SPECIFICATION SUBMITTAL
ntgrxwstns-3 12.12.03
Wallstations
Architectural Style
®
NTGRX-4B-__-__
4-Button Wallstation
Description
• Used to select scenes in GRAFIK Eye Control
Units.
• Scene selection functionality can be selected in
the field.
• Status LEDs indicate which scene is selected.
• Works with GRAFIK Eye 3000 and 4000 Series
Control Units.
• Selects scenes in just one Control Unit or a group
of up to eight Control Units.
• Can be ganged with the NTGRX-4S Wallstation to
give occupants access to 8, 12, or 16 scenes.
Finish and Engraving Options
• Available with engraving to meet specific project
needs.
• Available in a “no-insert” version for a sleeker look.
LEDs
Insert
Scene
selection
buttons
Color and Finish Codes
Field Selected Functionality
Scene selection
buttons activate:
Scenes 1 to 4
Scenes 5 to 8
Scenes 9 to 12
Scenes 13 to 16
DIP Switch Settings
5 6
1
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
ntgrxwstns-9 12.12.03
Wallstations
Architectural Style
®
2 3/4"
(70mm)
5/16"
(8mm)
1 3/8"
(35mm)
4 9/16"
(116mm)
1234567
4
3
2
1
Color and Finish Codes
Matte Finishes
Standard – Ship in 48 hours
White WH
Ivory IV
Beige BE
Gray GR
Brown BR
Black BL
Metal Finishes
Ship in 4 to 6 weeks
Bright Brass BB
Bright Chrome BC
Bright Nickel BN
Satin Brass SB
Satin Chrome SC
Satin Nickel SN
Antique Brass QB
Antique Bronze QZ
Anodized Aluminum Finishes
Ship in 4 to 6 weeks
Clear CLA
Black BLA
Brass BRA
Engraving E
No Insert NI
Also available:
-Custom Controls
-Color Matching
Ship in 4 to 6 weeks. Pricing
may vary depending on finishes.
Dimensions
Front View
Mounting
Power
Low-voltage type Class 2 (PELV).
Operating voltage: 12/24 V Direct Current.
Key Design Features
• Meets IEC 801-2. Tested to withstand 15kV
electro-static discharge without damage or
memory loss.
• Faceplate snaps on with no visible means of
attachment.
• Can be ganged to share a common faceplate
with NovaT*
® and Vareo® Dimmers. Counts as
a “small control” for ganging.
System Communications and Capacity
• Low-voltage type Class 2 (PELV) wiring
connects Wallstations to Control Units
and other components.
• Up to 8 Control Units and up to 16 total
Wallstations and/or Control Interfaces may
be linked for a total of 24 control points.
Terminals
Accept up to two #18 AWG (1.0mm
2
) typical.
Environment
32-104°F (0-40°C). Relative humidity less
than 90% non-condensing.
Side View
Back View
DIP Switches
1-4 used to set
address
5-7 used to
select function
Terminals for
Class 2
(PELV) wiring
Class 2 (PELV)
wiring
1-Gang U.S.
Wallbox
Faceplate
Specifications
2
DIP Switch Settings
Address
1234
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Reserved for GRX-PRG, if present on link.
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
ntgrxwstns-10 12.12.03
Wallstations
Architectural Style
®
DIP Switches
• Set DIP switches 1-4 to give the
Wallstation a unique system address
from 1 to 16.
• Set additional DIP switches (if any) to
specify function as shown on the first
page of the Wallstation’s Specification
Submittal.
123456
4
3
2
1
Wallstation Rear View
D: Drain/Shield
(2) #12 AWG
(2.5mm
2
)
(1) #18 AWG
(1.0mm
2
)
(2) #12 AWG
(2.5mm
2
)
Class 2/PELV
Control Wiring
1: Common
2: 24VFW
Wallstation Installation
Low-Voltage Class 2 (PELV) Wiring
• Use low-voltage Class 2 (PELV) wiring to daisy-chain
Wallstations to Control Units and other components.
• Make connections inside the wallbox or in a switch/junction
box with a maximum wire length of 8 feet (2.5m) from the link
to the Wallstation.
Note: EGRX Wallstations have a “D” terminal for Drain.
Connect the Drain/Shield at this terminal.
When used with GRAFIK Eye 3000 Control Units:
• Two #18 AWG (1.0mm
2
) conductors for common (terminal 1)
and 12 V Direct Current (terminal 2). Ensure that the terminal 2
connection is wired correctly. Refer to GRX-3000 Specification
Submittal.
• One shielded, twisted pair #18 AWG (1.0mm
2
) for data link
(terminals 3 and 4).
When used with GRAFIK Eye 4000 Control Units:
• Two #12 AWG (2.5mm
2
) conductors for common (terminal 1)
and 24 V Direct Current (terminal 2). These won’t fit in
terminals. Connect as shown.
• One shielded, twisted pair #18 AWG (1.0mm
2
) for data link
(terminals 3 and 4).
• Connect Drain/Shield as shown. Do not connect to Ground
(Earth) or Wallstation. Connect the bare drain wires and cut off
the outside shield.
Data Link
(1) Shielded, twisted
pair #18 AWG (1.0mm
2
)
3: MUX
4: MUX
3