Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
3691017b 2 08.12.16
Preset Dimming Controls
GXI-3000
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
•ProvidesairgapisolationwhentheOffsceneis
selected.
•10-yearpowerfailurememoryautomaticallyrestores
lightingtolevelspriortopower
interruption.
•Faceplatesnapsonwithnovisiblemeansof
attachment.
System Communications and Capacities
•Low-voltagetypePELVwiringconnectsControl
Units,Wallstations,andControlInterfaces.
•Upto8ControlUnitsmaybelinkedtocontrolupto
32zones.
•Upto16totalWallstationsandControlInterfaces
maybeaddedforatotalof24controlpoints.
Environment
•0-40°C.Relativehumiditylessthan90%
non-condensing.
Input Power
•230V~(CE)50Hz
•LightningStrikeProtection:
Canwithstandvoltagesurgesofupto6000V~
andcurrentsurgesupto3000A.
Sources
Controlsthefollowinglightingsourceswitha
smooth,continuousSquareLawdimmingcurve
oronafullconductionnon-dimbasis:
•LEDs
•Incandescent
•ElectronicLowVoltage
•MagneticLowVoltage
•Fluorescent
•NeonandColdCathode
Load Types
•Leading/Trailing-edgedimming
•0-10V-
•DALIR(broadcastonly)
•Switching(non-dimming)
Preset Controls
•4presetlightingscenesandoffareaccessiblefrom
theControlUnitfrontpanel.
•12additionalscenesarestoredintheControlUnit.
ThesescenesareaccessibleviaWallstationsand/or
ControlInterfaces.
•Lightlevelsfadesmoothlybetweenscenes.Fade
timecanbesetdifferentlyforeachscene,between
0-59sec.or1-60min.FadetimefromOffiscapped
at5sec.
Key Design Features
•MeetsIEC801-2.Testedtowithstand15kV
electrostaticdischargewithoutdamageor
memoryloss.
•Providesover-currentandshort-circuit
protection.
•ProvidescapabilitytotrimHighEndandLowEnd.
•Manualorautomaticselectionbetween
leadingedgeortrailingedgedimmingforlow
voltagetransformers.
Specifications