R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICA
TION SUBMITTAL
viseo-1 01.10.06
Wallstations
GRAFIK Systems
®
OMX-VDC-LB/OMX-VDC-LF
Viseo® Wallstation
Easy-to-read monochrome
LCD screen.
Side buttons select the
function listed on the
V
iseo screen.
Raise/Lower buttons
fine-tune the system
OMX-VDC-LF-WH
Navigation buttons
provide direct access
to every scene, zone,
and area in the system
Description
The Viseo Wallstation provides local access to
the Lighting Control System.
• Works with GRAFIK 5000
TM, GRAFIK 6000®,
GRAFIK 7000TM Systems.
• Program, monitor, and operate every lighting
zone* and scene of a space that is controlled
by an individual Processor. For multiple
Processor applications, contact Lutron.
• Offers an effective alternative to PC’s and other
plug-in devices for day-to-day operations.
• Automatically downloads data from your
system without reprogramming.
• Modify preset light levels.
• View the lighting status of all the areas in the
system.
• View the timeclock status of all the areas in the
system
• Take control of any lighting zone* or group of
lighting zones* in any area; fine tune in 1%
increments with graphic and numeric feedback.
Program changes to preset light levels,
including fade and delay times, in any area.
• Menus and help screens can be displayed in
one of 7 languages: English, French, German,
Italian, Spanish, Portuguese, or Dutch.
Design Options
Monochrome Color Options:
High contrast blue/white - OMX-VDC-LB
• Neutral black/white - OMX-VDC-LF
* Does not display Lighting Zone Controller or OMX-3600
zone information.
1
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICA
TION SUBMITTAL
viseo-2 01.10.06
Wallstations
GRAFIK Systems
®
Power
Low-voltage Class 2 (PELV)
Operating Voltage: 32 V
Key Design Features
• Liquid Crystal Display (LCD)
Resolution: 320 x 240 pixels (QVGA)
• Adjustable LCD contrast and backlight brightness.
• Change system time and date.
• Off-line programming allows changes to preset light levels without affecting
current lighting scene.
• On-line programming allows for viewing changes to preset light levels as
they are being made.
• Central or local options: configure Viseo Wallstation for various control,
monitoring and programming options for each individual area of the
building.
• Security: set-up and programming configuration options may be restricted
via numeric passcode.
• Field upgradeable software: allows future enhancements without hardware
changes.
• System information displayed in ASCII 7-bit format (Characters A-Z, a-z,
and 0-9) only.
Menus and help screens can be displayed in one of 7 languages: English,
French, German, Italian, Spanish, Portuguese, or Dutch.
System Communications and Capacity
• Low-voltage Class 2 (PELV) wiring connects Wallstations to Processor
Panel.
• Up to 32 Wallstations, Control Units, and/or Control Interfaces may be
connected per Class 2 (PELV) Control Station Device link. See Low
Voltage Wiring page for more details.
Additional Notes
Hidden spaces will not appear on V
iseo stations.
Viseo does not support hierarchical spaces; they will display all spaces as
a single list.
Terminals
Accept up to two #18 AWG (1.0mm
2
) typical.
Environment
32-104°F (0-40°C). Relative humidity less than 90% non-condensing.
Specifications
2
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICA
TION SUBMITTAL
viseo-3 01.10.06
Wallstations
GRAFIK Systems
®
Mounting
Front View
Back V
iew
SCENES ZONES AREAS
HELP&
SYSTEM
Wallstation
Link
MUX
MUX
Drain
Power
Common
5 4 3 2 1
No
Connection
9”
(229 mm)
7 5/8”
(194 mm)
3”
(76 mm)
5 1/4”
(133 mm)
6 1/2”
(165 mm)
6 1/2”
(165 mm)
1 7/8”
(47 mm)
2/5”
(10 mm)
Architectural Matte Finishes
White WH
Ivory IV
Beige BE
Gray GR
Brown BR
Black BL
Architectural Metal Finishes
Bright Brass BB
Bright Chrome BC
Satin Brass SB
Satin Chrome SC
Satin Nickel SN
Antique Brass QB
Antique Bronze QZ
Bright Nickel BN
Anodized Aluminum Finishes
Clear CLA
Black BLA
Brass BRA
Custom Controls, color matching,
and engraving available. Pricing and
lead time may vary depending on
colors, finishes, and options chosen.
Color and Finish Codes
Dimensions
Side View
3
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICA
TION SUBMITTAL
viseo-4 01.10.06
Wallstations
GRAFIK Systems
®
Wallstation
Link
MUX
MUX
Drain
Power
Common
5 4 3 2 1
No
Connection
D: Drain/Shield
Data Link
(1) Shielded, twisted pair
#18 AWG (1.0mm
2
)
3: MUX
4: MUX
Class 2/PELV
Control Wiring
1: Common
2: 32VDC
(1) #18 AWG
(1.0mm
2
)
(2) #12 AWG
(2.5mm
2
)
(2) #12 AWG
(2.5mm
2
)
• Use low-voltage Class 2 (PELV) wiring to daisy-
chain Wallstations to the Processor Panel.
• Two #12 AWG (2.5mm
2
) conductors for common
(terminal 1) and 32VDC (terminal 2). These will not
fit in terminals. Connect as shown.
• One shielded, twisted pair #18 AWG (1.0mm
2
) for
data link (terminals 3 and 4).
• Connect Drain/Shield as shown.
Caution! A Viseo Wallstation requires the
power equivalent of four (4) typical OMX
Wallstations. If the total power draw on the
link is greater than 32 typical OMX
Wallstations, a MX-RPTR is required.
Low-Voltage Class 2 (PELV) Wiring
Use appropriate wire connecting
devices as specified by local codes.
4