SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom
369861p 1 01.06.20
Lutron Room Thermostat
The myRoom Palladiom QS thermostat is a user
interface to an HVAC equipment controller. The large
backlit LCD display is easy to see and use, while a
built-in Passive Infrared (PIR) sensor detects
occupants moving within an area and works with
other system components to determine when the
space is occupied.
Model Number
MWP-T-OHW-XXX *-A myRoom Palladiom QS
thermostat
Features
• Aesthetically coordinates with Palladiom keypads.
Compatible with the following HVAC system
interfaces:
Lutron Fan Coil Unit (FCU) controller
(see spec 3691082 at www.lutron.com)
e
2-pipe or 4-pipe hydronic systems
e
3-speed or 010 V- variable fan speed control
e
On / Off or 010 V- modulating valve control
Specific VRV / VRF systems via BACnet®
(see page 4)
Specific VRV / VRF systems via wired third-party
HVAC controller interface (see page 6)
Backlit screen and buttons are easy to operate in a
dark room. The backlit screen and the buttons will
dim to a pre-selected level when not in use.
Ability to lock out local button control via myRoom
Plus system configuration. **
Built-in vandal-resistant PIR motion sensor with
Lutron exclusive XCT detection technology.
• Built-in room temperature sensor.
Programmable active backlight timeout.
myRoom Palladiom QS Thermostat
* “XXX” in the model number will be 2 or 3 letters that represent color / finish code.
See Colors and Finishes.
** Available with myRoom Palladiom thermostat version 3.11 or newer.
The FCU controller supports an optional wired
remote temperature sensor to allow for flexibility
regarding thermostat installation location. When
installed, the wired remote temperature sensor is
used instead of the internal thermostat sensor.
IEC SELV/NECR Class 2 control.
myRoom Plus and myRoom Prime guestroom
control solutions save energy by automatically
adjusting the room temperature setpoint based on
guest occupancy.
myRoom Plus can save energy based on room
sold / unsold information from the hotel property
management system.
In myRoom Plus, BACnet® interface supports
up to six myRoom Palladiom thermostats per
area / zone.
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom
369861p 2 01.06.20
Lutron Room Thermostat
Specifications
Regulatory Approvals
Lutron Quality Systems registered to ISO 9001:2015
Compliant with IEC 60730
cULus Listed
NOM Certified
RoHS Certified
Power Input
IEC SELV/NEC® Class 2
Operating voltage: 24 36 V- 60 mA
System Communication and Capacity
IEC SELV / NEC® Class 2 wiring connects Palladiom QS
thermostats to other devices on the QSLink.
• A Palladiom QS thermostat consumes 3power draw
units (PDU) on the QS link. For complete information,
see “Power Draw Units on the QS Link” (P/N 369405) at
www.lutron.com
Terminals
Each terminal accepts up to two 18 AWG (1.0mm
2
)
wires or one 22 AWG to 12 AWG (0.5 mm
2
to 2.5mm
2
)
solid or stranded wires.
Environment
Ambient operating temperature:
32 ˚F to 104 ˚F (0 ˚C to 40 ˚C)
Maximum 90% non-condensing relative humidity
Indoor use only
IP20 Rating
Compatibility
Palladiom QS thermostats are compatible with myRoom
Plus and myRoom Prime systems.
Room Temperature Sensor
Measuring range: 32 °F to 99 ˚F (0 ˚C to 37 ˚C)
• Accuracy
– At 70 °F: < +/− 1 °F
– At 25 °C: < +/− 0.5 °C
5% to 90% non-condensing, relative humidity
Temperature Setpoint and Display
• The Palladiom QS thermostat is adjustable in 1 °F
(0.5 °C) increments.
• The Palladiom QS thermostat displays room
temperature in 1 °F (0.5 °C) increments.
Toggle between Fahrenheit and Celsius temperature
units with a button press or Lutron Integration
Protocol command.
Continued on the next page...
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom
369861p 3 01.06.20
Lutron Room Thermostat
Specifications (continued)
Wallbox
Requires a 2.75in x 2.75in (70mm x 70mm)
metal conduit box with a minimum depth of 1.38in
(35mm).
Single wallbox: Lutron model number EBB-1-SQ
Pack of 15 wallboxes: Lutron model number
EBB-15-SQ
If the wallbox has top or bottom mounting tabs,
bend them back before installing the adapter.
If running conduit to the wallbox, use a low-profile
conduit connector with a maximum height of
0.125 in (3 mm).
Mounting
Mount on a clean, dry, interior wall.
Mount approximately 4 ft to 5 ft (1.2 m to 1.5 m)
above the floor. Follow all local and national codes.
Mount on a wall without pipes, chimneys, or ducts.
Mount on a wall with good visibility and control
access.
Do not mount on an exterior wall, close to a
window, next to a door, or areas with drafts.
Do not mount in direct airflow from supply and
return registers / grilles.
Do not expose to water (e.g., drips or splashes) or
mount in a damp area.
Do not mount within 4 ft (1.2 m) of heating sources
(e.g., direct sunlight, light bulbs, etc.).
Do not mount in areas with poor circulation (e.g.,
niches, alcoves, behind curtains, or behind doors).
Do not mount within 0.75 in (19 mm) of Palladiom
keypads, receptacles, or accessories.
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom
369861p 4 01.06.20
Lutron Room Thermostat
HVAC via BACnet® System Diagram
The myRoom Palladiom thermostat is able to interface with HVAC systems via BACnet® in a myRoom Plus system.*
There are several requirements for interfacing to a HVAC system via BACnet® that must be met in order to achieve
optimal performance. Lutron strongly recommends reviewing these requirements with the HVAC manufacturer,
the HVAC contractor, the BACnet® integrator, the mechanical, electrical, plumbing (MEP) engineer, and the Lutron
project manager and / or field service.
* Available with myRoom Palladiom thermostat version 3.11 or newer.
1. HVAC system performance (e.g., delays, changeover
temperature differential) is dictated by the HVAC
system. The Palladiom QS thermostat provides
operating mode, fan mode, and setpoint to
the system.
2. The current zone temperature must be provided
via BACnet® by the HVAC system to the Lutron
system in order to have it displayed on the Palladiom
QS thermostat and in myRoom Vue software. The
local Palladiom temperature sensor is disabled. If
the thermostat does not receive a temperature via
BACnet® within 5 minutes of being powered, an E4
error will be displayed.
3. Call status (actively heating / cooling) must be provided
via BACnet® by the HVAC system in order for:
a. The Palladiom thermostat to indicate the status on
the display.
b. myRoom Vue to be able to provide HVAC status,
HVAC energy reporting, and HVAC data logging.
4. Fan status must be provided via BACnet® by the
HVAC system in order for myRoom Vue to provide
HVAC energy reporting and HVAC data logging.
5. The Palladiom QS thermostat supports
1 °F / 0.5 °C resolution temperature changes
independent of the resolution supported by the
HVAC equipment connected via BACnet®.
243C IND. CONT. EQ.
GCU-HOSP
myRoom
IEC PELV
/
SELV
/
NECR Class 2
www.lutron.com/qs
+ 44.(0)20.7680.4481
+ 1.800.523.9466
lutron.com
PWR
2 1
COM
P
5 4
3
L2
L1
2.0 A
/
L1, L2
24
36 V-
250 mA
QS L1
1
2 3 4
5
COM
V+
MUX
D
MUX
QS L2
1
2 3 4
5
COM
V+
MUX
D
MUX
L2 TX
/
RX
L1 TX
/
RX
PWR
ERR
L1
L2
L1
L1
FD/Col
Con/Act
RJ45
FD/Col
Con/Act
RJ45
24
36 V-
Manufacturer
Specific BACnet®
Interface by others
HVAC
Systems
Other QS
devices
Ethernet
Ethernet
Ethernet
Lutron QS Link
BACnet®
Ethernet
VRF
Link
Power
Lutron Palladiom
Thermostat
Network Switch
by others
Building
Network
Lutron myRoom
Processor
BACnet® Client by others
Continued on the next page...
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom
369861p 5 01.06.20
Lutron Room Thermostat
HVAC via BACnet® System Diagram (continued)
6. The myRoom system supports OFF and AUTO
operating modes. Other operating modes are NOT
supported (e.g.,heat, cool).
7. The myRoom system supports either a single
setpoint with positive and negative drifts or a heat
and cool set-point. When drifts equal 0, single set-
point, heat set-point, and cool set-point will be the
same. If the HVAC system does not accept identical
heat and cool set-points then drifts must be set in
the myRoom system such that the heat and cool
set-points are spaced greater than the minimum
required by the HVAC system.
8. The myRoom system supports LOW, MEDIUM,
HIGH, and AUTO fan modes.
9. When the operating mode is OFF, the fan mode will
always be OFF. When the operating mode is AUTO,
the fan mode can never be OFF.
10. The temperature scale (°C / °F) displayed on the
Palladiom QS thermostat can be changed locally at
the thermostat. It cannot be changed via BACnet®.
11. If the BACnet® system loses communication with the
Palladiom QS thermostat, the HVAC system must
have its own method to maintain temperature.
12. myRoom Vue will not show the HVAC system alerts
and alarms when the HVAC system is connected via
BACnet®.
For a complete list of available BACnet® objects, see BACnet® PIC Statement for myRoom Virtual Devices
(P/N3691087) at www.lutron.com
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom
369861p 6 01.06.20
Lutron Room Thermostat
VRV / VRF via wired third-party HVAC controller System Diagram
243C IND. CONT. EQ.
GCU-HOSP
myRoom
IEC PELV
/
SELV
/
NECR Class 2
www.lutron.com/qs
+ 44.(0)20.7680.4481
+ 1.800.523.9466
lutron.com
PWR
2 1
COM
P
5 4
3
L2
L1
2.0 A
/
L1, L2
24
36 V-
250 mA
QS L1
1
2 3 4
5
COM
V+
MUX
D
MUX
QS L2
1
2 3 4
5
COM
V+
MUX
D
MUX
L2 TX
/
RX
L1 TX
/
RX
PWR
ERR
L1
L2
L1
L1
FD/Col
Con/Act
RJ45
FD/Col
Con/Act
RJ45
24
36 V-
Processor
GCU-HOSP
Third-party HVAC
controller
Compatible
VRV / VRF System
QS Link
Palladiom QS
Thermostat
HVAC Controller
Communication Link
Manufacturer Specific
Communication Link
To Other QS Devices
myRoom Plus:
Processor (GCU-HOSP) installed permanently.
myRoom Prime:
Processor (GCU-HOSP) connected temporarily for programming only.
See the “myRoom Prime Programming Kit” spec submittal
(P/N 369961) at www.lutron.com for more information.
Notes:
1. Indoor unit must support auto, heat, cool, and fan mode.
2. The Palladiom thermostat will not display the HVAC system error codes or call for heat or cool. Energy monitoring in myRoom Vue is not available
while interfacing with third-party controllers.
3. The Palladiom thermostat will overwrite changes made from outside the Lutron system so that the HVAC system continues to operate based on the
Palladiom thermostat’s programmed information.
4. The VRV / VRF manufacturer’s thermostat must be removed from “Manufacturer Specific Communication Link”. Leaving it connected can cause
issues in communication between wired HVAC controller and VRV / VRF systems.
5. The LG-PDRYCB500 and Procon A1M controllers are not sold by Lutron. Contact VRV / VRF system manufacturer for ordering and
confirming compatibility.
6. CoolPlug is sold by CoolAutomation. Contact CoolAutomation for ordering and confirming compatibility.
7. All third-party controllers are designed for one-to-one controls. Multiple VRV / VRF systems must not be connected to a single third-party controller.
Multiple third-party controllers must not be connected to a single myRoom Palladiom thermostat.
8. Inbuilt temperature sensor or humidity sensor of the myRoom Palladiom thermostat is not available when interfacing with third-party controllers.
9. If VRV / VRF system supports only cooling or only heating, verify the available op-modes are correctly configured in Q-Design. This cannot be
programmed to change automatically based on sensors.
Controller
VRV / VRF Equipment
Application Note
Lutron P/N
LG-PDRYCB500 LG VRF system 048627
CoolPlug Daikin or compatible systems 048650
Procon A1M Mitsubishi VRF system 048585
Firmware requirements:
myRoom Palladiom thermostat: V4.16 or later
6
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom
369861p 7 01.06.20
Lutron Room Thermostat
Fan Coil Unit System Diagram
243C IND. CONT. EQ.
GCU-HOSP
myRoom
IEC PELV
/
SELV
/
NECR Class 2
www.lutron.com/qs
+ 44.(0)20.7680.4481
+ 1.800.523.9466
lutron.com
PWR
2 1
COM
P
5 4
3
L2
L1
2.0 A
/
L1, L2
24
36 V-
250 mA
QS L1
1
2 3 4
5
COM
V+
MUX
D
MUX
QS L2
1
2 3 4
5
COM
V+
MUX
D
MUX
L2 TX
/
RX
L1 TX
/
RX
PWR
ERR
L1
L2
L1
L1
FD/Col
Con/Act
RJ45
FD/Col
Con/Act
RJ45
24
36 V-
Processor
GCU-HOSP
FCU Controller
(e.g., SMC53-MYRM)
Fan CoilUnit
QS Link
Palladiom QS
Thermostat
HVAC Controller
Communication Link
Water Valve and Fan
Control Signals
To Other QS Devices
myRoom Plus:
Processor (GCU-HOSP) installed permanently.
myRoom Prime:
Processor (GCU-HOSP) connected temporarily for programming only. See the
“myRoom Prime Programming Kit” spec submittal (P/N 369961) at
www.lutron.com for more information.
7
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom
369861p 8 01.06.20
Lutron Room Thermostat
Dimensions
Measurements shown as: in (mm)
Front View
Rear View
Side View Wallbox (EBB-1-SQ)
3.7
(94)
4.0
(102)
2.75
(70)
Minimum
1.38
(35)
2.36
(60)
Maximum
0.125
(3)
Low-profile
chase nipple
Wallbox
1.0
(25)
0.625
(16)
2.5
(64)
0.4
(10)
2.5
(64)
2.5
(64)
8
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom
369861p 9 01.06.20
Lutron Room Thermostat
PIR Sensor Placement and Operation
The ability of the PIR sensor to detect motion requires line-of-sight of room occupants. The PIR sensor must have
an unobstructed view of the room.
Hot objects, moving air currents, and automated shades can affect the performance of the PIR sensor. For best
performance, the PIR sensor should be mounted at least 4 ft (1.2 m) away from HVAC vents and light bulbs.
The performance of the PIR sensor depends on a temperature differential between the ambient room temperature
and that of room occupants. Warmer rooms may reduce the ability of the PIR sensor to detect occupants.
For use as part of the guest presence detection feature to control lights and thermostat based on the occupancy
state. PIR sensor is not intended to control lights, thermostat, or shades without using the myRoom Guest Controls
solution.
PIR sensor is not intended to control lights, thermostat, or shades without using guest presence detection.
180˚ sensor field-of-view
Sensitivity options:
– High sensitivity (default)
– Low sensitivity
• Coverage
– 30 ft x 30 ft (9 m x 9 m)
900 ft
2
(81 m²)
Vandal resistant with reinforced metal bar behind lens
9
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom
369861p 10 01.06.20
Lutron Room Thermostat
PIR Sensor Placement and Operation Diagrams
Horizontal Beam Diagram
(for reference only)
5 ft
(1.5 m)
5 ft
(1.5 m)
0
10 ft
(3 m)
10 ft
(3 m)
15 ft
(4.5 m)
15 ft
(4.5 m)
20 ft
(6.1 m)
20 ft
(6.1 m)
25 ft
(7.5 m)
25 ft
(7.5 m)
30 ft
(9 m)
30 ft
(9 m)
Vertical Beam Diagram
(for reference only)
5 ft
(1.5 m)
0
10 ft
(3 m)
10 ft
(3 m)
15 ft
(4.5 m)
15 ft
(4.5 m)
20 ft
(6.1 m)
20 ft
(6.1 m)
25 ft
(7.5 m)
25 ft
(7.5 m)
30 ft
(9 m)
30 ft
(9 m)
35 ft
(10.7 m)
5 ft
(1.5 m)
0
Occupancy Sensor Coverage
5 ft
(1.5 m)
5 ft
(1.5 m)
0
10 ft
(3 m)
10 ft
(3 m)
15 ft
(4.5 m)
20 ft
(6.1 m)
20 ft
(6.1 m)
15 ft
(4.5 m)
5 ft
(1.5 m)
35 ft
(10.7 m)
10
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom
369861p 11 01.06.20
Lutron Room Thermostat
Use IEC SELV / NEC® Class 2 (24 36 V-) wiring to
connect the thermostat to the QS link for power and
communication.
Connect two 22 AWG (0.5 mm
2
) shielded, twisted
pair wires to terminals 3 and 4. Shielding (drain) of
the twisted pair wires must be connected together
as shown, but do not connect the shielding to
earth / ground or the thermostat and do not allow it to
contact the grounded wallbox.
Connect the appropriate size wires to terminals 1
and 2 for power, according to your link length (see
table below).
Connect Drain / Shield as shown. Do not connect to
Ground (Earth) or the thermostat. Connect the bare
drain wires and cut off the outside shield.
Note: Use appropriate wire connecting devices as
specified by local codes.
QS Link Wire Sizes (check compatibility in your area)
QS Link Wiring Length Wire Gauge Lutron Cable Part Number
Less than 500 ft (153 m)
Power (terminals 1 and 2)
1 pair 18 AWG (1.0 mm
2
)
GRX-CBL-346S (non-plenum)
GRX-PCBL-346S (plenum)
Data (terminals 3 and 4)
1 twisted, shielded pair 22 AWG (0.5 mm
2
)
500 ft to 2000 ft
(153 m to 610 m)
Power (terminals 1 and 2)
1 pair 12 AWG (4.0 mm
2
)
GRX-CBL-46L (non-plenum)
GRX-PCBL-46L (plenum)
Data (terminals 3 and 4)
1 twisted, shielded pair 22 AWG (0.5 mm
2
)
QS Link Wiring
Link Wiring less than 500 ft (153 m)
Link Wiring 500 ft to 2000 ft (153 m to 610 m)
4321
4321
Fan Coil Unit
Controller
Rear View
Drain /
Shield
Data link
One twisted,
shielded pair
22AWG
(0.5mm
2
)
3: MUX (Purple)
4: _ (White)
IEC SELV/NECR
Class 2
One or two
18 AWG
(1.0mm
2
)
1: Common
(Black)
2: V+ (Red)
4321
4321
Drain /
shield
One or two
12AWG (2.5 mm
2
)
Data link
One twisted,
shielded pair
22AWG
(0.5mm
2
)
3: MUX (Purple)
4: _ (White)
IEC SELV/
NEC® Class 2
One 18 AWG
(1.0 mm
2
)
1: Common
(Black)
2: V+ (Red)
11
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom
369861p 12 01.06.20
Lutron Room Thermostat
Fan Coil Unit Controller Wiring
User Interface
Auto
Set
OFF
Heating On
Cooling On
Toggle System On / Off
Toggle °F / °C
Display Backlighting
1
Display °F / °C Indicator
Room Temperature
3
(Default) or Room
Setpoint
4
PIR Occupancy Sensor
Lower Room Setpoint
Raise Room Setpoint
System Off
2
Fan Mode
Auto
Low
Medium
High
Auto
Auto
Auto
Auto
Change Fan Mode
1
Turns on when any button is pressed. Turns off after 10 seconds of inactivity.
2
Room temperature and “OFF” are shown when system is off.
3
Display shows the current room temperature. First Raise / Lower button press changes the display to show the room setpoint. Further Raise / Lower button presses adjust the room
setpoint.
4
Display always shows the room setpoint. The first Raise / Lower button press activates the LCD backlight. Additional Raise / Lower button presses adjust the room setpoint.
NOTE: Button backlighting adjustable through system software.
4321
See “Fan Coil Unit Controller” spec submittal (P/N 369962) at www.lutron.com for more information.
Common (G)
_ (–)
MUX (+)
Control Outputs
for HVAC
24 V~ Power (from HVAC system)
FCU Controller
(e.g., SMC53-MYRM)
Fan Coil Unit Controller Wiring Wire Gauge Lutron Cable Part Number
Up to 500 ft (152 m) Common: 18 AWG or 22 AWG
(1.0 mm
2
or 0.5 mm
2
)
MUX, _: 1 twisted, shielded pair
18 AWG or 22 AWG (1.0 mm
2
or 0.5 mm
2
)
GRX-CBL-346S
(non-plenum)
GRX-PCBL-346S (plenum)
12
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom
369861p 13 01.06.20
Lutron Room Thermostat
)Lutron, Lutron, myRoom, Palladiom, and XCT are trademarks or registered trademarks of Lutron Electronics Co., Inc., in the U.S. and other countries.
All other product names, logos, and brands are property of their respective owners.
Colors and Finishes
Due to printing limitations, colors and finishes shown cannot be
guaranteed to perfectly match actual product colors.
Color chip keychains are available for more precise color
matching:
– Architectural Matte Finishes: AM-CK-1
– Architectural Metal Finishes: AMTL-CK-1
Almond
AL
Beige
BE
Black
BL
Brown
BR
Gray
GR
Ivory
IV
Light Almond
LA
Sienna
SI
Taupe
TP
White
WH
Architectural Matte Finishes
Glass Finish
Architectural Metal Finishes
Bright Nickel
BN
Satin Chrome
SC
Satin Nickel
SN
Bright Brass
BB
Bright Chrome
BC
Polished Graphite
PG
Clear White Glass
CWH
Clear Black Glass
CBL
Satin Brass
SB
Thermostat
Thermostat
Thermostat
Antique Brass*
QB
* Antique Brass is a handcrafted finish that is created using a manual relief process. This artisanal process can result in variations in luster, hue
and appearance.
13