Light Management Hub
The Quantum Light Management Hub (QP2) connects
Lutron QS devices, Lutron power panels, and
DMX512 devices to your Quantum lighting
control system.
Features
• Designed to control, manage, and monitor any Lutron
Energi Savr Node units, Lutron power panels,
GRAFIK Eye QS units, Sivoia QS shade / drapery
systems, and DMX512 devices.
• Supports both astronomic and time-of-day events
to automatically control the lights and shades in
the system.
• Simple reconfiguration of a space without rewiring.
• Individually control, monitor, and adjust any light or
shade in a space.
• QS links are topology-free.
QP2 Hub Capabilities
• Lighting management panels communicate via an
Ethernet connection using multicast protocol.
• Each hub can contain up to 2 Quantum processors.
Each processor has 2 digital communication links
for a maximum of 4 links per hub. Each link can
be configured to communicate on one of the
following protocols.
- Lutron power panels
- Lutron QS devices
- DMX512 devices
369-377c 1 05.28.2019
Centralized Control Equipment
Quantum
230 V CE Light Management Hub
Panel Capabilities
• Each Quantum Light Management Hub (QP2)
has 2 links that can be individually configured to
communicate with:
– Lutron power panels
– Lutron QS devices
DMX-512 devices for lighting zones (use
QSE-CI-DMX for DMX integration zones)
Allowed combinations of links a single processor:
1
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-377c 2 05.28.2019
Centralized Control Equipment
230 V CE Light Management Hub
Quantum
Specifications
Regulatory Approvals
CE
Power
• Input voltage: 220 - 240 V
, normal / emergency feed
50 / 60 Hz 10 A
• Output: Processor - 24 V
1 A per link
83 BTUs/hr
Physical Design
• Enclosure: IP-20 protection
• Weight: 20.4 kg
Mounting
• Surface mount only
Environment
• For indoor use only
• 0 ºC to 40 ºC
• Relative humidity less than 90% non-condensing
2
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-377c 3 05.28.2019
Centralized Control Equipment
230 V CE Light Management Hub
Quantum
How to Build a Model Number
Example
QP2 - 2P0CSE - 230
Panel
Type
Number of
Processors
Accessing
Device
Voltage
Panel Type
QP2 = Quantum Light Management Hub
Number of Processors
1P = 1 Quantum processor
2P = 2 Quantum processors
Accessing Device
SE = 5-port unmamaged Ethernet switch
Voltage
230 for 220 - 240 V
Additional Ratings
50 / 60 Hz
Output: Processor - 24 V 1 A per link
Available Model Numbers
Contact Lutron for options not listed below.
QP2-1P0CSE-230
QP2-2P0CSE-230
Note:
This panel is rated for Class A, Commercial Use Only.
3
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-377c 4 05.28.2019
Centralized Control Equipment
230 V CE Light Management Hub
Quantum
Dimensions
All dimensions shown as: mm
400
400
324
63.5
673
800
800
148
4
Front ViewLeft Side View Right Side View
Top View
Bottom View
22.22
7.95
4
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-377c 5 05.28.2019
Centralized Control Equipment
230 V CE Light Management Hub
Quantum
Mounting and Conduit Entry Notes
• Water damages equipment. Mount in a location where the panel and
processors will not get wet. Mount within 7˚ of true vertical.
• A minimum of 305 mm unobstructed space is required in front of and
below the panel for ventilation.
Front View Side View
Ceiling
Wall
IEC PELV / NEC
® Class 2
wiring only for control links
and Ethernet connection
Dedicated feed
Mains voltage only
Alternate IEC
PELV / NEC
®
Class 2 entry
Alternate IEC
PELV / NEC
®
Class 2 entry
Alternate IEC
PELV / NEC®
Class 2 entry
5
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-377c 6 05.28.2019
Centralized Control Equipment
230 V CE Light Management Hub
Quantum
Panel Overview
Mains voltage input,
normal / emergency feed
Receptacle (for Lutron service use only)
Panel power switch
IEC PELV / NEC
® Class 2 power supply board
Configurable links
(power panel or Lutron QS link)
5-port unmanaged Ethernet switch
Quantum processors
(2 maximum)
IEC PELV / NEC® Class 2 configurable link
wire trough
Processor LEDs
Unused (no connect)
IEC PELV / NEC
® Class 2 barrier
6
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-377c 7 05.28.2019
Centralized Control Equipment
230 V CE Light Management Hub
Quantum
Line Voltage Wiring
Protected Earth
(green)
Neutral
(blue)
Line
(brown)
Notes
• Mains voltage must enter hub from top right of hub.
• Run a dedicated 220-240 V
normal / emergency
feed.
• Run wiring so mains line voltage is separate from
IEC PELV / NEC® Class 2 wiring.
PE
N
220-240 V
N/E
Wire Sizes
• Power feed (live): 2.5 to 4.0 mm
2
Receptacle
for Lutron
Service
use only
7
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-377c 8 05.28.2019
Centralized Control Equipment
230 V CE Light Management Hub
Quantum
Quantum Ethernet Wiring
Notes
The inter-processor wiring is considered IEC PELV / NECR Class 2; do
not run in the same conduit as line (mains) voltage wiring.
• Processors cannot be daisy-chained. Each must be connected to an
Ethernet switch.
- Inter-processor wiring uses a standard Ethernet connection. All
wiring must comply with IEEE 802.3 standards and must support
Any-Source Multicast communication.
• Wiring distance for any single “wire segment”* is 100 m max; use
unmanaged Ethernet switches for longer distances.
• Processors cannot be more than 6 “wire segments” from the server.
• A dedicated network or VLAN is recommended for the lighting
control system.
• For more information about connecting a Quantum system to a
corporate or building wide network, please refer to the Quantum IT
Guide (P/N 040423) at www.lutron.com/ITGuide
* A wire segment is a length of cable connecting two devices communicating
over Ethernet.
Ethernet
switch
Example of Ethernet Wiring: Riser Diagram
Quantum
Light
Management
Hub
Quantum
Light
Management
Hub
Quantum
Light
Management
Hub
Quantum
Light
Management
Hub
Quantum
Light
Management
Hub
Quantum
server
Floor
Floor
Floor
To additional
Quantum
Light
Management
Hubs
Unmanaged Ethernet switch
(not provided by Lutron)
Note: Refer to the IT Guide for
managed switch configuration
requirements.
8
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-377c 9 05.28.2019
Centralized Control Equipment
230 V CE Light Management Hub
Quantum
Configurable Link Wiring: Power Panel Link
5 4 3 2 1
DRAIN
MUX
MUX
V+
COM
Link
terminator
(LT-1)
Control wiring
(1) 2.5 mm
2
1: Common
Data link
(1) shielded, twisted pair 1.0 mm
2
3: MUX
4: MUX
D: Drain wire in shield (keep away
from ground and all electronics)
Power panel
1 COM
2 N/C
3 MUX
4 MUX
D DRAIN
5 Sense line
Power panel
1 COM
2 N/C
3 MUX
4 MUX
D DRAIN
5 Sense line
Power panel
1 COM
2 N/C
3 MUX
4 MUX
D DRAIN
5 Sense line
4 3 3 4
Link
terminator
(LT-1)
Emergency/essential
sense line
(1) 1.0 mm
2
5: Sense line
Sense line is used when there
is a panel being supplied by an
emergency/essential feed
Data A OK
Data B OK
Power OK
12345D
C
D
A B
Common
24VFW
MUX
MUX
Drain
Sense
Comm
Drain
MUX
MUX
C
1
234
D
5
D
Link Link
S
ELECT
C
IRCUIT
Data link: twisted,
shielded pair
1.0 mm
2
3: MUX
4: MUX
Drain
(2) 2.5 mm
2
Configurable
links
Notes
Power panel link must be daisy-chained (no T-taps).
Maximum of 32 power panels per link (note that some GP series
panels can contain more than one circuit selector per panel).
It is not necessary to have the Quantum connection at the end of
the link. The panel can be in the middle of the link also.
The sense wire (terminal 5) is used whenever there is a panel
being supplied by an emergency/essential feed; see power panel
instructions for details. The sense wire will not be terminated at the
Quantum hub.
Each IEC PELV / NEC® Class 2 terminal can accept only two
0.5 mm
2
-1.0mm
2
wires. Two 2.5mm
2
conductors will not fit.
Connect as shown using appropriate wire connectors.
Power Panel IEC PELV / NEC® Class 2
Terminal Wiring
Total length of the power panel link may be no more than 600 m.
Lutron model: MX-RPTR-220 / 240 can be used to extend the link
beyond 600 m. Contact Lutron for more information.
Total length of control link may be no more than 600 m. If link
repeater interface and GRX-CBL-46L cable are used, length may
be up to 1200 m.
IEC PELV / NEC® Class 2 wiring cable is available from Lutron
(GRX-CBL-46L) and contains two 2.5mm
2
conductors for control
power, one twisted, shielded pair of 1.0mm
2
for data link, and one
1.0mm
2
conductor for emergency (essential) sense line.
Sense: 1.0 mm
2
Processor link
terminal
Unused
9
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-377c 10 05.28.2019
Centralized Control Equipment
230 V CE Light Management Hub
Quantum
Configurable Link Wiring: QS Link
Connecting GRAFIK Eye QS units to the QS Link
4 3 2 1
C B A
4 3 2 1
C B A
4 3 2 1
C B A
54321
4
3
2
1
4
3
2
1
4
3
2
1
GRAFIK Eye QS control unit
QS
wallstations
Configurable
links
1234
12
ABC
123456LN
54321
Sivoia QS
smart power
supply panel
Sivoia QS
shade
GRAFIK Eye QS control unit
Connecting Sivoia QS Shades to the QS Link
4 3 2 1
C B A
Data link: (1) twisted, shielded pair
1.0 mm
2
3: MUX
4: MUX
IEC PELV / NEC
® Class 2 control wiring
(2) 1.0 mm
2
1: Common
2: 24 V
(2) 2.5 mm
2
(2) 2.5 mm
2
IEC PELV / NEC®
Class 2
Terminal
Wiring
Note: Wallstations are powered directly from the light
management hub (not the GRAFIK Eye QS control unit)
DRAIN
MUX
MUX
V+
COM
DRAIN
MUX
MUX
V+
COM
Unused
(Drain wire in shield - Connect together to make one continuously
linked shield. Keep away from ground and control electronics.)
(Drain wire in shield - Connect together to make one continuously linked
shield. Keep away from ground and control electronics.)
DRAIN
wires
Available Power Draw
Units (PDUs) per link
Maximum Link
Length
Wire Gauge
Available from Lutron
in one cable
33 152.4 m
Power (terminals 1 and 2) 1 pair 1.0 mm
2
Data (terminals 3 and 4)1 pair 0.5 mm
2
twisted and shielded
GRX-CBL-346S
GRX-PCBL-346S
33 609.6 m
Power (terminals 1 and 2) 1 pair 4.0 mm
2
Data (terminals 3 and 4) 1 pair 0.5 mm
2
twisted and shielded
GRX-CBL-46L
GRX-PCBL-46L
10
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-377c 11 05.28.2019
Centralized Control Equipment
230 V CE Light Management Hub
Quantum
Configurable Link Wiring: QS Link
4 3 2 1
C B A
4 3 2 1
C B A
4 3 2 1
C B A
54321
4
3
2
1
4
3
2
1
4
3
2
1
QSNE-2DAL-D shown.
QS terminal connections are identical
regardless of model number.
From right
side of
configurable
links in
panel
QS
wallstations
Note: Wallstations are
powered directly from the light
management hub (not the
Energi Savr Node QS unit).
Connecting Energi Savr Node devices to the QS Link
DRAIN
MUX
MUX
V+
COM
(Drain wire in shield - Connect together to make one continuously linked shield. Keep away from ground and control electronics.)
Notes
System communication uses IEC PELV / NEC
® Class 2 wiring.
Follow all local and national electrical codes when installing IEC
PELV / NEC
® Class 2 wiring with mains wiring.
Each terminal accepts up to two 0.5 mm
2
-1.0 mm
2
wires.
Total length of control link must not exceed 600 m; If exceeding 600 m,
contact Lutron for wiring configuration.
Make all connections in the control unit’s wallbox.
A Quantum QS link can have up to 512 switch legs (outputs),
99 QS devices, and 33 power draw units (see page 4).
QS Link Wiring can be T-tapped or daisy-chained.
Wire sizes:
- Two 2.5 mm
2
conductors for control power.
- One twisted, shielded pair of 1.0 mm
2
for data link.
- Cable is available from Lutron: GRX-CBL-46L.
See Lutron cable specifications for all plenum and non-plenum
options available.
http://www.lutron.com/TechnicalDocumentLibrary/cables_nonplenum.
pdf
http://www.lutron.com/TechnicalDocumentLibrary/cables_plenum.pdf
The Quantum Light Management Hub provides 33 power draw units
(PDUs) on the QS Link. For more information, see “Power Draw Units
on the QS Link”(Lutron P/N 369405), at
http://www.lutron.com/TechnicalDocumentLibrary/369405%20
pdu%20spec%20submittal.pdf
Wire Gauge QS Link Max. Length
2.5 mm
2
600 m
1.5 mm
2
250 m
1.0 mm
2
150 m
11
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-377c 12 05.28.2019
Centralized Control Equipment
230 V CE Light Management Hub
Quantum
Configurable Link Wiring: DMX512
DMX512 Output Wiring Example
5 4 3 2 1
DRAIN
MUX
MUX
V+
COM
Link
terminator
(LT-1)
DMX512
Controllable
Device
COMMON
DATA +
DATA -
DMX512
Controllable
Device
COMMON
DATA +
DATA -
DMX512
Controllable
Device
COMMON
DATA +
DATA -
4 3 3 4
Link
terminator
(LT-1)
(3) Configurable Links
12
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-377c 13 05.28.2019
Centralized Control Equipment
230 V CE Light Management Hub
Quantum
Link
terminator
(LT-1)
Link
terminator
(LT-1)
DMX512 Lighting Control Console
(not provided by Lutron)
Lutron DMX512 Input
Jack model:
NT-DMXJ-IN
DMX512 Cable
(see table on next page)
DMX Patch Cable
(not provided by Lutron)
DMX512 Input Wiring Example
5 4 3 2 1
DRAIN
MUX
MUX
V+
COM
4 3
43
(3) Configurable Links
13
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
369-377c 14 05.28.2019
Centralized Control Equipment
230 V CE Light Management Hub
Quantum
Notes
• Installation and all devices must comply with the
ANSI E1.11-2008, USITT DMX512-A standard.
• Below are a few Important points from the standard:
All DMX512 devices in a DMX512 universe must be
wired in a daisy-chain configuration.
Total length of the link wiring for one DMX512
universe must not exceed 400 m. DMX repeaters
or splitters can be used to extend the link. All
repeaters must comply with the standard. The
repeater manufacturer’s guidelines must
be followed.
All cable used must comply with the standard.
Lutron models GRX-CBL-DMX-250 and
GRX-CLB-DMX-500 comply with the standard and
are recommended.
DMX512 link terminators must be installed at both
ends of the DMX512 link. Lutron model LT-1A link
terminators are included with the panel and are
recommended. Note that some DMX512 devices
have built-in link terminators.
A maximum of (31) DMX512 devices can be
directly connected to the DMX512 controller. If
(32) or more devices are required, DMX512
repeaters or splitters must be used to extend the
number of devices. A repeater or splitter is needed
so that no more than (32) devices are directly
connected on the same wire segment. Note that
link terminators are required at the beginning and
end of every wire segment.
• The Quantum processor can be programmed to
either control DMX512 devices (DMX512 output) or
to receive DMX512 signals from a DMX512 controller
(DMX512 input) such as a theatrical stage board.
All wiring must be low-voltage IEC PELV / NECR Class
2 wiring. Each terminals of the Lutron processor
can accept only stranded wire, and either
(1 or 2) 0.5 mm² – 1.0 mm² conductors or
(1) 1.5 mm² – 2.5 mm².
• The Quantum processor can be at the end or in the
middle of the DMX512 link. The link terminators must
always be installed at the ends of the link.
• Only one link of the processor can be configured as
a DMX512 link. The other link of the processor must
be configured as a QS link.
• DMX512 devices must be addressed prior to
commissioning of the system. A schedule of
the DMX devices and their addresses must be
supplied to the Lutron project manager prior to
commissioning. Lutron is not responsible for the
addressing of the DMX512 devices.
• Refer to the Lutron DMX512 Application Note #592
(P/N 048592) at www.lutron.com for information on
the different DMX512 applications that Lutron
can provide.
Configurable Link Wiring: DMX512 (continued)
DMX Cable Wiring Table
This table shows examples of some Manufacturers of DMX512
cable and how they should be terminated.
DMX512 Cable Type Wire
From
Circuit
Selector
To DMX512 Jack
Belden 9729/89729
(2) drain/shield C C (1) (white / black)
black + – (2) (red)
white + (3) (yellow)
black No Connect – (4) (blue)
red No Connect + (5) (black)
Duraflex 22 / 4WS
or Lutron
GRX-CBL-DMX-250/500
(2) drain/shield C C (1) (white / black)
white + – (2) (red)
black + (3) (yellow)
green No Connect – (4) (blue)
red No Connect + (5) (black)
)Lutron, Lutron, EcoSystem, Energi Savr Node, GRAFIK Eye, Hi-Lume,
Leaf Design, Pico, Sivoia, and Quantum are trademarks or registered
trademarks of Lutron Electronics Co., Inc. in the US and/or other countries.
NEC is a registered trademark of National Fire Protection Association,
Quincy, Massachusetts.
UL is a trademark of UL LLC.
14