LV16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoomTM / HomeWorks® QS Lighting Control Panels
369868b 1 04.27.16
Low-Voltage Enclosure
Low-voltage enclosures are surface-mounted in an
electrical closet or equipment space. The number of
enclosures and the types of components within them are
customized to fit the size, lighting plan, and design of a
space. Low-voltage enclosures can be distributed
throughout a space near the rooms they are controlling, to
provide maximum flexibility during installation of the
low-voltage wiring.
The LV16 low-voltage enclosure provides a compact
housing for mounting a maximum of two Guestroom
Control Units or system interfaces in any combination. In
addition, it can house up to four wire landing boards and
two power supplies.
The enclosure accepts one 120V~ (LV16-120) or one
220-240V~ (LV16-230) feed to power the panel, which
is contained in an enclosed area, allowing access to only
the low-voltage connections when the enclosure cover is
removed.
Models Available
LV16-120 120 V~ Low-Voltage Enclosure
LV16-230 220-240 V~ Low-Voltage Enclosure
LV16 Low-Voltage Enclosure
1
LV16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoomTM / HomeWorks® QS Lighting Control Panels
369868b 2 04.27.16
Specifications
Regulatory Approvals
LV16-120 model only
Complies with UL
® 508
Complies with CSA C22.2, #14
Complies with NOM 003
• RoHS Compliant
LV16-230 model only
Complies with IEC/EN 50178
• RoHS Compliant
Power
• 120V~ 50/60Hz 2 A (LV16-120)
• 220 –240V~ 50/60Hz 2 A (LV16-230)
Environment
• Ambient temperature: 0 ºCto 40ºC (32°F to 104°F).
• Relative humidity: 0%– 90%, non-condensing.
• Indoor use only.
• Passive cooling.
• IP20 Construction.
Mounting
• Surface-mount only.
• Enclosure fully populated with components generates
heat, maximum 110 BTUs/hr.
• Meets NEC
® requirements for installation in “other
space used for environmental air”.
Construction
• 1.5 mm (16-gauge) powder coated sheet metal
enclosure.
• 1.5 mm (16-gauge) powder-coated metal cover
with ventilation holes. Cover is attached using four
Phillips-head screws.
Line Voltage Connections
• Use copper wire only.
• Supply conductors rated at 75°C (167 °F) or higher.
• Use supplied wire harnesses to connect to
corresponding Lutron
® power supply harness.
Capacity
• Enclosure can accommodate two Guestroom
Control Units (GCU-HOSP) or system interface
devices (QSE-IO, QSE-CI-DMX, or QSE-CI-NWK-E),
four wire landing boards (QS-WLB), and 2 power
supplies (QSPS-DH-1-75-H).
2
LV16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoomTM / HomeWorks® QS Lighting Control Panels
369868b 3 04.27.16
Panel Mounting
• Install in accordance with all local and national
electrical codes.
• Indoor use only.
• Consult dimensions page for panel size, conduit
knockouts, and mounting hole locations.
• Panels weigh up to 14 kg (30 lb) with all components
installed. Reinforce wall structure for weight and local
codes.
• Mount panel where audible noise is acceptable (power
supply hums slightly).
• This equipment is passively air-cooled. Mount in a
location where the vented cover will not be blocked.
305mm (12in) of clearance in front of the vents is
required. A reduced clearance of 46 mm (1.8 in) in
front of the cover can be achieved. See Wall Cavity
Mounting section for more details.
• Mount panel so line voltage wiring is at least 1.8m
(6ft) from sound or electronic equipment and wiring.
• Surface-mount only.
• Use keyholes with bolts sufficient for 14 kg (30 lb)
load, M6 (1/4 in) bolts rec om mend ed.
• Mount within 7º of true vertical.
Suspended Ceiling Installation
Panel(s) can be a minimum of 1 in (25 mm) from the
top of the suspended ceiling and ceiling.
Panels cannot be vertically stacked when installed
above a suspended ceiling.
Maintain 12 in (304 mm) of clearance in front of panel
when mounting in a suspended ceiling.
1 in
(25 mm)
Minimum
1 in
(25 mm)
Minimum
Suspended Ceiling
NOTE: Installation must comply with all working space
requirements. Consult with your jurisdiction for local
requirements.
Ceiling
3
LV16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoomTM / HomeWorks® QS Lighting Control Panels
369868b 4 04.27.16
Wall Cavity Mounting requires a minimum of
8.125 cubic feet (0.23 cubic meter) of confined space.
This confined space requires a minimum of 27 square
inches (442 square millimeters) of venting (area of vent
openings/aperture) for each of the intake and exhaust
vents.
Intake vent must be located below the bottom panel
while the exhaust vent must be located above the top
panel.
The confined space must have a Removable
Access Panel large enough to service the
equipment.
Panels should only be surface-mounted.
Panels should be mounted a minimum of 6 in
(153 mm) from the floor and 6 in (153 mm) from
the ceiling to ensure proper ventilation.
Do not stack multiple LV16 panels if mounting in a
wall cavity.
Exhaust Vent
27 square inches
(442 square
millimeters) minimum
of venting
Removable
Access Panel
(by others)
PD4-16-F Dimming/
Switching Panel shown
surface mounted behind a
removable access panel.
Wiring Conduit
Structural Wall
Intake Vent
27 square inches
(442 square
millimeters) minimum
of venting
Wiring Conduit
LV16-120
Low-Voltage
Enclosure
Wall Cavity Mounting
In addition to the Panel Mounting requirements found in this document, the following is required when
mounting panels into a wall cavity.
NOTE: Installation must comply with all working space
requirements. Consult with your jurisdiction for local
requirements.
4
LV16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoomTM / HomeWorks® QS Lighting Control Panels
369868b 5 04.27.16
Wall Cavity Mounting (continued)
30in (762 mm)
78in
(1981 mm)
6in
(153 mm)
2.9in
(74 mm)
1.8in
(46 mm)
Exhaust
Vent
Front View Cross-section view of
access-wall installation
6in
(153 mm)
Minimum
*9 in (228 mm)
shown
PD4-16-F Dimming/Switching
Panels shown surface mounted
behind a removable access
panel.
LV16-120
Low-Voltage
Enclosure
Minimum clearance
from panel cover to
access panel wall
Minimum clearance
from panel cover to
access panel wall
Intake
Vent
6in
(153 mm)
Minimum
6in
(153 mm)
Minimum
6in
(153 mm)
Minimum
*9 in (228 mm)
shown
NOTE: Installation must comply with all working space requirements. Consult with your jurisdiction for local requirements.
5
LV16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoomTM / HomeWorks® QS Lighting Control Panels
369868b 6 04.27.16
Louvered upper (exhaust) vent must be
installed as shown with vent openings
facing upwards.
Louvered lower (intake) vent must be
installed as shown with vent openings
facing downwards.
Note the direction of
louvered vent openings.
Wall Cavity Mounting (continued)
Vent orientation: Proper venting is required to cool equipment correctly when installed behind a removable
access panel. If louvered vents are used, they must be installed as shown below to allow required air flow and
cooling. A minimum of 27 square inches (442 square millimeters) of venting (area of vent openings/aperture)
required for each of the intake and exhaust vents.
6
LV16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoomTM / HomeWorks® QS Lighting Control Panels
369868b 7 04.27.16
Mounting Dimensions
All dimensions shown as: mm (in)
-7°
+7°
Line voltage
wire entry
(non-IEC
PELV/NEC
®
Class 2)
Input
Power
Switch
Power Supply
DIN Rail End
Stop (5x)
Terminal
Shield
Surface
Mounting
Pedestal (4x)
406
(16.0)
381
(15.0)
326
(12.8)
427
(16.8)
455
(18.0)
108
(4.2)
Ø 7.9
(0.31)
10.9
(0.43)
Ø 15.8
(0.63)
IEC PELV/NEC® Class 2 only
Top View
Left Side View Right Side View
Bottom View
292
(11.5)
7
LV16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoomTM / HomeWorks® QS Lighting Control Panels
369868b 8 04.27.16
Typical Configuration Example
L(+) N(-)
QSPS-DH-1-60
120 - 240 V
Input / Entrada / Entrée
24 V
Output / Salida / Sortie
22.5 - 25 V
Assembled in U.S.A.
GCU-HOSP
Guestroom Control Unit
+ 44.(0)20.7680.4481
+ 1.800.523.9466
lutron.com
243C IND. CONT. EQ.
IEC PELV/ NEC Class 2
®
50015757 Rev. A
Power Supply
QSPS-DH-1-75-H
1
(up to 2, not included)
Guestroom Control Unit
GCU-HOSP
1,2
OR
System Interfaces
1,2
QS Wire Landing Board
QS-WLB
1
(up to 4, not included)
1
All components sold separately.
2
Maximum of 2 Control Units / Interfaces allowed per enclosure.
8