SPECIFICATION SUBMITTAL
ne-xp-6 12.05.08
Power Equipment
XP Switching Panels
GRAFIK Systems
PELV (Class 2: USA) Wiring Overview for Combination
Normal/Emergency Softswitch
® Panel
XP Panel
Control Unit
Control Interface
Wallstations
XP Panel
Control Unit
Control Interface
Wallstations
Processor
Panel
Power Panel Link
GRAFIK Eye® 4000 System
PELV (Class 2: USA) wiring link requires:
Two 12 AWG (2.5 mm
2
) conductors for control power.
One twisted, shielded pair of 18 AWG (1.0 mm
2
) for data link.
One 18 AWG (1.0 mm
2
) conductor for Emergency (Essential) sense line, from panel to panel.
Total length of control link may be no more than 2,000 ft. (610 m).
Approved low-voltage cable is available from Lutron,
1
Belden, and Liberty. These are approved with 22
AWG data link wires.
GRAFIK 5000TM/6000®/7000® System
PELV (Class 2: USA) wiring link requires:
Two 12 AWG (2.5 mm
2
) conductors for control power.
One twisted, shielded pair of 18 AWG (1.0 mm
2
) for data link.
One 18 AWG (1.0 mm
2
) conductor for emergency (essential) sense line, from panel to panel.
Total length of control link may be no more than 2,000 ft. (600 m).
If MUX-RPTR interface and GRX-CBL-46L cable
1
is used, length may be up to 4,000 ft. (1200 m).
System communications use low-voltage PELV (Class 2: USA) wiring.
Wiring must be daisy-chained.
Wiring must run separately from line (mains) voltage.
GRX-CBL-46L PELV (Class 2: USA) wiring cable is available from Lutron and contains:
Two 12 AWG (2.5 mm
2
) conductors for control power.
One twisted, shielded pair of 22 AWG (0.625 mm
2
) for data link.
One 18 AWG (1.0 mm
2
) conductor for emergency (essential) sense line.
1
Refer to GRAFIK 5000/6000/7000 Specification