SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Radio Powr Savr Wireless Wall-Mount Occupancy and Vacancy Sensors
369481j 1 11.12.18
Radio Powr Savr Wireless Occupancy/
Vacancy Wall-Mount Sensor
Lutron Radio Powr Savr wall-mounted occupancy and
vacancy sensors are wireless, battery-powered, passive
infrared (PIR) sensors that automatically control lights via
RF communication to compatible dimming or switching
devices. These sensors detect the heat from people
moving within an area to determine when the space is
occupied. The sensors then wirelessly transmit the
appropriate commands to the associated dimming or
switching devices to turn the lights on or off automatically.
They combine both convenience and exceptional energy
savings along with ease of installation.
Features
• Wirelessoccupancy/vacancysensorhas2settings
available:Auto-On/Auto-Off,andManual-On/Auto-Off
• VacancymodelmeetsCATitle24requirements
• PassiveinfraredmotiondetectionwithexclusiveLutronXCT
Technology for fine motion detection
• 180°fieldofviewmodel:
– Minormotion=1500ft
2
(139.4 m
2
)
– Majormotion=3000ft
2
(278.7 m
2
)
• 90°fieldofviewmodel:
– Minormotion=1225ft
2
(113.8 m
2
)
– Majormotion=2500ft
2
(232.3 m
2
)
• Hallwaymodelwithlong,narrowfieldofview:
– Majormotion=coverageofupto150ft(45.7m)
• SimpleandintuitiveadjustmentsavailableforTimeout,
Activity, and Auto-On settings
• Accessibletestbuttonsmakesetupeasy
• Lensilluminatesduringtestmodetoverifyideallocations
• Multiplesensorscanbeaddedforextendedcoverage;refer
to product specification submittal of receiving device to
determine system limits
• 10-yearbatterylifedesign
• RoHScompliant
Compatible RF Devices
• ForusewithLutronproductsonly
• SupportssimultaneousassociationwithmultipleLutron
ClearConnectdevicesand/orsystems*
* ContactLutronCustomerServiceatwww.lutron.comforfrequency/
channel code compatibility with your particular geographic region, and for
integrating with other Lutron® lighting and shading products.
Models Available
• LRF - LB-P-WH
CoverageType
Sensor Type
Frequency/ChannelCode
Example:
LRF
2
-
VH
LB-P-WH
(434MHzWhiteHallwayVacancySensor)
Frequency/Channel Code
2=431.0–437.0MHz(US,Canada,Mexico,Brazil)*
3=868.125–869.850MHz(Europe,UAE)
4=868.125–868.475MHz(China,Singapore)
5=865.5–866.5MHz(India)
7=433.0–433.7MHz(HongKong,Macau)
Sensor Type
O=Occupancy/Vacancy(Auto-On/Auto-Off)
V=Vacancy(Manual-On/Auto-Off)**
Coverage Type
H=Hallway
K=90°Corner-Mount
W=180°Wall-Mount
* BAAcompliantmodelsavailableforLRF2configurations.Adda“U”prefix
to your chosen model number. Example: ULRF2-OWLB-P
** VacancysensortypeforLRF2modelsonly
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Radio Powr Savr Wireless Wall-Mount Occupancy and Vacancy Sensors
369481j 2 11.12.18
RF Range
• Distancebetweenlocalloadcontrolsandsensorshould
notexceed60ft(18m)line-of-sightor30ft(9m)through
walls.
Sensor Coverage Test
• Dedicatedtestbutton
• Lensilluminatesorangeinresponsetomotionduringtest
mode
Wireless Communication Test
• Dedicatedtestbutton
• Turnassociatedloadsonandoff
Timeout Options
• 1minute*
• 5minutes
• 15minutes(defaultsetting)
• 30minutes
Auto-On Options (Occupancy Versions Only)
• Enabled: Sensor turns lights ON and OFF automatically
(default setting)
• Disabled**:LightsmustbeturnedONmanuallyfrom
dimming or switching device. Sensor turns lights OFF
automatically
Sensitivity Options
• Low Activity: (default setting)
• Medium Activity:
• High Activity:
* Intendedforuseinhigh-activity,briefly-occupiedareasonly
** Thereisa15-secondgraceperiodthatbeginswhenthelightsare
automatically turned off, during which the lights will automatically turn
backoninresponsetomotion.Thisgraceperiodisprovidedasasafety
and convenience feature in the event the lights turn off while the room is
still occupied, so that the user does not need to manually turn the lights
backon.After15seconds,thegraceperiodexpiresandthelightsmust
be manually turned on.
Specifications
Regulatory
• LutronQualitySystemsRegisteredtoISO9001:2008
Regulatory Approvals
LRF2-
• cULus® listed
• FCCcertified
• ICcertified
• COFETELcertified
• ANATELcertified
• SUTELcertified
• MeetsCA(U.S.A.)EnergyCommissionTitle24
requirements
LRF3-
• CEmarked(EuropeanUnion)
• TRAtypeapproved(UnitedArabEmirates)
• CITCtypeapproved(SaudiArabia)
LRF4-
• SRRCtypeapproved(MainlandChina)
• iDAregistered(Singapore)
LRF5-
• WPCtype(India)
Power/Performance
• Operatingvoltage:3V-
• Operatingcurrent:14μAnominal
• RequiresoneCR123lithiumbattery
• 10-yearbattery-lifedesign
• Non-volatilememory(savedchangesarestoredduring
power loss)
Environment
• Temperature:32°Fto104°F(0°Cto40°C)
• Forindooruseonly
• Relativehumidity:lessthan90%non-condensing
Note: For unconditioned environments where the air
temperature may approach the temperature of the
occupants, additional sensors will be needed to achieve
the same coverage. This is true of any sensor that relies
exclusively on passive infrared technology.
Warranty
• 5-YearLimitedWarranty.ForadditionalWarranty
information,pleasevisitwww.lutron.com/
TechnicalDocumentLibrary/Sensor_Warranty.pdf
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Radio Powr Savr Wireless Wall-Mount Occupancy and Vacancy Sensors
369481j 3 11.12.18
Installation Overview
Sensor Setup
• SensorsetupisavailableasaservicebyLutron.Formore
information, please see the Sensor Layout and Tuning
specificationsubmittal(P/N3601235)atwww.lutron.com.
Sensor Placement
• Themountingheightofthesensorshouldbebetween6ft
and 8 ft (1.6 m and 2.4 m).
• Forsmallerroomslessthan12ft×12ft(3.7m×3.7m),
detection may be improved by mounting the sensor at 6 ft
(1.8 m) from the floor.
• Theabilitytodetectmotionrequiresthatthesensorhave
line-of-sight of all room occupants. The sensor must have
an unobstructed view of the room. DO NOT mount behind
or near tall cabinets, shelves, hanging fixtures, etc. The
sensor cannot detect occupants through glass objects
such as patio or shower doors.
• Hotobjectsandmovingaircurrentscanaffectthe
performance of the sensor. To ensure proper operation,
the sensor should be mounted at least 4 ft (1.2 m) away
fromlightbulbsandHVACvents.
• Theperformanceofthesensordependsonatemperature
differential between the ambient room temperature and
thatofroomoccupants.Warmerroomsmayreducethe
sensor’s ability to detect occupants.
• Distancebetweenlocalloadcontrolsandsensorshould
notexceed60ft(18m)line-of-sightor30ft(9m)through
walls.
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Radio Powr Savr Wireless Wall-Mount Occupancy and Vacancy Sensors
369481j 4 11.12.18
Figure A. 180° Wall-Mount Sensor and Hallway Sensor
MountingBracket
Figure B. 90° Corner-Mount Sensor
MountingBracket
Mounting
• 180°andhallwaysensorsmountdirectlytowallwith
mountingbracket(included).SeeFigureA.
• 90°sensorsmountdirectlyincorneroronwalloffset
awayfromcornerwithmountingbracket(included).See
FigureB.
Temporary mounting is recommended to test sensor
coverage and wireless communication before
permanently installing the sensor.
Temporarymounting:A3MTMCommandTM adhesive
strip is provided for temporarily mounting and
testing the sensor. This strip is designed for easy,
damage-free removal and is not reusable.
Permanentmounting:Mountingbracket,screws,
and anchors are provided to mount sensor.
• TheFlexibleMountingArmature,LRF-ARM-WH
(purchased separately), allows sensors to be mounted at
greater heights on a ceiling, wall, or other flat surface.
The ball-and-clamp design expands the coverage
area for Lutron standard wall-, corner-, or hall-mount
sensors.SeeFigureC.
– Commonmountingareas:warehouseaisles,loading
docks,longhallways.
Figure C. Flexible Mounting Armature
Measurementsare:in(mm)
MountingBracket
(for wall or ceiling)
3.625
(92)
2.18
(55)
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Radio Powr Savr Wireless Wall-Mount Occupancy and Vacancy Sensors
369481j511.12.18
Dimensions
4.35in
(110mm)
1.8 in
(46 mm)
1.35in
(34 mm)
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Radio Powr Savr Wireless Wall-Mount Occupancy and Vacancy Sensors
369481j 6 11.12.18
Coverage Diagrams
180° Wall-Mount Sensors
Models:LRFX-OWLB-P-WHandLRFX-VWLB-P-WH
0 10ft
(3.0m)
20ft
(6.1 m)
30ft
(9.1 m)
40ft
(12.2 m)
50ft
(15.2m)
60ft
(18.3 m)
Horizontal Beam Diagram
25ft
( 7. 6 m)
25ft
( 7. 6 m)
20ft
(6.1 m)
20ft
(6.1 m)
10ft
(3.0m)
10ft
(3.0m)
0
15ft
(4.6 m)
25ft
( 7. 6 m)
50ft
(15.2m)
60ft
(18.3 m)
Tested Coverage Area
Majormotioncoverage:3000ft
2
(278.7 m
2
)
Minormotioncoverage:1500ft
2
(139.4 m
2
)
ComplianttoNEMAWD7testgrid(shownbelow)
0 10ft
(3.0m)
20ft
(6.1 m)
30ft
(9.1 m)
40ft
(12.2 m)
50ft
(15.2m)
60ft
(18.3 m)
Vertical Beam Diagram*
7 ft
(2.1 m)
0
* Sensormountingshownat7ft(2.1m).Mountingheightshouldbebetween6ftand8ft(1.6mand2.4m).
6
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Radio Powr Savr Wireless Wall-Mount Occupancy and Vacancy Sensors
369481j 7 11.12.18
Coverage Diagrams
90° Corner-Mount Sensors
Models:LRFX-OKLB-P-WHandLRFX-VKLB-P-WH
Horizontal Beam Diagram
0 0
Tested Coverage Area
Majormotioncoverage:2500ft
2
(232.3 m
2
)
Minormotioncoverage:1225ft
2
(113. 8 m
2
)
ComplianttoNEMAWD7testgrid(shownbelow)
0 10ft
(3.0m)
20ft
(6.1 m)
30ft
(9.1 m)
40ft
(12.2 m)
50ft
(15.2m)
Vertical Beam Diagram*
7 ft
(2.1 m)
0
* Sensormountingshownat7ft(2.1m).Mountingheightshouldbebetween6ftand8ft(1.6mand2.4m).
35ft
(10.7m)
50ft
(15.2m)
35ft
(10.7m)
50ft
(15.2m)
50
ft
(15.2
m)
35
ft
(10.7
m)
7
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Radio Powr Savr Wireless Wall-Mount Occupancy and Vacancy Sensors
369481j 8 11.12.18
Coverage Diagrams
Hallway Sensors
Models:LRFX-OHLB-P-WHandLRFX-VHLB-P-WH
• Designedtomountattheendofahallwaywithaclear
view down the length of a hall.
• Detectionatlongerdistancesisbestwhenmotionoccurs
at right angles to the sensor.
• Multiplesensorscanbeusedtoextendcoverage.
Maximum Recommended Hallway Length
Hall Width Hall Length
6 ft (1.8 m) or less
50ft(15.2m)
8 ft (2.4 m) or less 100ft(30.5m)
10ft(3.0m)ormore 150ft(45.7m)
* Sensormountingshownat7ft(2.1m).Mountingheightshouldbebetween6ftand8ft(1.6mand2.4m)andcenteredwithinhallway.
Side View*
150ft
(45.7m)
0 25ft
( 7. 6 m)
50ft
(15.2m)
75ft
(22.9 m)
100ft
(30.5m)
125ft
(3 8 .1 m)
7 ft
(2.1 m)
0
Top View
150ft
(45.7m)
0 25ft
( 7. 6 m)
50ft
(15.2m)
75ft
(22.9 m)
100ft
(30.5m)
125ft
(3 8 .1 m)
5ft
(1.5m)
5ft
(1.5m)
0
)Lutron,Lutron,andClearConnectaretrademarksofLutronElectronicsCo.,Inc.,registeredintheU.S.andothercountries.
RadioPowrSavrandXCTaretrademarksofLutronElectronicsCo.,Inc.
3MandCommandaretrademarksof3MCompany.
8