42
(86.9)
3.94
(100.1)
All Wireless Transmitters must be installed within
30 ft (10 m) of the PowPakTM Relay Module.
30 ft (10 m)
Maximum
40 ft (12 m)
30 ft (10 m)
PowPak
Relay Module
Installincenterofroomto
maximizeRFcoverage.
Pico®
Wireless
Transmitter
Half-inch
NPTTradeSize
Radio Powr Savr
Occupancy Sensor
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak
Relay Module with Softswitch® Energi TriPak
Series Wireless Lighting Control
369-428f 6 04.03.12
Default Operation
Transmitting Device Transmitted Command Softswitch®
Relay Default Action
CCO Default Action
Pico®
WirelessControl
On Close NoAction
Off Open NoAction
Raise NoAction NoAction
Lower NoAction NoAction
Preset Close NoAction
Radio Powr Savr
OccupancySensor
Occupied Close NO=Close,NC=Open
Unoccupied Open NO=Open,NC=Close
Radio Powr Savr
Vacancy Sensor
Occupied NoAction NO=Close,NC=Open
Unoccupied Open NO=Open,NC=Close
Radio Powr Savr
Daylight Sensor
Ambient Light Below
Target Level
Close NoAction
Ambient Light Above
Target Level
Open NoAction
6