GRAFIK SystemsT XP Switching Panels Power Equipment
369345e 2 01.23.14
SPECIFICATION SUBMITTAL
Job Name:
Job Number:
Model Numbers:
Regulatory Approvals
• ULR Listed (Reference: UL File 42071)
• Complies with ISO-9000
• CSA, NOM
• Seismic Certified (Test Method AC156. Reference
OSHPD Preapproval OSP-0215-10).
Power
• Input power: 100 to 127 V~, 220 to 240 V~
(non-CE), 230 V~ (CE), 277 V~, and 347 V~. All
voltages 50/60 Hz, phase-to-neutral.
• Control circuit (Feed-Through XP Panels only):
Dedicated feed, same voltage and phase as Panel.
• Branch Circuit Breakers: ULR rated thermal magnetic.
AIC ratings:
120 V~ 10,000 A
220 to 240 V~ 6000 A
277 V~ 18,000 A
347 V~ 14,000 A
• Lightning strike protection: Meets ANSI/IEEE standard
62.41-1980. Can withstand voltage surges of up
to 6000 V~ and current surges of up to 3000 A.
• 10-year power failure memory: Automatically restores
lighting to levels prior to power interruption.
Load Types (relay ratings)
Relay Rating
Load Type
120 V~ 230 V~
(CE)
220-240 V~ 277 V~ 347 V~
Tungsten 20 A 16 A 16 A 20 A 16 A
AC General
Use
20 A 16 A 16 A 20 A 16 A
Electric
Discharge
Lamp
16 A 16 A 16 A 16 A 16 A
Electronic
Ballast
NEMA 410
16 A N/A N/A 16 A N/A
Resistive 20 A 16 A 16 A 20 A 16 A
Inductive 20 A 16 A 16 A 20 A 16 A
Motor
1.0 HP N/A N/A 2.0 HP N/A
Specifications
Load
•
When using the Switching Module to control
receptacles, it may be used with, but is not limited to,
the following:
– Monitors – Fans
– Humidifiers – Printers
Note: Refer to the manufacturer’s guidelines for
acceptable switching methods.
•
When using the Switching Module to control
receptacles, it may NOT be suitable for use with
devices that require any of the following:
– Shut-down process before power is interrupted,
such as computers.
– Cool-down process before power is interrupted,
such as projectors.
– Programming, such as clocks or DVRs.
– Long warm-up cycle.
•
Not for use with loads that present a hazard if
automatically energized, for example heaters.
•
Any receptacles that are controlled by an
automatic control device must be marked with
“u” located on the controlled receptacle outlet
where visible after installation as stated in 2014
NECR Article 406.3(E).
Switching Modules (120, 277, 347 V~)
• Able to control 20 A receptacles.
• Switch legs rated at 20 A.
• Patented SoftswitchR circuit eliminates arcing at
mechanical contacts when loads are switched, which
prolongs relay life to an average of 1,000,000 cycles
at 16 A.
• 10 BTU / hour per module.
Panel Type Voltage Std. SCCR Rating
XP Feed-through
(all sizes)
120/277 V~ 25,000 A
XP Main Lug Panels
(all sizes)
120/277 V~ 25,000 A
Short Circuit Current Ratings (other ratings available)