PD4-16-F
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
myRoom / HomeWorks Lighting Control Panels
369867f 3 01.14.20
Mounting for Panels
• For indoor use only.
• Surface-mount only.
• Install in accordance with all local and national
electrical codes.
• Equipment is passively air-cooled.
• Panels weigh up to 30 lb (14 kg). Reinforce
wall structure for weight and local codes.
• Use keyholes with bolts sufficient for 30 lb
(14 kg) load, 1/4 in (M6) bolts recommended.
• Mount panel(s) within 7º of true vertical.
• Leave 6 in (153 mm) clearance on each side of
panel.
• Mount in a location where the cover will not
be blocked. 12 in (304 mm) of clearance is
recommended in front of the panel, however a
minimum of 3.03 in (77 mm) can be achieved:
see Wall Cavity Mounting guidelines for more
information.
• Panel can be installed in a minimum of
8.125 cubic feet (0.23 cubic meter) of
confined space providing intake and exhaust
venting requirements are met. See Wall Cavity
Mounting section for details.
• Mount panel so Line / Mains voltage wiring is
at least 6 ft (1.8 m) from sound or electronic
equipment and wiring.
• Mount panel where audible noise is
acceptable (internal relays on modules click).
• Panel(s) should be a minimum of 6 in
(153 mm) from the floor and ceiling.
• Panel can be installed above a suspended
ceiling. See Suspended Ceiling Installation
section for details.
• Consult Dimensions page for panel size,
conduit knockouts, and mounting hole
locations.
Panel Stacking
• Do not mount more than two PD4-16-F panels
vertically.
• A single LV16 panel may be installed under as many
as two PD4-16-F panels.
• A minimum vertical spacing of 6 in (153 mm) is
required between each panel.
• If stacking two PD4-16-F panels above an LV16
panel, PDUs should only be provided by the LV16
panel. No PDUs should be provided by any modules
located in the PD4-16-F panels.
Suspended Ceiling Installation
• Panel(s) can be a minimum of 1 in (25 mm) from the
top of the suspended ceiling and ceiling.
• Panels cannot be vertically stacked when installed
above a suspended ceiling.
• Maintain 12 in (304 mm) of clearance in front of panel
when mounting in a suspended ceiling.
1 in
(25 mm)
Minimum
1 in
(25 mm)
Minimum
Suspended Ceiling
NOTE: Installation must comply with all working space
requirements. Consult with your jurisdiction for local
requirements.
Ceiling