SPECIFICATION SUBMITTAL
369357 Rev. A 1 11.19.10
Power Modules
Switching Power Module
GRAFIK Eye®
Model Number
PHPM-SW-DV-WH
Capacity
16 A
Control Power
120 V
Switching Power Module
Description
Provides capability for a zone on a GRAFIK Eye
control unit (or other product) to switch a fully
loaded circuit of lighting.
May be used to switch incandescent, electronic
low-voltage, magnetic low-voltage, HID,
fluorescent ballasts, and neon/cold cathode
lighting sources.
Utilizes Softswitch® arcless switching technology.
Provides power and switching for one zone.
Up to 3 power modules may be wired on a single
GRAFIK Eye zone.
Model available for 120 V control power.
Model available for 120 - 277 V load power.
Works with 120 V versions of:
Lutron® 3-wire fluorescent dimmers (consult
Lutron for Vierti®); see approved list in the
dimmers & switches specification guide at www.
lutron.com
GRAFIK Eye QS control units
GRAFIK Eye 3000 Series control units
LP, LCP, and GP dimming panels
HomeWorks® remote power panels
Model and Capacities
Load Power
120 - 277 V
1
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369357 Rev. A 2 11.19.10
Power Modules
Switching Power Module
GRAFIK Eye®
Power
Control / load power:
120 V / 120 - 277 V
50 / 60 Hz, phase-to-neutral.
Load (output) power: Phase independent of control unit.
Sources/Load Types
Switches the following load types:
Incandescent (tungsten)
Halogen
Magnetic low-voltage transformer (iron core)
Electronic (solid-state) low-voltage transformer.
Magnetic and electronic fluorescent dimming ballasts
Neon/cold-cathode
HID
Motors:
1/2 HP at 277 V
1/3 HP at 120 V
May be used with GFI/AFI breaker protected loads.
Key Design Features
Patented Softswitch® technology.
Two LEDs on front of unit provide diagnostic information
(visible when faceplate is removed).
Terminals
Accept up to two 12 AWG (2.5 mm
2
) wires.
Environment
32 to 104 °F (0 to 40 °C). Relative humidity less than 90% non-condensing.
Indoor use only.
Maximum heat output of module: 15 BTU/hour.
Mounting
Surface or recess mount.
Power module is UL tested and approved for use in spaces designed for
environmental air handling.
Specifications
2
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369357 Rev. A 3 11.19.10
Power Modules
Switching Power Module
GRAFIK Eye®
Mount in 2-gang U.S. wallbox 3.5 in
(89 mm) deep or 4 x 4 in (102 x 102 mm)
junction box 2.1 in deep (53 mm).
Indoors only.
Mount only where ambient temperature is
32 to 104 °F (0 to 40 °C).
Allow 4.5 in (114 mm) above and below
unit and between faceplates when
mounting several in a vertical layout.
Mount so line (mains) voltage wiring is at
least 6 ft (1.8 m) from sound or electronic
equipment and wiring.
Mount within of true vertical.
Mount to 4 x 4 in (102 x 102 mm), 2.1 in (53 mm) deep
U.S. junction box
Mount to 2-gang U.S. wallbox
Dimensions and Mounting
6.3 in
(160 mm)
0.4 in (10 mm)
Mount to 4 x 4 in (102 x 102 mm), 2.1 in (53 mm) deep
U.S. junction box with barrier
(for 277 V
loads if required by local electrical code)
1.2 in (30.5 mm)
5.1 in (129.5 mm)
Barrier
3
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369357 Rev. A 4 11.19.10
Power Modules
Switching Power Module
GRAFIK Eye®
Pull 12 AWG (2.5 mm
2
) copper (Cu) wires (75 °C/167 °F minimum) for input power and load circuit.
Strip 1/2 in (12 mm) insulation from wires before connecting.
Run separate neutral for load circuit - no common neutrals.
May be used with GFI breaker protected loads. Load circuit wiring (from GFI breaker to power module to
load) must be run in its own non-metallic conduit, or nuisance tripping may occur. Maximum 100 ft (30.5
m) between power module and load.
May be used with AFI breaker protected loads. Maximum load on AFI circuit is 1000 W. Exceeding 1000 W
may cause nuisance tripping of AFI breaker.
Note: The power modules may be on the same
circuit as the control unit only if the total load does
not exceed the rating of the breaker.
Wiring
Single Power Feed
1 2 3 4 5 6 L N
H/L
N
SH
H/L
N
Load
120 V
GRAFIK Eye QS
Zone in
Control Neutral
Wire to appropriate
zone
Legend
H/L Hot/Live
N Neutral
SH Switched Hot
DH Dimmed Hot
Ground
Not Used
Circuit breaker
120 V
{
4
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369357 Rev. A 5 11.19.10
Power Modules
Switching Power Module
GRAFIK Eye®
Multiple Power Feeds
Wiring
The load breaker may be on a different
phase than the control breaker.
1 2 3 4 5 6 L N
H/L
N
SH
H/L
N
N
H/L
Load
GRAFIK Eye QS
Zone in
Control Neutral
Wire to appropriate
zone
Legend
H/L Hot/Live
N Neutral
SH Switched Hot
DH Dimmed Hot
Ground
Not Used
Load breaker
Control breaker
120 V
}
120 - 277 V
Load wiring
{
5
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369357 Rev. A 6 11.19.10
Power Modules
Switching Power Module
GRAFIK Eye®
Wiring Multiple Power Modules to a Single GRAFIK Eye® Zone
Shown with separate feeds for control and loads. All breakers must be turned off prior to
installing or servicing the modules. Up to 3 power modules may be wired to a single zone.
1 2 3 4 5 6 L N
H/L
N
SH
H/L
N
H/L
N
H/L
N
H/L
N
H/L
N
N
H/L
SH
SH
Load
GRAFIK Eye QS
Zone in
Control Neutral
Wire to appropriate zone
Load breaker
Load
Zone in
Control Neutral
Load breaker
Load
Zone in
Control Neutral
Load breaker
Control breaker
Load wiring
1
for Power
Module #1
{
Load wiring
1
for Power
Module #2
{
Load wiring
1
for Power
Module #3
{
1
Load feed: 120 - 277 V for PHPM-SW-DV-WH
120 V
}
6
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369357 Rev. A 7 11.19.10
Power Modules
Switching Power Module
GRAFIK Eye®
Note: The power module may be on the same circuit/control
zone as the control device only if the total load does not
exceed the rating of the breaker (120 V only).
Multilocation Wiring
H/L
H/L
N
N
SH
Load
Legend
H/L Hot/Live
N Neutral
SH Switched Hot
DH Dimmed Hot
Ground
Not Used
Circuit breaker
{
3-wire
fluorescent
dimmer
120 V
(main
dimmer)
369357 Rev. A 7 11.19.10
3-wire
fluorescent
dimmer
120 V
(accessory/
companion
dimmer or
3-way switch)
H/L 120 V
N
Load
wiring
(see
Note
below)
Note:
1
Load feed: 120 - 277 V for PHPM-SW-DV-WH
SH
(red wire)
Cap off
DH
(yellow
or orange
wire)
Zone in
Control Neutral
For specific wire colors, see the wallbox lighting controls
catalog at www.lutron.com/wallbox catalog
7
®
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369357 Rev. A 8 11.19.10
Power Modules
Switching Power Module
GRAFIK Eye®
Wiring a Power Module to an LP, LCP, GP, or HomeWorks® Panel
Up to three switching power modules may be wired to an output of a 120 V LP or LCP panel. The load
type for the output must be set as non-dim load type on the panel’s circuit selector (for an LP or GP panel),
controller (for an LCP panel), or HomeWorks software (for a HomeWorks panel).
DH
DH
DH
DH
H
N
N
N
N
N
H/L
N
SH
H/L
N
Load
(1) 14 to 10 AWG
(2.0 to 4.0 mm
2
)
(1) 14 to 10 AWG
(2.0 to 4.0 mm
2
)
Zone In
Control
Neutral
Dimmed
Hot
Neutral
120 V Branch Circuit
Breakers
Neutral Lug
Neutral (1) 14 to 2/0 AWG
(2.0 to 70 mm
2
)
Power (Hot/Live)
(3) 14 to 2/0 AWG (2.0 to 70 mm
2
)
1
120 - 277 V if used with
PHPM-SW-DV-WH power module
Load
wiring
1
{
Wire to appropriate output
8