Power
• Low-voltage type Class 2 (PELV)
Operating voltage: 24VDC.
Lighting Sources/Load Types
Controls lighting sources with a smooth, continuous Square Law
dimming curve via GP and LP Dimming Panels.
Lighting Control
• 12 user-programmable slider scenes plus 2 panic scenes and off.
• Light levels fade smoothly between scenes. Fade time can be set
differently for each scene, between 0-59 sec. or 1-60 min. Fade
time is not adjustable for panic scenes.
Key Design Features
• Meets IEC 801-2. Tested to withstand 15kV electrostatic discharge
without damage or memory loss.
• Power failure memory automatically restores lighting to the scene
selected prior to power interruption.
• Faceplate snaps on with no visible means of attachment.
System Communications and Capacities
• Low-voltage type Class 2 (PELV) wiring connects Control Units,
Wallstations, and Control Interfaces.
• Up to 8 Control Units may be linked to control up to 64 zones.
• Up to 16 total Wallstations and Control Interfaces may be added
for a total of 24 control points.
Environment
• 32-104°F (0-40°C). Relative humidity less than 90% non-
condensing.
Specifications