R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
grxsld-1 06.30.04
Control Units
Slider Control
®
GRAFIK Eye 4000 Series Slider Control Unit
Description
• Controls up to 8 zones of lighting.
• Provides pushbutton recall of a single lighting
scene.
• Stores up to 12 scenes that can be recalled
using an optional Access Control.
• Includes default “panic” scenes (full-on)
• Allows full-range dimming plus slide-to-off
using zone sliders.
• Provides a user-selectable Master Slider.
• Controls virtually any light source via dimming
panels.
• Mounts in a standard U.S. wallbox.
Models available to:
• Control 3, 4, 6, or 8 zones of lighting.
Slider Control Units work with:
• GRAFIK Eye Wallstations
• GP and LP Dimming Panels
GRXSLD-4106-WH
1
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
grxsld-2 06.30.04
Control Units
Slider Control
®
Power
• Low-voltage type Class 2 (PELV)
Operating voltage: 24VDC.
Lighting Sources/Load Types
Controls lighting sources with a smooth, continuous Square Law
dimming curve via GP and LP Dimming Panels.
Lighting Control
• 12 user-programmable slider scenes plus 2 panic scenes and off.
• Light levels fade smoothly between scenes. Fade time can be set
differently for each scene, between 0-59 sec. or 1-60 min. Fade
time is not adjustable for panic scenes.
Key Design Features
• Meets IEC 801-2. Tested to withstand 15kV electrostatic discharge
without damage or memory loss.
• Power failure memory automatically restores lighting to the scene
selected prior to power interruption.
• Faceplate snaps on with no visible means of attachment.
System Communications and Capacities
• Low-voltage type Class 2 (PELV) wiring connects Control Units,
Wallstations, and Control Interfaces.
• Up to 8 Control Units may be linked to control up to 64 zones.
• Up to 16 total Wallstations and Control Interfaces may be added
for a total of 24 control points.
Environment
• 32-104°F (0-40°C). Relative humidity less than 90% non-
condensing.
Specifications
2
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
grxsld-3 06.30.04
Control Units
Slider Control
®
How to Build a Model Number
G R X S L D - 4 1 0 6 - W H
Prefix
Number
of Zones
Color
Option
Prefix:
GRXSLD for GRAFIK Eye 4000 Series
Slider Control Units
Number of Zones:
3, 4, 6, or 8
Color Option:
Architectural Matte Finishes
White WH
Ivory IV
Beige BE
Gray GR
Brown BR
Black BL
Architectural Metal Finishes
Bright Brass BB
Bright Chrome BC
Satin Brass SB
Number
of Zones
3
4
6
8
Model Number
GRXSLD-4103-__
GRXSLD-4104-__
GRXSLD-4106-__
GRXSLD-4108-__
Model Numbers
3
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
grxsld-4 06.30.04
Control Units
Slider Control
®
1 15/16"
(49mm)
5/16"
(8mm)
4 9/16"
(116mm)
Dimensions
GRXSLD-4103
GRXSLD-4104
GRXSLD-4106
GRXSLD-4108
6 11/16"
(168mm)
6 11/16"
(168mm)
8 5/16"
(208mm)
8 5/16"
(208mm)
Faceplate
Bezel
GRXSLD Control Unit
Mounting
Notes:
• Use standard U.S. wallboxes; 3.5 in. (90mm) deep recommended, 2.75 in. (70mm) deep minimum.
• To remove faceplate from unit, remove the slider knobs and pull faceplate off.
4
123456
4
3
2
1
S
e
n
s
e
+
2
4
V
C
o
m
m
n
C
o
m
m
o
n
D
r
a
i
n
D
r
a
i
n
M
U
X
M
U
X
M
U
X
M
U
X
LinkLink
Data B OK PowerData A
AB
1234D5 C D
1234D5 C D
SSA
SSA RTN
DO NOT USE
2 IN, OUT
1 IN, OUT
DO NOT USE
MUX (4) IN
MUX (3) IN
MUX (4) OUT
MUX (3) OUT
CU WIRE
ONLY
4
3
2
1
12
3
45
D
USA: CLASS 2
IEC: PELV
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
grxsld-5 06.30.04
Control Units
Slider Control
®
Low-Voltage Class 2 (PELV) Wiring
• Connect Drain/Shield as shown. Terminate only at Power Panel if Drain Terminal
is provided. Connect the bare drain wires and cut off the outside shield.
• Make all connections in the Control Unit’s wallbox. Remote connections (T-taps)
must be in a switch box or junction box with a maximum wire length of 8 ft.
(2.5m) from the link to the connected unit.
Dimming Panel
Rear View of GRXSLD Control Unit
Wallstation/
Control Interface
Blue
Drain
Drain
Black
To additional Wallstations/
Control Interfaces (16 maximum)
Class 2/PELV
Control Wiring
1: Common
2: 24VDC
Data Link
3: MUX
4: MUX
D: Drain/Shield
All-in-one cable available
from Lutron:
GRX-CBL-46L
5