SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoomTM / HomeWorks® QS Lighting Control Panels
369868b 3 04.27.16
Panel Mounting
• Install in accordance with all local and national
electrical codes.
• Indoor use only.
• Consult dimensions page for panel size, conduit
knockouts, and mounting hole locations.
• Panels weigh up to 14 kg (30 lb) with all components
installed. Reinforce wall structure for weight and local
codes.
• Mount panel where audible noise is acceptable (power
supply hums slightly).
• This equipment is passively air-cooled. Mount in a
location where the vented cover will not be blocked.
305mm (12in) of clearance in front of the vents is
required. A reduced clearance of 46 mm (1.8 in) in
front of the cover can be achieved. See Wall Cavity
Mounting section for more details.
• Mount panel so line voltage wiring is at least 1.8m
(6ft) from sound or electronic equipment and wiring.
• Surface-mount only.
• Use keyholes with bolts sufficient for 14 kg (30 lb)
load, M6 (1/4 in) bolts rec om mend ed.
• Mount within 7º of true vertical.
Suspended Ceiling Installation
• Panel(s) can be a minimum of 1 in (25 mm) from the
top of the suspended ceiling and ceiling.
• Panels cannot be vertically stacked when installed
above a suspended ceiling.
• Maintain 12 in (304 mm) of clearance in front of panel
when mounting in a suspended ceiling.
1 in
(25 mm)
Minimum
1 in
(25 mm)
Minimum
Suspended Ceiling
NOTE: Installation must comply with all working space
requirements. Consult with your jurisdiction for local
requirements.
Ceiling