PD4-16-F
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom / HomeWorks Lighting Control Panels
369867f 1 01.14.20
DIN Panels and Accessories
The Lutron myRoom and HomeWorks families of DIN
rail panels are designed to accept DIN Power
Modules (DPMs). The DPMs can be configured in the
panel to control multiple load types to fit the size,
lighting plan and design of the space.
Features
Panels house up to four DIN Power Modules (DPMs)
or up to three DIN Power Modules (DPMs) and one
QSPS power supply.
Compatible DPMs
Digital Controllers
LQSE-2ECO-D
LQSE-2DAL-D
Dimming
MQSE-4A1-D
MQSE-3A1-D
MQSE-2A1-D
LQSE-4A1-D
LQSE-4T5-120-D
QSNE-4T10-D
LQSE-4T10-D
Switching
MQSE-4S1-D
MQSE-3S1-D
MQSE-2S1-D
LQSE-4S5-230-D
LQSE-4S8-120-D
QSNE-4S10-D
LQSE-4S10-D
Power Supplies and Motor Controllers
MQSPS-DH-1-30 (requires MQSPS-BRK)
QSPS-DH-1-75-H
LQSE-4M-D
Feed-through panel.
Panels extensively tested to ensure optimal thermal
performance with maximum load in 32 °F to 104 °F
(0 °C to 40 °C) ambient environment.
Panels are rated for 120–240 V~ ULR, CE and
non-CE applications.
Models Available
PD4-16-F 120–240 V~ Non-CE
Line / Mains Voltage Enclosure
PD4-16-F-CE 220–240 V~ CE
Line / Mains Voltage Enclosure
PD4-16-F Enclosure (without cover)
PD4-16-F Enclosure (with cover)
1
PD4-16-F
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom / HomeWorks Lighting Control Panels
369867f 2 01.14.20
Specifications
Regulatory Approvals
PD4-16-F model only
Complies with ULR 508
Complies with CSA C22.2, #14
Complies with NMX-J-515-ANCE-2008
PD4-16-F-CE model only
Complies with EN 50178
Power
120 –240V~ 50/60Hz
Environment
• Mount where ambient temperature is 32°F to
104°F (0 ºCto 40ºC). Relative humidity 0%–90%,
non-condensing.
• Indoor use only.
• Passive cooling.
• International Protection Marking: IP20
Mounting
• Surface-mount only.
• Enclosure with a maximum number of DPMs installed
generates heat, maximum 140 BTUs / hour.
• Meets NEC® requirements for installation in “other
space used for environmental air.
Construction
• 16-gauge (1.5 mm) powder-coated sheet metal
enclosure.
• 16-gauge (1.5 mm) powder-coated metal cover with
ventilation holes and hinged access door. Cover is
attached using four Phillips-head screws.
• Includes two DIN rails for mounting DPMs or power
supplies.
Line / Mains Voltage Connections
Wires land directly on DPMs or power supplies.
Modules in the panel can be wired using one power
feed or up to four power feeds. If feeding through
Lutron power modules using Line / Mains terminals,
the total load current must be less than or equal to
15 A. It is recommended that all feed splicing be
done outside of this enclosure.
Grounding Terminals
• 15 position aluminum ground bar (PD4-16-F)
• 23 position copper ground bar (PD4-16-F-CE)
Capacity
• Enclosure can accommodate 4 DPMs or power
supplies.
2
PD4-16-F
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom / HomeWorks Lighting Control Panels
369867f 3 01.14.20
Mounting for Panels
For indoor use only.
Surface-mount only.
Install in accordance with all local and national
electrical codes.
Equipment is passively air-cooled.
Panels weigh up to 30 lb (14 kg). Reinforce
wall structure for weight and local codes.
Use keyholes with bolts sufficient for 30 lb
(14 kg) load, 1/4 in (M6) bolts recommended.
Mount panel(s) within 7º of true vertical.
Leave 6 in (153 mm) clearance on each side of
panel.
Mount in a location where the cover will not
be blocked. 12 in (304 mm) of clearance is
recommended in front of the panel, however a
minimum of 3.03 in (77 mm) can be achieved:
see Wall Cavity Mounting guidelines for more
information.
Panel can be installed in a minimum of
8.125 cubic feet (0.23 cubic meter) of
confined space providing intake and exhaust
venting requirements are met. See Wall Cavity
Mounting section for details.
Mount panel so Line / Mains voltage wiring is
at least 6 ft (1.8 m) from sound or electronic
equipment and wiring.
Mount panel where audible noise is
acceptable (internal relays on modules click).
Panel(s) should be a minimum of 6 in
(153 mm) from the floor and ceiling.
Panel can be installed above a suspended
ceiling. See Suspended Ceiling Installation
section for details.
Consult Dimensions page for panel size,
conduit knockouts, and mounting hole
locations.
Panel Stacking
Do not mount more than two PD4-16-F panels
vertically.
A single LV16 panel may be installed under as many
as two PD4-16-F panels.
A minimum vertical spacing of 6 in (153 mm) is
required between each panel.
If stacking two PD4-16-F panels above an LV16
panel, PDUs should only be provided by the LV16
panel. No PDUs should be provided by any modules
located in the PD4-16-F panels.
Suspended Ceiling Installation
Panel(s) can be a minimum of 1 in (25 mm) from the
top of the suspended ceiling and ceiling.
Panels cannot be vertically stacked when installed
above a suspended ceiling.
Maintain 12 in (304 mm) of clearance in front of panel
when mounting in a suspended ceiling.
1 in
(25 mm)
Minimum
1 in
(25 mm)
Minimum
Suspended Ceiling
NOTE: Installation must comply with all working space
requirements. Consult with your jurisdiction for local
requirements.
Ceiling
3
PD4-16-F
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom / HomeWorks Lighting Control Panels
369867f 4 01.14.20
Wall Cavity Mounting requires a minimum of
8.125 cubic feet (0.23 cubic meter) of confined space.
This confined space requires a minimum of 27 square
inches (442 square millimeters) of venting (area of vent
openings / aperture) for each of the intake and exhaust
vents.
Intake vent must be located below the bottom panel
while the exhaust vent must be located above the top
panel.
The confined space must have a Removable
Access Panel large enough to service the
equipment.
Panels should only be surface-mounted.
Panels should be mounted a minimum of 6 in
(153 mm) from the floor and 6 in (153 mm) from
the ceiling to ensure proper ventilation.
Exhaust Vent
27 square inches
(442 square
millimeters) minimum
of venting
Removable
Access Panel
(by others)
PD4-16-F
Dimming / Switching Panel
shown surface mounted
behind a removable access
panel.
Wiring Conduit
Structural Wall
Intake Vent
27 square inches
(442 square
millimeters) minimum
of venting
Wiring Conduit
LV16-120
Low-Voltage
Enclosure
Wall Cavity Mounting
In addition to the Panel Mounting requirements found in this document, the following is required when
mounting panels into a wall cavity.
NOTE: Installation must comply with all working space
requirements. Consult with your jurisdiction for local
requirements.
4
PD4-16-F
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom / HomeWorks Lighting Control Panels
369867f 5 01.14.20
Wall Cavity Mounting (continued)
30in (762 mm)
78in
(1981 mm)
6in
(153 mm)
3.03in
(77 mm)
1.8in
(46 mm)
Exhaust
Vent
Front View Cross-section view of
access-wall installation
6in
(153 mm)
Minimum
*9 in (228 mm)
shown
PD4-16-F Dimming / Switching
Panels shown surface mounted
behind a removable access
panel.
LV16-120
Low-Voltage
Enclosure
Minimum clearance
from panel cover to
access panel wall
Minimum clearance
from panel cover to
access panel wall
Intake
Vent
6in
(153 mm)
Minimum
6in
(153 mm)
Minimum
6in
(153 mm)
Minimum
*9 in (228 mm)
shown
NOTE: Installation must comply with all working space requirements. Consult with your jurisdiction for local requirements.
5
PD4-16-F
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom / HomeWorks Lighting Control Panels
369867f 6 01.14.20
Louvered upper (exhaust) vent must be
installed as shown with vent openings
facing upwards.
Louvered lower (intake) vent must be
installed as shown with vent openings
facing downwards.
Note the direction of
louvered vent openings.
Wall Cavity Mounting (continued)
Vent orientation: Proper venting is required to cool equipment correctly when installed behind a removable
access panel. If louvered vents are used, they must be installed as shown below to allow required air flow and
cooling. A minimum of 27 square inches (442 square millimeters) of venting (area of vent openings / aperture)
required for each of the intake and exhaust vents.
6
PD4-16-F
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom / HomeWorks Lighting Control Panels
369867f 7 01.14.20
Panel Dimensions
All dimensions shown as: in (mm)
Top View
Bottom View
Left Side View
Right Side View
16.00
(406.4)
16.09
(408.7)
12.85
(326.4)
18.09
(459.5)
0.15
(3.8)
18.00
(457.2)
14.50
(368.3)
3.08
(78.2)
Ø 0.31
(7.9)
0.43
(10.9)
Ø 0.63
(15.8)
2.97
(75.5)
)Lutron, Lutron, myRoom, and HomeWorks are trademarks or registered trademarks of Lutron Electronics Co., Inc. in the US and/or other countries.
All other product names, logos, and brands are property of their respective owners.
7