SPECIFICATION SUBMITTAL
ntgrx1s-1 08.20.04
Wallstations
NTGRX-1S
®
Description
• Ideal for large projects that use the maximum
number of Wallstations and/or Control Interfaces
but still require additional control points.
• Provides line-voltage three-way control for retrofit
applications.
Features
• Wires to GRAFIK Eye 3000 Series Control Units
using 120 VAC line voltage wiring.
• Wires to GRAFIK Eye 4000 Series Control Units
using Class 2 (PELV) wiring.
• Does not require an address.
• Toggles the connected GRAFIK Eye Control Unit
between Scene 1 and Off.
• Operates one GRAFIK Eye 3000 or 4000 Series
Control Unit.
• Up to ten NTGRX-1S Entrance Controls may be
wired in parallel to a single Control Unit.
• Not for use with 2-zone Control Units.
NTGRX-1S-__-_
Entrance Control
Color and Finish Codes
1
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
ntgrx1s-2 08.20.04
Wallstations
NTGRX-1S
®
Color and Finish Codes
Matte Finishes
Standard – Ship in 48 hours
White WH
Ivory IV
Beige BE
Gray GR
Brown BR
Black BL
Metal Finishes
Ship in 4 to 6 weeks
Bright Brass BB
Bright Chrome BC
Bright Nickel BN
Satin Brass SB
Satin Chrome SC
Satin Nickel SN
Antique Brass QB
Antique Bronze QZ
Anodized Aluminum Finishes
Ship in 4 to 6 weeks
Clear CLA
Black BLA
Brass BRA
Engraving E
Also available:
-Custom Controls
-Color Matching
Ship in 4 to 6 weeks. Pricing
may vary depending on finishes.
Power
Operating voltage: 12 to 40 VDC
and 100 to 127 VAC.
Key Design Features
• Meets IEC 801-2. Tested to withstand 15kV
electro-static discharge without damage or
memory loss.
• Faceplate snaps on with no visible means of
attachment.
• Can be ganged to share a common faceplate
with NovaT*
® and Vareo® Dimmers. Counts as
a “small control” for ganging.
System Communications and Capacity
• Does not require an address.
• Does not count toward the maximum number
of Wallstations/Control Interfaces on a Class 2
(PELV) link.
• Wires directly to and communicates directly
with the GRAFIK Eye 3000 or 4000 Series
Control Unit.
• Up to ten NTGRX-1S Entrance Controls may
be wired in parallel to the Control Unit.
Wires
Two #18 AWG (1.0mm
2
) wires.
Environment
32-104°F (0-40°C). Relative humidity less
than 90% non-condensing.
Specifications
2 3/4”
(70mm)
2 3/4”
(70mm)
1 3/8”
(35mm)
1/4”
(7.5mm)
4 9/16”
(116mm)
Dimensions
Front View
Side View
Faceplate
1-Gang
U.S. Wallbox
Mounting
2
R
Job Name:
Job Number:
Model Numbers:
Page
SPECIFICATION SUBMITTAL
ntgrx1s-3 08.20.04
Wallstations
NTGRX-1S
®
Zone 1
Zone 3
Neutral
Zone 2
Zone 4
CU Wire Only
Hot/Live
CLASS 2
SSA
1234
USA Class 2
IEC PELV
Zone 6 Zone 5
SSA
SSA RTN
DO NOT USE
2 IN, OUT
1 IN, OUT
DO NOT USE
MUX (4) IN
MUX (3) IN
MUX (4) OUT
MUX (3) OUT
USA: CLASS 2
IEC: PELV
Black
Blue
GRX-4103 Control Unit
NTGRX-1S
(10 maximum)
When used with GRAFIK Eye 4000 Series Control Units
Wiring
When used with GRAFIK Eye 3000 Series Control Units
Note: Each line-voltage terminal accepts up to two
#12 AWG (2.5mm
2
) copper wires.
Note: Each terminal accepts up to two #12 AWG (2.5mm
2
) copper wires.
NTGRX-1S connects to 3000 Series Control Units using 120 VAC.
Connect to the appropriate line-voltage terminals.
Connecting 120 VAC to the low-voltage Class 2 (PELV) terminals may
cause damage to lighting controls or injury.
Distribution Panel
Hot/Live
Neutral
2 #12 AWG
(2.5mm
2
)
Neutral
NTGRX-1S
(10 maximum)
Black
Blue
Hot/Live
Rear View of GRX-3106
Earth/Ground from Distribution Panel
All connections to 4000 Series Control Units are Class 2 (PELV).
Connecting 120 VAC to any terminals on 4000 Series Control Units
may cause damage to lighting controls or injury.
3