BACnet PIC Statement for myRoom Virtual Devices using Versions 9.5 to 11.5
Software
License
myRoom
Object Name Type Instance Read Write COV Units Min PV Max PV
Inactive
Text (0)
Active
Text (1)
State Text (Multi-State)
Occupied Level AV 10 X X X — 0 216 — — —
N
otes: The light level to which the lights in the area will be set when an area transitions to Occupied or when Occupancy is disabled. Values:
0 = Off
1–100 = Light Level Percentage
101 = Unaffected
102 = Daylighting (not available)
200 = Off Scene
201–216 = Scene 1 through 16
(100 = default)
Additional Occupied
Timeout
AV 11 X X X min 0 300 — — —
Notes: After all sensors in the area indicate Unoccupied, the value displayed will be the number of additional minutes that the system will
wait before changing the lights to the Unoccupied level. Note: the sensor also has a built-in timeout. To learn how to check the sensor
see the Lutron Occupancy Vacancy Sensors on www.lutron.com
Loadshed Allowed
(not available)
BV 12 X X X — 0 1 No Yes —
Loadshed Goal
(not available)
AV 13 X X X — 0 90 — — —
Occupancy Mode MSV 14 X X X — 1 4 — — 1 = Inactive
2 = Automatic ON and Automatic OFF
3 = Manual ON and Automatic OFF
4 = Not Applicable
Notes: Determines the way that the occupancy sensors control the lights. When set to Inactive, the Occupancy Mode will not control the
lights in the area. When set to Automatic ON and Automatic OFF, the sensors will turn lights to their occupied level when occupied
and to their unoccupied level when unoccupied. When set to Manual ON and Automatic OFF, the sensors will set lights to the
unoccupied level only when an area changes to Unoccupied. Not Applicable means that the area is not controlled by occupancy.
Number of Lamp
Failures
AV 15 X — X — 0 none — — —
Notes: For all digitally-controlled EcoSystem or DALI
® fluorescent ballasts and LED drivers controlled by a DIN power module, the number of
ballasts with lamp failures in the area will be displayed. If the value is 0, there are no lamp failures for the area.
Number of Devices
Not Responding
AV 16 X — X — 0 none — — —
Notes: For any QS device, EcoSystem or DALI
® digital fluorescent ballast or LED drivers controlled by a DIN power module, the number of
devices that are programmed into the system but are not responding will be displayed. If the value is 0, there are no device failures
for the area.
Hyperion Enabled
(not available)
BV 17 X X X — 0 1 Disabled Enabled —
Total Lighting
Power
AV 18 X — X watts 0 none — — —
Notes: A calculated value that indicates the total instantaneous power consumption for all of the lighting loads in the area.
Maximum Lighting
Power
AV 19 X — X watts 0 none — — —
Notes: The maximum connected lighting load of the area. This value is the maximum value that Total Power can achieve. Maximum Power
minus Total Power equals the power being saved. Typically, this value does not change.
AV = Analog Value, BV = Binary Value, MSV = Multi-State Value
PV = Present Value