SPECIFICATION SUBMITTAL
369379 Rev. A 6 12.10.10
Wireless Control Interfaces
SZ-IO
Stanza®
CCI and CCO terminals each hold one
28-16AWG(0.08-1.5mm
2
) wire
15-24V 200 mA
Power terminals each hold
two18AWG(1.0mm
2
)
wires
CCO 1 NC
CCO 1 NO
1-2 COM
CCO 2 NC
CCO 2 NO
CCO 3 NC
CCO 3 NO
3-4COM
CCO4NC
CCO4NO
CCO5NC
CCO5NO
5COM
CCI 1
CCI 2
CCI 3
CCI4
CCI5
COM
+PWR OUT
COM
Wiring Diagram
Contact Closure Outputs
Contact Closure Inputs
GND
N/C
Operation
The SZ-IO receives its operating settings during
system startup. A device database containing
settings is transferred to the SZ-IO after it has been
addressed. This database includes settings for:
• CCObehavior(maintainedvs.momentary)
• Momentarypulsetime
• CCIprogrammingaction
• Systempresets
LED Feedback
The SZ-IO provides 7 LEDs for user feedback:
Status LEDs
LEDs1through5providefeedbackfortheCCOs
and CCIs. The display mode (CCO vs. CCI status)
depends on the position of DIP switch 7: The LED
lights when the CCO is active or when the CCI is
closed.
Switch up (on): CCI status displayed
Switch down (off): CCO status displayed
Addressing Mode LED
LED 6 will blink during addressing. A slow blink
(onfor3secondsevery4seconds)indicatesan
unaddressed device. A fast blink (once per second)
indicates an addressed device. When not in
addressing mode, this LED is off.
RF Link Activity LED
LED 7 will blink when the SZ-IO receives or
transmits an RF packet.
Diagnostic Mode and DIP Switch Settings
Diagnostic mode allows the user to override the contact
closure outputs (CCOs) of the device.
Diagnostic Mode Operation
1. Enter diagnostic mode. Move DIP switch 6 to the on (up)
position. LEDs 6 and 7 will flash together (once per second)
while the unit is in diagnostic mode.
2. Select CCOs to override.UseDIPswitches1through5to
select which CCOs to close when the addressing (ADDR)
button is pressed. (The DIP switch number corresponds to
the CCO it controls.)
3. Activate the CCOs. Press the addressing button to activate
the CCOs you set using the DIP switches in the previous step.
The CCOs will remain active as long as the button is pressed.
4.Exit diagnostic mode. Move DIP switch 6 to the off (down)
position. LEDs 6 and 7 will stop flashing together.
DIP Switch Settings
Switch # LED Display
6 7 Mode Shows
Normal Outputs
Normal Inputs
Diagnostic Outputs
Switch up (On) Switch down (Off)
Note:Indiagnosticmode,DIPs1-5settheoverridestateoftheoutputs.
Note: For ESD protection, the included ground
wire should be connected to Earth/Ground before
device is powered.