SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
369865d 1 02.07.18
BACnet PIC Statement for myRoom Virtual Devices using Versions 9.5 to 11.5
Software
License
myRoom
ASHRAE’s BACnet® Protocol Implementation Conformance Statement (PICS)
Date: February 7, 2018
Vendor Name: Lutron Electronics Co., Inc.
Product Name: myRoom BACnet Integration
Applications Software Version: 2.0
Firmware Revision: 9.5 to 11.5
BACnet Protocol Revision: 4
Vendor ID: 176
Product Description
BACnet IP is embedded in the myRoom processor. There are two types of BACnet devices available in myRoom:
subsystem devices and area devices. The subsystem devices are main BACnet devices; typically, one main device
per guestroom of the building. The area devices are virtual BACnet devices of the subsystem device, typically one
per room of the building. It is normal to have multiple subsystem main devices and area virtual devices in a project.
BACnet Interoperability Building Blocks Supported (Annex K):
K.1.2 BIBB Data Sharing ReadProperty-B (DS-RP-B)
K.1.4 BIBB Data Sharing ReadPropertyMultiple-B (DS-RPM-B)
K.1.8 BIBB Data Sharing WriteProperty-B (DS-WP-B)
K.1.10 BIBB Data Sharing WritePropertyMultiple-B (DS-WPM-B)
K.1.12 BIBB Data Sharing COV-B (DS-COV-B)
K.5.2 BIBB Device Management DynamicDeviceBinding-B (DM-DDB-B)
K.5.4 BIBB Device Management DynamicObjectBinding-B (DM-DOB-B)
K.5.6 BIBB Device Management DeviceCommunicationControl-B (DM-DCC-B)
BACnet Standardized Device Profile (Annex L):
BACnet Application Specific Controller (B-ASC)
Segmentation Capability:
Segmented requests supported? No. Window Size: n/a
Segmented responses supported? No. Window Size: n/a
Non-Standard Application Services:
Non-standard application services are not supported.
BACnet is a registered trademark of ASHRAE. ASHRAE does not endorse, approve or test
products for compliance with ASHRAE standards. Compliance of listed products to the
requirements of ASHRAE Standard 135 is the responsibility of BACnet International (BI).
1
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
369865d 2 02.07.18
BACnet PIC Statement for myRoom Virtual Devices using Versions 9.5 to 11.5
Software
License
myRoom
Standard Object Types Supported:
Device
1. Dynamically creatable using BACnet CreateObject service? No.
2. Dynamically deletable using BACnet DeleteObject service? No.
3. List of optional properties supported: Active_COV_Subscriptions, Description, Location, Profile_Name.
4. List of all properties that are writable where not otherwise required by this standard: None.
5. List of proprietary properties: None.
6. List of any property value range restrictions: None.
Analog Value
1. Dynamically creatable using BACnet CreateObject service? No.
2. Dynamically deletable using BACnet DeleteObject service? No.
3. List of optional properties supported: COV_Increment (See Table for objects that support this property).
4. List of all properties that are writable where not otherwise required by this standard: None.
5. List of proprietary properties: None.
6. List of any property value range restrictions: See Table.
Binary Value
1. Dynamically creatable using BACnet CreateObject service? No.
2. Dynamically deletable using BACnet DeleteObject service? No.
3. List of optional properties supported: Active_Text, Inactive_Text.
4. List of all properties that are writable where not otherwise required by this standard: None.
5. List of proprietary properties: None.
6. List of any property value range restrictions: See Table.
Multi-State Value
1. Dynamically creatable using BACnet CreateObject service? No.
2. Dynamically deletable using BACnet DeleteObject service? No.
3. List of optional properties supported: State_Text.
4. List of all properties that are writable where not otherwise required by this standard: None.
5. List of proprietary properties: None.
6. List of any property value range restrictions: See Table.
Data Link Layer Options:
Other: These devices are virtual devices and are represented by a six octet address equal to the 48-bit device
instance of the virtual device.
Device Address Binding:
Is static device binding supported? No.
Networking Options:
BACnet / IP Annex J non-BBMD functionality; the myRoom processor is able to register as a foreign device. The
myRoom processor is able to initiate original-broadcast-NPDU.
Character Sets Supported:
Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
• ANSI X3.4.
BACnet Routing:
The myRoom processor is a BACnet router. All of the virtual area devices are routed through the main subsystem
device.
2
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
369865d 3 02.07.18
BACnet PIC Statement for myRoom Virtual Devices using Versions 9.5 to 11.5
Software
License
myRoom
Object Name Type Instance Read Write COV Units Min PV Max PV
Inactive
Text (0)
Active
Text (1)
State Text (Multi-State)
{AreaName}
{
Instance}
DEVICE {Base} +
{System}
+ 1
X —— ——
Notes: The Area Name is the logical name that typically corresponds to a physical location in a building. The Instance is the same as the
unique Device ID assigned to each area.
Lighting Level AV 2 X X X % 0 100
Notes: The intensity level of all lighting fixtures in the area. The lighting level will be an analog value between 0% and 100%. If the lighting
fixtures in the area are at different light levels, this value will be set to the level of the highest intensity in that area. Does not include
RF zones.
Lighting State BV 3 X X X 0 1 Off On
Notes: The lighting state will be ON if any of the lighting fixtures in the area are in the On state; if all lighting fixtures are off, the lighting
state will be set to OFF.
Lighting Scene MSV 4 X X X 1 Number
of scenes
defined
for this
area
{SceneName}
Notes: The lighting preset to which the lighting fixtures in that area are currently set. If the value is set to 1, the Off Scene will be selected,
which will turn all lights to OFF. All other scenes are defined within the Lutron system configuration software. If lights are currently
not set to a valid lighting scene, then the value will be set to an unknown preset level.
Daylighting Enabled
(not available)
BV 5 X X X 0 1 Disabled Enabled
Daylighting Level
(not available)
AV 6 X X X % 0 100
Disable Occupancy BV 7 X X X 0 1 False True
Notes: When set to True, the area will go to the Occupied level and the occupancy sensors will no longer affect the lights in the area.
Occupancy State MSV 8 X X 1 4 1 = Unoccupied
2 = Occupied
3 = Inactive (not available)
4 = Unknown
Notes: A read-only property that indicates the occupancy of a guestroom area. Occupied means that at least one sensor in the area is
indicating Occupancy. Unoccupied means that all of the sensors in the area are indicating Unoccupied. Unknown means that not all of
the sensors in the area have reported their status.
Unoccupied Level AV 9 X X X 0 216
Notes: The light level to which the lights in the area will be set when an area transitions to Unoccupied. Values:
0 = Off
1–100 = Light Level Percentage
101 = Unaffected
102 = Daylighting (not available)
200 = Off Scene
201–216 = Scene 1 through 16
(0 = default)
AV = Analog Value, BV = Binary Value, MSV = Multi-State Value
{AreaName} is a text string defined in the Lutron myRoom system configuration software
{Instance} is a number defined in the Lutron myRoom system configuration software that is equal to the {Base} number + {System} number +1
{Base} is a 22-bit value set in the Lutron myRoom system configuration software (default 1760000)
{System} is an 8-bit value set in the Lutron myRoom system configuration software (0 to 127)
{SceneName} is a text string of the name of each scene that is defined in the Lutron myRoom system configuration software
PV = Present Value
3
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
369865d 4 02.07.18
BACnet PIC Statement for myRoom Virtual Devices using Versions 9.5 to 11.5
Software
License
myRoom
Object Name Type Instance Read Write COV Units Min PV Max PV
Inactive
Text (0)
Active
Text (1)
State Text (Multi-State)
Occupied Level AV 10 X X X 0 216
N
otes: The light level to which the lights in the area will be set when an area transitions to Occupied or when Occupancy is disabled. Values:
0 = Off
1–100 = Light Level Percentage
101 = Unaffected
102 = Daylighting (not available)
200 = Off Scene
201–216 = Scene 1 through 16
(100 = default)
Additional Occupied
Timeout
AV 11 X X X min 0 300
Notes: After all sensors in the area indicate Unoccupied, the value displayed will be the number of additional minutes that the system will
wait before changing the lights to the Unoccupied level. Note: the sensor also has a built-in timeout. To learn how to check the sensor
see the Lutron Occupancy Vacancy Sensors on www.lutron.com
Loadshed Allowed
(not available)
BV 12 X X X 0 1 No Yes
Loadshed Goal
(not available)
AV 13 X X X 0 90
Occupancy Mode MSV 14 X X X 1 4 1 = Inactive
2 = Automatic ON and Automatic OFF
3 = Manual ON and Automatic OFF
4 = Not Applicable
Notes: Determines the way that the occupancy sensors control the lights. When set to Inactive, the Occupancy Mode will not control the
lights in the area. When set to Automatic ON and Automatic OFF, the sensors will turn lights to their occupied level when occupied
and to their unoccupied level when unoccupied. When set to Manual ON and Automatic OFF, the sensors will set lights to the
unoccupied level only when an area changes to Unoccupied. Not Applicable means that the area is not controlled by occupancy.
Number of Lamp
Failures
AV 15 X X 0 none
Notes: For all digitally-controlled EcoSystem or DALI
® fluorescent ballasts and LED drivers controlled by a DIN power module, the number of
ballasts with lamp failures in the area will be displayed. If the value is 0, there are no lamp failures for the area.
Number of Devices
Not Responding
AV 16 X X 0 none
Notes: For any QS device, EcoSystem or DALI
® digital fluorescent ballast or LED drivers controlled by a DIN power module, the number of
devices that are programmed into the system but are not responding will be displayed. If the value is 0, there are no device failures
for the area.
Hyperion Enabled
(not available)
BV 17 X X X 0 1 Disabled Enabled
Total Lighting
Power
AV 18 X X watts 0 none
Notes: A calculated value that indicates the total instantaneous power consumption for all of the lighting loads in the area.
Maximum Lighting
Power
AV 19 X X watts 0 none
Notes: The maximum connected lighting load of the area. This value is the maximum value that Total Power can achieve. Maximum Power
minus Total Power equals the power being saved. Typically, this value does not change.
AV = Analog Value, BV = Binary Value, MSV = Multi-State Value
PV = Present Value
4
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
369865d 5 02.07.18
BACnet PIC Statement for myRoom Virtual Devices using Versions 9.5 to 11.5
Software
License
myRoom
Object Name Type Instance Read Write COV Units Min PV Max PV
Inactive
Text (0)
Active
Text (1)
State Text (Multi-State)
Roof-Mount
C
loudy Day Sensor:
Area Status
(not available)
BV 20 X X X 0 1 Dark Sunny
Radio Window
Sensor Dark
Override State
(not available)
MSV 21 X X* X 1 3 1 = Disabled
2 = Enabled
3 = Mixed
Light Level
Discrepancy
(not available)
BV 22 X X 0 1 False True
Number of Wireless
Input Device
Failures
AV 23 X X none
Notes: If a wireless input (e.g., occupancy sensor) that is connected to the system is no longer communicating with the Lutron system, the
device output will be greater than 0. The value will be equal to the number of failures in the area. This could be because of battery
failure, the device being out of range of the QSM, or device failure. If the value equals 0, all wireless inputs in the area are reporting
properly.
Radio Window
Sensor Bright
Override State
(not available)
MSV 24 X X* X 1 3 1 = Disabled
2 = Enabled
3 = Mixed
Number of Loads
with Lamps
Nearing End of Life
(not available)
AV 25 X X 0 none
{ZoneName} Level AV 1000 to
1099
XXX % 0100—
Notes: The light level intensity of a specific zone of lighting within an area. The light level will be an analog value between 0% and 100%.
There can be multiple lighting zones defined within each area. Each lighting fixture in the area will be assigned to one, and only one,
lighting zone. Each will have a unique instance ID from 1000 to 1999. RF zone controls are not included.
{ShadeGroupName}
Level
AV 2000 to
2999
XXX % 0100—
Notes: The shade level of a specific shade group of Lutron Sivoia QS shades within an area. The shade level will be an analog value between
0% and 100%. 100% equals fully open; 0% equals fully closed. There can be multiple shade groups within each area; each group will
have a unique instance ID from 2000 to 2999.
{ShadeGroupName}
Preset
MSV 3000 to
3999
X X X 1 34 {PresetName}
Notes: Displays to which shade preset the shade motors of each shade group in an area are currently set.
The values correspond to:
1 = Open; 2–30 = User programmable presets; 31 = Closed; 32–33 = Not used
34 = Undefined (Shade levels do not match any presets)
{ShadeGroupName}
Radio Window
Sensor Shade
Group Status
(not available)
MSV 4000 to
4099
X X 1 3 1 = Unknown
2 = Sunny
3 = Dark
* Mixed is a read-only state.
AV = Analog Value, BV = Binary Value, MSV = Multi-State Value
{ZoneName} is a text string defined in the Lutron system configuration software
{ShadeGroupName} is a text string defined in the Lutron system configuration software
{PresetName} is a text string defined in the Lutron system configuration software
PV = Present Value
5
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
369865d 6 02.07.18
BACnet PIC Statement for myRoom Virtual Devices using Versions 9.5 to 11.5
Software
License
myRoom
Object Name Type Instance Read Write COV Units Min PV Max PV
Inactive
Text (0)
Active
Text (1)
State Text (Multi-State)
{3-WireMotorZone
Na
me}
MSV 5000 to
5099
X X X 1 3 1 = Stop
2 = Open
3 = Close
Notes: Displays the current state of a 3-wire motor output within a specific area. If the value is set to 1, the output will be in the Stopped
state (both relays open). If the value is set to 2, the output will be Opening (open relay active). If the value is set to 3, the output will
be Closing (close relay active).
Light Sensor Value
(not available)
AV 6000 to
6999
X—X fc 0—
{PartitionWall
Name} State
(not available)
MSV 7000 to
7099
X X X 1 3 1 = Unknown
2 = Closed
3 = Open
{HVACZoneName}
Temperature
Celsius
AV 7100 X X Degrees
Celsius
0100
Notes: The temperature currently measured in the HVAC zone of this area. Temperature caps at the limit of the range, in degrees Celsius.
{HVACZoneName}
Heat Setpoint
Celsius
AV 7101 X X X Degrees
Celsius
0100
Note: Zone heat setpoint of the HVAC unit, in degrees Celsius.
{HVACZoneName}
Cool Setpoint
Celsius
AV 7102 X X X Degrees
Celsius
0100
Note: Zone cool setpoint of the HVAC unit, in degrees Celsius.
{HVACZoneName}
Temperature
Fahrenheit
AV 7103 X X Degrees
Fahrenheit
32 212
Notes: The temperature currently measured in the HVAC zone of this area. Temperature caps at the limit of the range, in degrees Fahrenheit.
{HVACZoneName}
Heat Setpoint
Fahrenheit
AV 7104 X X X Degrees
Fahrenheit
32 212
Note: Zone heat setpoint of the HVAC unit, in degrees Fahrenheit.
{HVACZoneName}
Cool Setpoint
Fahrenheit
AV 7105 X X X Degrees
Fahrenheit
32 212
Note: Zone cool setpoint of the HVAC unit, in degrees Fahrenheit.
{HVACZoneName}
Operating Mode
MSV 7106 X X X 1 8 1 = Off/Protect
2 = Heat
3 = Cool
4 = Auto
5 = Emergency Heat
6 = Reserved
7 = Fan
8 = Dry
Notes: The operating mode currently commanded in the HVAC zone. See Operating State for actual reported stage information.
AV = Analog Value, MSV = Multi-State Value
fc = foot candles
{3-WireMotorZoneName} is a text string defined in the Lutron system configuration software
{PartitionWallName} is a text string defined in the Lutron system configuration software
{HVACZoneName} is a text string defined in the Lutron system configuration software. Only one HVAC zone per Area Virtual Device is supported.
PV = Present Value
6
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
369865d 7 02.07.18
BACnet PIC Statement for myRoom Virtual Devices using Versions 9.5 to 11.5
Software
License
myRoom
Object Name Type Instance Read Write COV Units Min PV Max PV
Inactive
Text (0)
Active
Text (1)
State Text (Multi-State)
{HVACZoneName}
Ope
rating State
MSV 7107 X X 1 10 1 = None, Heat Last
2 = Heat 1
3 = Heat 1+2
4 = Heat 1+2+3
5 = Heat 3
6 = None, Cool Last
7 = Cool 1
8 = Cool 1+2
9 = Off
10 = Emergency Heat
11 = Dry
Notes: The stage information currently reported for the HVAC zone and its unit. See Operating Mode for commanded mode.
{HVACZoneName}
Fan Mode
MSV 7108 X X X 1 8 1 = Auto
2 = On
3 = Cycler
4 = No Fan
5 = High
6 = Medium
7 = Low
8 = Top
Notes: The fan operating mode currently commanded in the HVAC zone. See Fan State for actual reported stage information.
{HVACZoneName}
Fan State
MSV 7109 X X 1 5 1 = Unknown
2 = Off
3 = High/On
4 = Medium
5 = Low
Notes: The speed information currently reported for the HVAC fan zone and its fan unit. See Fan Mode for commanded mode.
{HVACZoneName}
Eco Mode
(not available)
BV 7110 X X X 0 1 Disabled Enabled
{HVACZoneName}
HVAC Schedules
(not available)
MSV 7112 X X X 1 3 1 = Disabled
2 = Enabled
3 = Permanent Hold
4 = Temporary Hold
{HVACZoneName}
HVAC Power
AV 7113 X X watts 0 none
Notes: A read-only, calculated value which indicates the instantaneous power consumption of this HVAC zone in watts.
AV = Analog Value, BV = Binary Value, MSV = Multi-State Value
{HVACZoneName} is a text string defined in the Lutron myRoom system configuration software. Only one HVAC zone per Area Virtual Device is supported.
{KeypadName} is a text string defined in the Lutron myRoom system configuration software
PV = Present Value
7
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
369865d 8 02.07.18
BACnet PIC Statement for myRoom Virtual Devices using Versions 9.5 to 11.5
Software
License
myRoom
Object Name Type Instance Read Write COV Units Min PV Max PV
Inactive
Text (0)
Active
Text (1)
State Text (Multi-State)
{HVACZoneName}
Si
ngle Setpoint
Celsius
AV 7114 X X X Degrees
Celsius
0100
Note: Zone heat setpoint of the HVAC unit, in degrees Celsius.
{HVACZoneName}
Single Setpoint
Fahrenheit
AV 7115 X X X Degrees
Fahrenheit
32 212
Note: Zone heat setpoint of the HVAC unit, in degrees Celsius.
{HVACZoneName}
Negative Drift
Celsius
AV 7116 X X X Degrees
Celsius
08—
{HVACZoneName}
Positive Drift
Celsius
AV 7117 X X X Degrees
Celsius
08—
{HVACZoneName}
Negative Drift
Fahrenheit
AV 7118 X X X Degrees
Fahrenheit
015—
{HVACZoneName}
Positive Drift
Fahrenheit
AV 7119 X X X Degrees
Fahrenheit
015—
{KeypadName}
State
BV 8000 to
8999
XXX 0 1DisabledEnabled
Notes: When set to Enabled, the selected keypad will work as programmed. When set to Disabled, the selected keypad will have no effect on
the system.
AV = Analog Value, BV = Binary Value, MSV = Multi-State Value
{HVACZoneName} is a text string defined in the Lutron myRoom system configuration software. Only one HVAC zone per Area Virtual Device is supported.
{KeypadName} is a text string defined in the Lutron myRoom system configuration software
PV = Present Value
)Lutron, Lutron, EcoSystem, and Sivoia are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries.
Hyperion and myRoom are trademarks of Lutron Electronics Co., Inc.
BACnet is a registered trademark of the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (ASHRAE).
DALI is a registered trademark of DALI Systems Co. Ltd.
8