LQSE-4S5-230-D
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
HomeWorks QS Switching Power Module
3691061b 1 01.19.18
Switching Power Module
The DIN Power Module (DPM) family is a group of
modular products for the control of lighting loads. This
product is compatible with Lutron HomeWorks QS
systems. This document describes the following
product:
LQSE-4S5-230-D: 4-zone power module for
switching only.
Features
Four switched output zones.
Adaptive zero-cross switching maximizes relay life.
Rated for lighting loads as defined by IEC/EN 60669
as well as INC, MLV, and ELV.
Rated for motor loads of 1/2 HP.
Includes QS link for seamless connection to a
HomeWorks QS system.
LEDs on the module provide diagnostic information.
Buttons on module provide override control.
Manual Override Contact Closure Input (CCI).
Programmable Contact Closure Output (CCO).
Power failure memory automatically returns the
outputs to the levels they were set to prior to a
power outage.
LQSE-4S5-230-D
HomeWorks QS
LQSE-4S5-230-D
220-240 V~ 50
/
60 Hz 16 A
+1.844.LUTRON1
lutron.com
1234
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
220-240 V~ 5 A
220-240 V~ 5 AX, 1/2 HP
NNNN
M
N
L
HomeWorks QS
LQSE-4S5-230-D
220-240 V~ 50
/
60 Hz 16 A
+1.844.LUTRON1
lutron.com
1234
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2Zn. 3Zn. 4
220-240 V~ 5 A
220-240 V~ 5 AX, 1/2 HP
NNNN
M
N
L
H
M
L
LQSE-4A-D
DIN Rail Power Module
230 V~ 50 / 60 Hz 10 A
www.lutron.com +44.(0)20.7702.0657
CCI
500 W Max 800 W Max 500 W Max 500 W Max
Zone 2Zone 1 Zone 3 Zone 4
Input
Hi Temp
Prog
Power
Opt1
Opt2
Opt3
Def
Option
7
QS Link
Switching
Power
Module
Contact Closure Output
Manual Override
Contact Closure Input
Dimming Power Module
HomeWorks
QS Panel
QS
Contact
Closure
Interface GRAFIK Eye QS
seeTouch QS
Wallstation
Up to 100
QS devices
System Example
Sivoia QS
Shades/
Draperies
Palladiom
Keypad
1
LQSE-4S5-230-D
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
HomeWorks QS Switching Power Module
3691061b 2 01.19.18
Specifications
Power
• 220-240V~ 50/60Hz
Single input feed
16 A maximum input current
Lightning strike protection meets ANSI/IEEE standard
C62.41 and IEC 61000-4-5. Can withstand voltage
surges up to 6000V~ and current surges up to
3000A.
ESD-protection exceeds agency requirements per
IEC-61000-4-2
For ungrounded delta feed applications, contact Lutron.
Regulatory Approvals
Complies with IEC/EN 60669
Lutron Quality Systems registered to ISO9001.2015
CE marked
Environment
For thermal specifications, see Mounting section
Relative humidity: less than 90% non-condensing
For indoor use only
Output Zone Ratings
Each zone is rated at 5A for switching. Rated for
resistive, inductive, or capacitive lighting loads as
defined by IEC/EN 60669.
Air gap off per output.
No minimum load per output.
• This module is designed to control loads with ratings as
noted in the table below.
Outputs cannot be used to control general purpose
receptacles.
Load Type
Relay Ratings
220-240 V~
Tungsten 5 A/zone, 16 A max/module
AC General Use 5 A/zone, 16 A max/module
Electric Discharge Lamp 5 A/zone, 16 A max/module
Electronic Ballast 5 A/zone, 16 A max/module
Resistive 5 A/zone, 16 A max/module
Inductive 5 A/zone, 16 A max/module
Motor
5 A (1/2 HP)/zone,
16 A max/module
• Special considerations:
When controlling lamps, Lutron recommends
using permanently installed fixtures.
If controlling plug-in lamps, installation must
ensure a method of preventing non-rated loads
being plugged into the unit. An example is a
dedicated receptacle with an alternate plug type.
Controlling loads outside the parameters listed in
the specifications may damage the device and
void the warranty.
• If attempting to control general purpose receptacles,
use the appropriate third-party power pack for the
rated load.
• Run a separate neutral for each load circuit. A
common neutral connection is not recommended.
Unit may be powered by Ground Fault Interrupter
(GFI) or Residual Current Circuit Breaker with
Overload (RCBO) protected circuit if required.
For applications requiring higher wattage ratings, use
GRX-TVI or LQSE-4S10-D for 220-240 V~.
Programming and Compatibility Requirements
Setup and programming of the Switching Module
is done through the HomeWorksQS programming
software.
HomeWorksQS software version 12.0 or higher
required.
HomeWorksQS Wallstations
HomeWorksQS wallstations can be configured to
control Switching Modules with the HomeWorksQS
programming software.
Wallstation LED indicators display the status of
programmed lights.
2
LQSE-4S5-230-D
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
HomeWorks QS Switching Power Module
3691061b 3 01.19.18
Specifications - (continued)
QS Link Limits
A QS link in a HomeWorksQS system can have up
to 512zones (outputs) and 100devices (required
HomeWorks QS processor counts as 1 device on the
QS link).
Each Switching Module counts as one device toward
the 100device limit, and 4 zones toward the 512 zone
limit.
Terminals
Mains wiring: 1.0 mm² to 2.5 mm² (18 AWG to 12 AWG)
(single wire, solid or stranded)
CCI / CCO
wiring: 0.5 mm² to 2.5 mm² (22 AWG to 12 AWG)
(single wire, solid or stranded)
0.5 mm² to 1.5 mm² (20 AWG to 16 AWG)
(two wires, solid or stranded)
Zone wiring: 1.0 mm² to 2.5 mm² (18 AWG to 12 AWG)
(single wire, solid or stranded)
QS Link: 0.5 mm² to 2.5 mm² (22 AWG to 12 AWG)
(single wire, solid or stranded)
0.5 mm² to 1.0 mm² (20 AWG to 18 AWG)
(two wires, solid or stranded)
3
LQSE-4S5-230-D
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
HomeWorks QS Switching Power Module
3691061b 4 01.19.18
Manual Mode Operation
Zone button on the unit can be used to turn loads on
and off.
Contact Closure Input (CCI)
When the CCI is open, the Switching Power Module
will enter Manual Override Mode, which will turn on
all loads and disable control of all local zones and QS
devices.
When the CCI is closed or jumpered (factory default),
the Switching Power Module zones will return to
the settings they were at prior to entering Manual
Override Mode.
Contact Closure Output (CCO)
Accepts voltages of 0 –24V~ / 0 –24V-; see chart
below for load switching capacities:
Switching Voltage
Resistive Load
R
0 –24 V- 1.0 A
0 –24 V~ 0.5 A
Provides both normally open (N.O.) and normally
closed (N.C.) dry contacts.
Maintained or momentary output type.
Output relay is non-latching (if relay is closed and
power is lost, relay will open).
The CCO is not rated to control unclamped, inductive
loads. Inductive loads include, but are not limited to,
relays, solenoids, and motors. To control these types
of equipment, a flyback diode (not included) must be
used (DC voltages only). See diagram below.
Inductive
Load
Flyback Diode
(required for
inductive loads)
CCO Output
N.O. N.C.
COM
+
24 V-
maximum
4
LQSE-4S5-230-D
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
HomeWorks QS Switching Power Module
3691061b 5 01.19.18
Mounting
Mount in a Lutron DIN Panel (see specification
sheet P/N 369788 at www.lutron.com) or in an IP20
(minimum) rated consumer panel or breaker panel
with integrated DIN rail.
Unit is 9 DIN modules (161.7 mm [6.37 in]) wide.
Mount in an accessible and serviceable location.
Unit may be mounted by pressing the unit onto the
DIN rail with the clips locked. To remove the unit from
the DIN rail, unlock the clips using a screwdriver.
See Lutron P / N 048466 at www.lutron.com for more
information on mounting and installation in panels
with integrated DIN rail.
Mount the Power Module where audible noise is
acceptable (internal relays click).
Unit generates heat, maximum 24 BTUs/hr.
Mount unit such that all the conditions below are met:
Room ambient temperature is between 0 ºC and
40 ºC (32 ºF and 104 ºF).
Temperature inside mounting panel, within 20 mm
(0.80 in) of unit, is between 0 ºC and 40 ºC
(32 ºF and 104 ºF).
Calibration point maximum: 65 ºC (149 ºF).
HomeWorks QS
LQSE-4S5-230-D
220-240 V~ 50
/
60 Hz 16 A
+1.844.LUTRON1
lutron.com
1234
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
220-240 V~ 5 A
220-240 V~ 5 AX, 1/2 HP
NNNN
M
N
L
LL
HomeWorks® QS
LQSE-4S1-D
120
-
240 V~ 50
/
60 Hz 4 A
+1.610.282.3800
lutron.com
1234
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
120
-
240 V~ 1 A
120
-
240 V~ 1 AX, 1 FLA
/
6 LRA
®
NN NNNN
M
IEC SELV
/
NECR Class 2
LL
LL
HomeWorks® QS
LQSE-4S1-D
120
-
240 V~ 50
/
60 Hz 4 A
+1.610.282.3800
lutron.com
1234
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
120
-
240 V~ 1 A
120
-
240 V~ 1 AX, 1 FLA
/
6 LRA
®
NN NNNN
M
IEC SELV
/
NECR Class 2
LL
LL
HomeWorks® QS
LQSE-4S1-D
120
-
240 V~ 50
/
60 Hz 4 A
+1.610.282.3800
lutron.com
1234
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
120
-
240 V~ 1 A
120
-
240 V~ 1 AX, 1 FLA
/
6 LRA
®
NN NNNN
M
IEC SELV
/
NECR Class 2
LL
LL
HomeWorks® QS
LQSE-4S1-D
120
-
240 V~ 50
/
60 Hz 4 A
+1.610.282.3800
lutron.com
1234
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
120
-
240 V~ 1 A
120
-
240 V~ 1 AX, 1 FLA
/
6 LRA
®
NN NNNN
M
IEC SELV
/
NECR Class 2
LL
Mounting clips (4) on unit
Locked Unlocked
Mechanical Dimensions
HomeWorks QS
LQSE-4S5-230-D
220-240 V~ 50
/
60 Hz 16 A
+1.844.LUTRON1
lutron.com
1234
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
220-240 V~ 5 A
220-240 V~ 5 AX, 1/2 HP
NNNN
M
N
L
161.7 mm
(6.37 in)
89.7 mm
(3.53 in)
60.6 mm
(2.38 in)
5
LQSE-4S5-230-D
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
HomeWorks QS Switching Power Module
3691061b 6 01.19.18
Wiring from Distribution to Switching Power Module
Turn off all circuit breakers or isolators feeding the Switching Power Module at the distribution panel.
• Run line / hot and neutral wires from a 220-240 V~ 50 / 60 Hz feed to the Switching Power Module unit.
Run a separate neutral for each load circuit. A common neutral connection is not recommended.
Mains Wiring and IEC SELV Separation
Follow appropriate local and national codes to avoid violating required separation guidelines.
Wiring: Mains and Output Zones
HomeWorks QS
LQSE-4S5-230-D
220-240 V~ 50
/
60 Hz 16 A
+1.844.LUTRON1
lutron.com
12
34
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
220-240 V~ 5 A
220-240 V~ 5 AX, 1/2 HP
NNNN
M
N
L
Zone 1
Zone 2
Zone 3
Zone 4
HomeWorks QS
LQSE-4S5-230-D
220-240 V~ 50
/
60 Hz 16 A
+1.844.LUTRON1
lutron.com
1234
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
220-240 V~ 5 A
220-240 V~ 5 AX, 1/2 HP
NNNN
M
N
L
Mains
Neutral
Outputs
LL
LL
Distribution Panel
220-240 V~
Hot/Line
Neutral
To additional
modules
Note: If wiring for feed-through to
other Lutron modules using mains
terminals, total current of all modules
must be less than or equal to 16 A.
IEC SELV
QS LinkCCI CCO
6
LQSE-4S5-230-D
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
HomeWorks QS Switching Power Module
3691061b 7 01.19.18
HomeWorks QS
LQSE-4S5-230-D
220-240 V~ 50
/
60 Hz 16 A
+1.844.LUTRON1
lutron.com
1234
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
220-240 V~ 5 A
220-240 V~ 5 AX, 1/2 HP
NNNN
M
N
L
LL
HomeWorks® QS
LQSE-4S1-D
120
-
240 V~ 50
/
60 Hz 4 A
+1.610.282.3800
lutron.com
1234
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
120
-
240 V~ 1 A
120
-
240 V~ 1 AX, 1 FLA
/
6 LRA
®
NN NNNN
M
IEC SELV
/
NECR Class 2
LL
LL
HomeWorks® QS
LQSE-4S1-D
120
-
240 V~ 50
/
60 Hz 4 A
+1.610.282.3800
lutron.com
1234
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
120
-
240 V~ 1 A
120
-
240 V~ 1 AX, 1 FLA
/
6 LRA
®
NN NNNN
M
IEC SELV
/
NECR Class 2
LL
LL
HomeWorks® QS
LQSE-4S1-D
120
-
240 V~ 50
/
60 Hz 4 A
+1.610.282.3800
lutron.com
1234
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
120
-
240 V~ 1 A
120
-
240 V~ 1 AX, 1 FLA
/
6 LRA
®
NN NNNN
M
IEC SELV
/
NECR Class 2
LL
LL
HomeWorks® QS
LQSE-4S1-D
120
-
240 V~ 50
/
60 Hz 4 A
+1.610.282.3800
lutron.com
1234
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
120
-
240 V~ 1 A
120
-
240 V~ 1 AX, 1 FLA
/
6 LRA
®
NN NNNN
M
IEC SELV
/
NECR Class 2
LL
LL
HomeWorks® QS
LQSE-4S1-D
120
-
240 V~ 50
/
60 Hz 4 A
+1.610.282.3800
lutron.com
1234
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
120
-
240 V~ 1 A
120
-
240 V~ 1 AX, 1 FLA
/
6 LRA
®
NN NNNN
M
IEC SELV
/
NECR Class 2
LL
CCI Wiring
Pre-installed
Jumper
OR Device Wiring
LL
HomeWorks® QS
LQSE-4S1-D
120
-
240 V~ 50
/
60 Hz 4 A
+1.610.282.3800
lutron.com
1234
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
120
-
240 V~ 1 A
120
-
240 V~ 1 AX, 1 FLA
/
6 LRA
®
NN NNNN
M
IEC SELV
/
NECR Class 2
LL
LL
HomeWorks® QS
LQSE-4S1-D
120
-
240 V~ 50
/
60 Hz 4 A
+1.610.282.3800
lutron.com
1234
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
120
-
240 V~ 1 A
120
-
240 V~ 1 AX, 1 FLA
/
6 LRA
®
NN NNNN
M
IEC SELV
/
NECR Class 2
LL
LL
HomeWorks® QS
LQSE-4S1-D
120
-
240 V~ 50
/
60 Hz 4 A
+1.610.282.3800
lutron.com
1234
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
120
-
240 V~ 1 A
120
-
240 V~ 1 AX, 1 FLA
/
6 LRA
®
NN NNNN
M
IEC SELV
/
NECR Class 2
LL
LL
HomeWorks® QS
LQSE-4S1-D
120
-
240 V~ 50
/
60 Hz 4 A
+1.610.282.3800
lutron.com
1234
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
120
-
240 V~ 1 A
120
-
240 V~ 1 AX, 1 FLA
/
6 LRA
®
NN NNNN
M
IEC SELV
/
NECR Class 2
LL
CCO Wiring
N.O. Wiring OR N.C. Wiring
LL
HomeWorks® QS
LQSE-4S1-D
120
-
240 V~ 50
/
60 Hz 4 A
+1.610.282.3800
lutron.com
1234
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
120
-
240 V~ 1 A
120
-
240 V~ 1 AX, 1 FLA
/
6 LRA
®
NN NNNN
M
IEC SELV
/
NECR Class 2
LL
Third-party Device Third-party Device
CCO (N.O.)
CCO (N.C.)COM
COMCCI
Device Wiring
Wiring: Manual Override
Contact Closure Input and
Contact Closure Output
IEC SELV Contact Closures
Manual Override Contact Closure Input
(CCI) /Contact Closure Output (CCO) wiring
is IEC SELV. Follow all applicable national
and local codes for proper circuit separation
and protection.
Turn off all breakers or isolators feeding the
Switching Power Module at distribution
panel before servicing unit.
CCI is local control only and cannot
control other units over the QS link. CCI
on up to 32 units may be connected to an
emergency or manual override device in
parallel if event is intended to affect multiple
units.
When in Manual Override Mode:
All zone outputs will be switched on.
Controls will not affect units in Manual
Override Mode.
Controls connected to a unit in Manual
Override Mode will continue to affect
units on the link that are not in Manual
Override Mode.
Manual override contact closure input
is normally closed (N.C.). The Switching
Power Module is shipped with a jumper
pre-installed.
Note: The Switching Power Module will
default to Manual Override Mode if
the CCI is left open. If no Manual
Override contact input is required,
leave the wire jumper in the CCI
terminals.
7
LQSE-4S5-230-D
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
HomeWorks QS Switching Power Module
3691061b 8 01.19.18
Wiring: QS Link
HomeWorks QS
LQSE-4S5-230-D
220-240 V~ 50
/
60 Hz 16 A
+1.844.LUTRON1
lutron.com
1234
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
220-240 V~ 5 A
220-240 V~ 5 AX, 1/2 HP
NNNN
M
N
L
LL
HomeWorks® QS
LQSE-4S1-D
120
-
240 V~ 50
/
60 Hz 4 A
+1.610.282.3800
lutron.com
1234
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
120
-
240 V~ 1 A
120
-
240 V~ 1 AX, 1 FLA
/
6 LRA
®
NN NNNN
M
IEC SELV
/
NECR Class 2
LL
LL
HomeWorks® QS
LQSE-4S1-D
120
-
240 V~ 50
/
60 Hz 4 A
+1.610.282.3800
lutron.com
1234
CCI COM
CCO N.O.
CCO COM
COM
CCI
CCO N.C.
MUX
MUX
Zn. 1Prog. Zn. 2 Zn. 3 Zn. 4
120
-
240 V~ 1 A
120
-
240 V~ 1 AX, 1 FLA
/
6 LRA
®
NN NNNN
M
IEC SELV
/
NECR Class 2
LL
Control Link
Data Link
1: COM
2: Do Not Connect
3: MUX
4: MUX
• QS link wiring is IEC SELV. Follow all applicable
local codes for proper circuit separation and
protection.
Turn off all breakers or isolators feeding the
Switching Power Module at distribution panel before
servicing unit.
Wiring may be daisy chained or t-tapped.
Total length of QS link wiring must not exceed 610 m
(2 000 ft).
Wire Gauge:
Control (terminal 1): 1.0 mm
2
(18 AWG).
Data (terminals 3 and 4): 1 pair 0.5 mm
2
to
1.0 mm
2
, (22 AWG to 18 AWG) twisted and
shielded.
Can use Lutron cable GRX-CBL-346S-500 (less
than 152 m [500 ft]) or GRX-CBL-46L (152 m to
610 m [500 ft to 2000 ft]).
• See HomeWorks QS Wiring Guidelines
application note on www.myLutron.com
)Lutron, Lutron, HomeWorks, seeTouch, and GRAFIK Eye are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries.