0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 1 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
0 10 V Dimming Panels
0 10 V dimming panels provide 0 10 V dimming and switching for up to 48 0 10 V dimming/switching circuits.
Switching circuits provide air-gap off functionality when the 0 10 V control signal is set to zero.
Feed-Through Panels (without branch circuit breakers)
Panels are available with various quantities of 0 10 V dimming and switching circuits. Refer to the Product
Selection Guide pages for available combinations and additional information.
0 10 V Dimming/Switching
Panels work with:
• Quantum
® Systems
GRAFIK Eye
® 4000 Control Units
GP and LP Dimming Panels
DMX512 Control Systems via the
2Link
TM option
Mini-Size 010 V Panels
Dual voltage*
0 10 V Dimming circuits: 2 to 8
Switching circuits: 4 to 12
Standard-Size 010 V Panels
Dual voltage*
0 10 V Dimming circuits: 2 to 24
Switching circuits: 12 to 40
Large-Size 0–10 V Panels
Dual voltage*
0 10 V Dimming circuits: 2 to 48
Switching circuits: 28 to 48
* Dual voltage panels are rated for use at 120 V~ or 277 V~
Available Circuit Configurations
Separate Breakers for
Each Circuit per Module
Single Breaker for
All Circuits per Module
(continued on next page…)
1
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 2 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
0 10 V Dimming Panels (continued)
Main Lug Panels (with branch circuit breakers: 4 breakers per module, 1 breaker per switching circuit)
Panels are available with various quantities of 0 10 V dimming and switching circuits. Refer to the Product
Selection Guide pages for available combinations and additional information.
0 10 V Dimming/Switching
Panels work with:
• Quantum
® Systems
GRAFIK Eye
® 4000 Control Units
GP and LP Dimming Panels
DMX512 Control Systems via the
2Link
TM option
Standard-Size 010 V Panels
120 V~ only
0 10 V Dimming circuits: 4 to 20
Switching circuits: 4 to 20
Large-Size 0–10 V Panels
120 V~ or 277 V~
0 10 V Dimming circuits: 2 to 24
Switching circuits (120 V~): 24 to 36
Switching circuits (227 V~): 4 to 24
Extra-Large-Size 010 V Panels
277 V~ only
0 10 V Dimming circuits: 2 to 24
Switching circuits: 28 to 36
Available Circuit Configuration
Separate Breakers for Each Circuit
per Module
(continued on next page…)
2
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 3 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
0 10 V Dimming Panels (continued)
Mini-Size 010 V Panels
120 V~ or 277 V~
Large-Size 0–10 V Panels
120 V~ or 277 V~
Standard-Size 010 V Panels
120 V~ or 277 V~
0 10 V Dimming/Switching
Panels work with:
• Quantum
® Systems
GRAFIK Eye
® 4000 Control Units
GP and LP Dimming Panels
DMX512 Control Systems via the
2Link
TM option
0 10 V Dimming circuits: 4 to 8
Switching circuits: 4 to 8
0 10 V Dimming circuits: 12 to 24
Switching circuits: 12 to 24
0 10 V Dimming circuits: 28 to 48
Switching circuits: 28 to 48
Available Circuit Configuration
Single Breaker for All Circuits
per Module
Main Lug Panels (with branch circuit breakers: 1 breaker per module)
Panels are available only with equal quantities of 0 10 V dimming and switching circuits. Refer to the Product
Selection Guide pages for available combinations and additional information.
3
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 4 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Regulatory Approvals
• UL® Listed (Reference: UL File 42071)
Complies with ISO-9000
• CSA
Seismic Certified models available (Test Method
AC156. Reference OSHPD Preapproval OSP-0215-10).
Contact Lutron
® for details.
Power
Input power: 120 V~, 277 V~.
All voltages 50/60 Hz, phase-to-neutral.
Control circuit (feed-through panels only) dedicated
feed:
120 V~ or 277 V~ for dual voltage panels
Branch circuit breakers: UL
® rated thermal magnetic.
AIC ratings:
120 V~ 10,000 A
277 V~ 18,000 A (panels with 1 breaker per circuit)
14,000 A (panels with 1 breaker
per module)
Lightning strike protection: Meets ANSI/IEEE standard
62.41-1980. Can withstand voltage surges of up to
6000 V~ and current surges of up to 3000 A.
10-year power failure memory: Automatically restores
lighting to levels prior to power interruption.
Load Types (relay ratings)
Relay Rating
Load Type
120 V~ 277 V~
Tungsten 20 A 20 A
AC General Use* 20 A 20 A
Electric Discharge Lamp 16 A 16 A
Electronic Ballast (NEMA
® 410) 16 A 16 A
LED (NEMA
® 410) 16 A 16 A
Resistive 20 A 20 A
Inductive 20 A 20 A
Motor 1.0 HP 2.0 HP
* For additional information about 20 A receptacle controls using Lutron®
switching modules, see Lutron® XP Specification Submittal
(P/N369345e).
Maximum Inrush Requirements
LED loads, ballast loads, and other high inrush loads
must meet NEMA® 410 limits.
The maximum inrush current for each circuit must not
exceed 500 A peak, 2 ms duration.
Note: For inrush questions or for products with higher
inrush capability, please consult Lutron
®.
(continued on next page…)
Line voltage
Line current
2 ms
max.
500 A
max.
0 10 V Dimming Panels: Specifications
4
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 5 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
010 V Dimming Modules (TVM)
Two 0 10 V- circuits per module.
Sink or source 50 mA per output (maximum 750 mA
total per twenty-four outputs*).
5 BTU/hour maximum per module.
DIN rail mounted.
Able to control:
0 –10 V-, IEC
® Standard 60929
10 – 0 V-
PWM (Pulse Width Modulation), IEC
® Standard
60929
– DALI
® (Broadcast only), IEC® Standard 62386
Switching Modules (120 V~, 277 V~)
Able to control 20 A receptacles.
Switch legs rated at 20 A.
Four switch legs per module.
Patented Softswitch
® circuit eliminates arcing at
mechanical contacts when loads are switched, which
prolongs relay life to an average of 1,000,000 cycles
at 16 A.
10 BTU / hour per module.
For additional information, see Lutron
® XP
Specification Submittal (P/N369345e).
Wiring
Internal: Pre-wired by Lutron®.
System communications:
Low-voltage IEC PELV/NEC
® Class2 wiring connects
0 10 V dimming panels to other components.
Line (mains) voltage: Feed and load wiring only.
(Feed-through 0 10 V dimming panels also have
control circuit wiring). No other wiring or assembly
required.
Physical Design
Enclosure: NEMA-Type 1, IP-20 protection; 16 U.S.
gauge steel. Indoor use only.
Weight:
Mini-size panels: 27lb (13kg)
Standard-size panels: 80lb (37kg)
Large-size panels: 135lb (61.3kg)
Extra-large-size panels: 200lb (90.7kg)
Seismic Certification Limits (seismic-certified models
only):
– S
DS
= 2.5 g, z/h = 1.0, I
P
= 1.5
Contact Lutron
® for details.
Mounting
Mini- and standard-size panels: Surface-mount or
recess-mount between 16in (40 cm) studs.
Large-size and extra-large-size panels: Surface-mount
only.
Environment
32 °F to 104 °F (0 °C to 40 °C). Relative humidity less
than 90% non-condensing.
Warranty
For warranty information, please visit
www.lutron.com/en-US/Service-Support/Pages/
Service/Warranty/Warranty.aspx
0 10 V Dimming Panels: Specifications (continued)
* Each group of up to twelve TVM modules (twenty-four 010 V outputs) is powered by a single GRX-TVM-ISO2 power module. The 750 mA maximum
output rating per twenty-four 0–10 V circuits is based on the limitation of this power module.
5
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 6 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Prefix
CXP: Switching Panel
Number of Switching Circuits
Indicates number of load circuits in the panel (4 to 48)
Number of 0 10 V- Circuits
T2–T48: 2 – 48 0 –10 V- circuits
1
Panel Feed
F T: Feed-through (no branch circuit breakers)
2-Link Circuit Selector (optional)
Omit if 2-link is not required
Custom Panel Suffix
0 10 V Dimming Panels: How to Build a Model Number
Feed-Through Panels (without branch circuit breakers)
Prefix Number of
Switching
Circuits
Number of
0 –10V-
Circuits
Panel
Feed
Custom Panel Suffix
C X P 4 8 T 4 8 FT 2 L C G P X X X X
1
Number of 010 V- circuits vary based on number of switching circuits in the panel. Contact Lutron® for specific variations.
(continued on next page…)
Indicates a panel with special options
CGP718 includes panels with up to 40 switching
circuits and up to 24 0 10 V- circuits
CGP2686 includes panels with more than 40
switching circuits OR more than 24 0 10 V- circuits
Refer to the Product Selection Guide pages for
available combinations of 0 10 V dimming/switching
circuits as well as additional CGP number and panel
size information
If additional custom features are required, contact
Lutron
®
Examples of Custom Features That May
Require a Unique CGP Number
347 V~ switching
Constant-hot terminal blocks
2-Link
Circuit
Selector
(optional)
6
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 7 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Prefix
CXP: Switching Panel
Number of Switching Circuits
Indicates number of load circuits in the panel (4 to 48)
Voltage
120: 100 127 V~
277: 277 V~
Feed Type
4: 3-phase, 4-wire
Number of 0 10 V- Circuits
T2–T48: 2 – 48 0 –10 V- circuits
Panel Feed
ML: Main Lugs only
2-Link Circuit Selector (optional)
Omit if 2-link is not required
Branch Circuit Breakers
20: 20 A branch circuit breakers
15: 15 A branch circuit breakers
Custom Panel Suffix
0 10 V Dimming Panels: How to Build a Model Number (continued)
Main Lug Panels (with branch circuit breakers)
Prefix Feed
Type
Number of
Switching
Circuits
Voltage Number of
0 –10V-
Circuits
Panel
Feed
Branch
Circuit
Breakers
Custom Panel Suffix
C X P 4 8 2 7 7 4 T 4 8 M L 2 L 2 0 C G P X X X X
2-Link
Circuit
Selector
(optional)
Examples of Custom Features That May
Require a Unique CGP Number
Constant-hot terminal blocks
Main breakers (restrictions apply)
Branch breakers with higher AIC ratings
Alternate feed configurations
Indicates panel with special options
CGP662 includes 277 V~ panels with 1 breaker per
circuit; may have up to 36 switching circuits and up to
240 –10 V- circuits
CGP1404 includes 120 V~ panels with 1 breaker per
circuit; may have up to 40 switching circuits and up to
240 –10 V- circuits
CGP2705 includes 120 V~ and 277 V~ panels with
1 breaker per module; may have up to 48 switching
circuits and up to 480 10 V- circuits. Panels built
under this CGP number must always have an equal
number of switching circuits and 0 10 V- circuits
Refer to the Product Selection Guide pages for
available combinations of 0 10 V dimming/switching
circuits as well as additional CGP number and panel
size information
If additional custom features are required, contact
Lutron
®
7
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 8 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
0 10 V Dimming Panels: Configurations
Feed-Through Panels (without branch circuit breakers)
Mini-Size Panels 24 in (609 mm)
(120/277 V~)
Model
Prefix
Switching
Circuits
0 –10 V-
Circuits
Feed Type Maximum Feed
XP4 4 2 – 4
Feed-through 120/277 V~ 20 A
XP8 8 2 – 8
XP12 12 2 – 8
Standard-Size Panels 59 in (1498 mm)
(120/277 V~)
Model
Prefix
Switching
Circuits
0 –10 V-
Circuits
Feed Type Maximum Feed
XP12 12 10 –12
Feed-through 120/277 V~ 20 A
XP16 16 2 –16
XP20 20 2 –20
XP24 24 2 –24
XP28 28 224
XP32 32 224
XP36 36 224
XP40 40 224
Large-Size Panels 63 in (1600 mm)
(120/277 V~)
Model
Prefix
Switching
Circuits
0 –10 V-
Circuits
Feed Type Maximum Feed
XP28 28 26 – 28
Feed-through 120/277 V~ 20 A
XP32 32 26 – 32
XP36 36 26 – 36
XP40 40 26 – 40
XP44 44 2 – 44
XP48 48 2 – 48
Wire Sizes (apply to feed and load wiring):
Panels accept 14 to 10 AWG (2.5 to 4.0 mm
2
) for feed wiring and switch legs (to loads)
Power (Line/Hot) and Switched (Line/Hot) connect directly to terminal block for switch legs
(continued on next page…)
8
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 9 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
0 10 V Dimming Panels: Configurations (continued)
Main Lug Panels (with branch circuit breakers: 4 breakers per module, 1 breaker per switching circuit)
Standard-Size Panels 59 in (1498 mm)
(120 V~)
Model
Prefix
Switching
Circuits
0 –10 V-
Circuits
Feed Type and Wire Size
Maximum
Feed
Branch Circuit
Breakers
XP4 4 2 – 4
3Ø 4W
Main Lugs only
Main Lugs accept
4AWG (25mm
2
) to
250 kcmil (mcm) (120mm
2
)
200 A 15 A or 20 A
XP8 8 2 – 8
XP12 12 212
XP16 16 2 –16
XP20 20 2 –20
Large-Size Panels 63 in (1600 mm)
(120 V~)
Model
Prefix
Switching
Circuits
0 –10 V-
Circuits
Feed Type and Wire Size
Maximum
Feed
Branch Circuit
Breakers
XP24 24
2 – 24
3Ø 4W
Main Lugs only
Main Lugs accept
4AWG (25mm
2
) to
300 kcmil (mcm) (150mm
2
)
225 A 15 A or 20 A
XP28 28
2 – 24
XP32 32
2 – 24
XP36 36
2 – 24
Large-Size Panels 63 in (1600 mm)
(277 V~)
Model
Prefix
Switching
Circuits
0 –10 V-
Circuits
Feed Type and Wire Size
Maximum
Feed
Branch Circuit
Breakers
XP4 4 2 – 4
3Ø 4W
Main Lugs only
Main Lugs accept
4AWG (25mm
2
) to
300 kcmil (mcm) (150mm
2
)
250 A 20 A
XP8 8 2 – 8
XP12 12 212
XP16 16 2 –16
XP20 20 2 –20
XP24 24 2 –24
Extra-Large-Size Panels 82 in (2082 mm)
(277 V~)
Model
Prefix
Switching
Circuits
0 –10 V-
Circuits
Feed Type and Wire Size
Maximum
Feed
Branch Circuit
Breakers
XP28 28 2 – 24
3Ø 4W
Main Lugs only
Main Lugs accept
4AWG (25mm
2
) to
350 kcmil (mcm) (185mm
2
)
300 A 20 AXP32 32 2 – 24
XP36 36 2 – 24
Wire Sizes (apply to load wiring):
Panels accept 14 to 10 AWG (2.5 to 4.0 mm
2
) for switch legs (to loads)
(continued on next page…)
9
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 10 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
0 10 V Dimming Panels: Configurations (continued)
Main Lug Panels (with branch circuit breakers: 1 breaker per module)
Mini-Size Panels 24 in (609 mm)
(120/277 V~)
Model
Prefix
Switching
Circuits
0 –10 V-
Circuits
Feed
Type
Wire Size
Maximum
Feed
Branch Circuit
Breakers
XP4 4 4
2W
14 AWG to 8 AWG (2.5 mm
2
to 6.0 mm
2
)
15 A* or 20 A
15 A* or 20 A
XP8 8 8
3Ø 4W
Standard-Size Panels 59 in (1498 mm)
(120/277 V~)
Model
Prefix
Switching
Circuits
0 –10 V-
Circuits
Feed
Type
Wire Size
Maximum
Feed
Branch Circuit
Breakers
XP16 16 16
3Ø 4W 14 AWG to 2/0 AWG (2.5 mm
2
to 70 mm
2
)
175 A
(CU wire)
135 A
(AL wire)
15 A* or 20 A
XP20 20 20
XP24 24 24
Large-Size Panels 63 in (1600 mm)
(120/277 V~)
Model
Prefix
Switching
Circuits
0 –10 V-
Circuits
Feed
Type
Wire Size
Maximum
Feed
Branch Circuit
Breakers
XP28 28 28
3Ø 4W 14 AWG to 2/0 AWG (2.5 mm
2
to 70 mm
2
)
175 A
(CU wire)
135 A
(AL wire)
15 A* or 20 A
XP32 32 32
XP36 36 36
XP40 40 40
XP44 44 44
XP48 48 48
* 15 A available for 120 V~ panels only.
Wire Sizes (apply to load wiring):
Panels accept 14 to 10 AWG (2.5 to 4.0 mm
2
) for switch legs (to loads)
10
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 11 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
0 10 V Dimming Panels: Product Selection Guides
Use the Product Selection Guides on the following pages to determine:
Available combinations of 010 V dimming circuits and switching circuits for each panel type.
Basic CGP numbers for these panels (other CGP number options may be available if additional custom features
are required).
Enclosure sizes for each available combination.
Using the Product Selection Guides:
Step 1:
Select the proper Product Selection Guide for the panel type you are specifying:
Product Selection Guide 1: Feed-through panels
Product Selection Guide 2: 120 V~ Main lug panels (1breaker per circuit)
Product Selection Guide 3: 277 V~ Main lug panels (1breaker per circuit)
Product Selection Guide 4: 120 V~ or 277 V Main lug panels (1 breaker per module)
Step 2:
Select the total number of switching circuits from the horizontal row across the top of the guide.
Step 3:
Select the proper number of 0 10 V circuits from the vertical column at the left of the guide.
Step 4:
The intersection of these two values will indicate the proper CGP number and enclosure size for that combination
of switching and 0 10 V dimming circuits. (N/A indicates an invalid combination for that panel type.)
Example
Product
Selection Guide
1
Quantity of Switching Circuits
Quantity of 0 –10 V
Dimming Circuits
4 8 12 16 20 24 28 32
2
718
(24 in)
718
(24 in)
718
(24 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
4
718
(24 in)
718
(24 in)
718
(24 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
6 N/A
718
(24 in)
718
(24 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
8 N/A
718
(24 in)
718
(24 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
10 N/A N/A
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
12 N/A N/A
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
14 N/A N/A N/A
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
Step 1
Type of panel:
Feed-through
Step 2
Number of
Switching Circuits: 12
Step 3
Number of 0 10 V
Dimming Circuits: 6
Step 4
CGP number: 718;
enclosure size: 24 in
(609 mm)
(continued on next page…)
11
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 12 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
0 10 V Dimming Panels: Product Selection Guides (continued)
120 V~ / 277 V~ Feed-Through Panels (Dual Voltage)
Product
Selection Guide
1
Quantity of Switching Circuits
Quantity of 0 –10 V
Dimming Circuits
4 8 12 16 20 24 28 32 36 40 44 48
2
718
(24 in)
718
(24 in)
718
(24 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
2686
(63 in)
2686
(63 in)
4
718
(24 in)
718
(24 in)
718
(24 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
2686
(63 in)
2686
(63 in)
6 N/A
718
(24 in)
718
(24 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
2686
(63 in)
2686
(63 in)
8 N/A
718
(24 in)
718
(24 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
2686
(63 in)
2686
(63 in)
10 N/A N/A
718
(24 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
2686
(63 in)
2686
(63 in)
12 N/A N/A
718
(24 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
2686
(63 in)
2686
(63 in)
14 N/A N/A N/A
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
2686
(63 in)
2686
(63 in)
16 N/A N/A N/A
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
2686
(63 in)
2686
(63 in)
18 N/A N/A N/A N/A
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
2686
(63 in)
2686
(63 in)
20 N/A N/A N/A N/A
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
2686
(63 in)
2686
(63 in)
22 N/A N/A N/A N/A N/A
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
2686
(63 in)
2686
(63 in)
24 N/A N/A N/A N/A N/A
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
718
(59 in)
2686
(63 in)
2686
(63 in)
26 N/A N/A N/A N/A N/A N/A
2686
(63 in)
2686
(63 in)
2686
(63 in)
2686
(63 in)
2686
(63 in)
2686
(63 in)
28 N/A N/A N/A N/A N/A N/A
2686
(63 in)
2686
(63 in)
2686
(63 in)
2686
(63 in)
2686
(63 in)
2686
(63 in)
30 N/A N/A N/A N/A N/A N/A N/A
2686
(63 in)
2686
(63 in)
2686
(63 in)
2686
(63 in)
2686
(63 in)
32 N/A N/A N/A N/A N/A N/A N/A
2686
(63 in)
2686
(63 in)
2686
(63 in)
2686
(63 in)
2686
(63 in)
34 N/A N/A N/A N/A N/A N/A N/A N/A
2686
(63 in)
2686
(63 in)
2686
(63 in)
2686
(63 in)
36 N/A N/A N/A N/A N/A N/A N/A N/A
2686
(63 in)
2686
(63 in)
2686
(63 in)
2686
(63 in)
38 N/A N/A
N/A N/A N/A N/A N/A N/A N/A
2686
(63 in)
2686
(63 in)
2686
(63 in)
40 N/A N/A N/A N/A N/A N/A N/A N/A N/A
2686
(63 in)
2686
(63 in)
2686
(63 in)
42 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
2686
(63 in)
2686
(63 in)
44 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
2686
(63 in)
2686
(63 in)
46 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
2686
(63 in)
48 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
2686
(63 in)
(continued on next page…)
12
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 13 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
0 10 V Dimming Panels: Product Selection Guides (continued)
120 V~ Main Lug Panels (1 breaker per switching circuit)
Product
Selection Guide
2
Quantity of Switching Circuits
Quantity of 0 –10 V
Dimming Circuits
4 8 12 16 20 24 28 32 36 40 42
2
1404
(59 in)
1404
(59 in)
1404
(59 in)
1404
(59 in)
1404
(59 in)
1404
(63 in)
1404
(63 in)
1404
(63 in)
1404
(63 in)
N/A N/A
4
1404
(59 in)
1404
(59 in)
1404
(59 in)
1404
(59 in)
1404
(59 in)
1404
(63 in)
1404
(63 in)
1404
(63 in)
1404
(63 in)
N/A N/A
6 N/A
1404
(59 in)
1404
(59 in)
1404
(59 in)
1404
(59 in)
1404
(63 in)
1404
(63 in)
1404
(63 in)
1404
(63 in)
N/A N/A
8 N/A
1404
(59 in)
1404
(59 in)
1404
(59 in)
1404
(59 in)
1404
(63 in)
1404
(63 in)
1404
(63 in)
1404
(63 in)
N/A N/A
10 N/A N/A
1404
(59 in)
1404
(59 in)
1404
(59 in)
1404
(63 in)
1404
(63 in)
1404
(63 in)
1404
(63 in)
N/A N/A
12 N/A N/A
1404
(59 in)
1404
(59 in)
1404
(59 in)
1404
(63 in)
1404
(63 in)
1404
(63 in)
1404
(63 in)
N/A N/A
14 N/A N/A N/A
1404
(59 in)
1404
(59 in)
1404
(63 in)
1404
(63 in)
1404
(63 in)
1404
(63 in)
N/A N/A
16 N/A N/A N/A
1404
(59 in)
1404
(59 in)
1404
(63 in)
1404
(63 in)
1404
(63 in)
1404
(63 in)
N/A N/A
18 N/A N/A N/A N/A
1404
(59 in)
1404
(63 in)
1404
(63 in)
1404
(63 in)
1404
(63 in)
N/A N/A
20 N/A N/A N/A N/A
1404
(59 in)
1404
(63 in)
1404
(63 in)
1404
(63 in)
1404
(63 in)
N/A N/A
22 N/A N/A N/A N/A N/A
1404
(63 in)
1404
(63 in)
1404
(63 in)
1404
(63 in)
N/A N/A
24 N/A N/A N/A N/A N/A
1404
(63 in)
1404
(63 in)
1404
(63 in)
1404
(63 in)
N/A N/A
26 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
28 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
30 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
32 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
34 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
36 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
38 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
40 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
42 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
44 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
46 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
48 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
(continued on next page…)
13
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 14 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
0 10 V Dimming Panels: Product Selection Guides (continued)
277 V~ Main Lug Panels (1 breaker per switching circuit)
Product
Selection Guide
3
Quantity of Switching Circuits
Quantity of 0 –10 V
Dimming Circuits
4 8 12 16 20 24 28 32 36 40 42
2
662
(63 in)
662
(63 in)
662
(63 in)
662
(63 in)
662
(63 in)
662
(63 in)
662
(82 in)
662
(82 in)
662
(82 in)
N/A N/A
4
662
(63 in)
662
(63 in)
662
(63 in)
662
(63 in)
662
(63 in)
662
(63 in)
662
(82 in)
662
(82 in)
662
(82 in)
N/A N/A
6 N/A
662
(63 in)
662
(63 in)
662
(63 in)
662
(63 in)
662
(63 in)
662
(82 in)
662
(82 in)
662
(82 in)
N/A N/A
8 N/A
662
(63 in)
662
(63 in)
662
(63 in)
662
(63 in)
662
(63 in)
662
(82 in)
662
(82 in)
662
(82 in)
N/A N/A
10 N/A N/A
662
(63 in)
662
(63 in)
662
(63 in)
662
(63 in)
662
(82 in)
662
(82 in)
662
(82 in)
N/A N/A
12 N/A N/A
662
(63 in)
662
(63 in)
662
(63 in)
662
(63 in)
662
(82 in)
662
(82 in)
662
(82 in)
N/A N/A
14 N/A N/A N/A
662
(63 in)
662
(63 in)
662
(63 in)
662
(82 in)
662
(82 in)
662
(82 in)
N/A N/A
16 N/A N/A N/A
662
(63 in)
662
(63 in)
662
(63 in)
662
(82 in)
662
(82 in)
662
(82 in)
N/A N/A
18 N/A N/A N/A N/A
662
(63 in)
662
(63 in)
662
(82 in)
662
(82 in)
662
(82 in)
N/A N/A
20 N/A N/A N/A N/A
662
(63 in)
662
(63 in)
662
(82 in)
662
(82 in)
662
(82 in)
N/A N/A
22 N/A N/A N/A N/A N/A
662
(63 in)
662
(82 in)
662
(82 in)
662
(82 in)
N/A N/A
24 N/A N/A N/A N/A N/A
662
(63 in)
662
(82 in)
662
(82 in)
662
(82 in)
N/A N/A
26 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
28 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
30 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
32 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
34 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
36 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
38 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
40 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
42 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
44 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
46 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
48 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
(continued on next page…)
14
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 15 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
0 10 V Dimming Panels: Product Selection Guides (continued)
120 V~ or 277 V~ Main Lug Panels (1 breaker per module)
Product
Selection Guide
4
Quantity of Switching Circuits
Quantity of 0 –10 V
Dimming Circuits
4 8 12 16 20 24 28 32 36 40 44 48
2 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
4
2705
(24 in)
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
6 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
8 N/A
2705
(24 in)
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
10 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
12 N/A N/A
2705
(59 in)
N/A N/A N/A N/A N/A N/A N/A N/A N/A
14 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
16 N/A N/A N/A
2705
(59 in)
N/A N/A N/A N/A N/A N/A N/A N/A
18 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
20 N/A N/A N/A N/A
2705
(59 in)
N/A N/A N/A N/A N/A N/A N/A
22 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
24 N/A N/A N/A N/A N/A
2705
(59 in)
N/A N/A N/A N/A N/A N/A
26 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
28 N/A N/A N/A N/A N/A N/A
2705
(63 in)
N/A N/A N/A N/A N/A
30 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
32 N/A N/A N/A N/A N/A N/A N/A
2705
(63 in)
N/A N/A N/A N/A
34 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
36 N/A N/A N/A N/A N/A N/A N/A N/A
2705
(63 in)
N/A N/A N/A
38 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
40 N/A N/A N/A N/A N/A N/A N/A N/A N/A
2705
(63 in)
N/A N/A
42 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
44 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
2705
(63 in)
N/A
46 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
48 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
2705
(63 in)
15
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 16 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
0 10 V Dimming Panels: Dimensions
All dimensions shown as: in (mm)
Mini-Size Panels 24 in (609 mm)
Top View
14.38
(365)
Bottom View
4.09
(104)
Right Side View
4.15 (10 5)
0.15 (4)
Left Side View
24.00
(610)
Front View
15.88
(403)
21.50
(546)
24.50
(622)
2.21 (56)
1.34 (34)
8.00
(203)
Cover
15.13
(384)
10.75
(273)
(continued on next page…)
16
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 17 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
0 10 V Dimming Panels: Dimensions (continued)
All dimensions shown as: in (mm)
Standard-Size Panels 59 in (1498 mm)
Top View
14.38
(365)
Bottom View
4.15
(105)
Right Side View
4.21 (107)
0.15 (4)
Left Side View
59.00
(1499)
Front View
15.88
(403)
41.75
(1060)
59.50
(1511)
2.43 (62)
2.69 (68)
8.00
(203)
Cover
15.13
(394)
11.0 0
(279)
(continued on next page…)
17
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 18 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
0 10 V Dimming Panels: Dimensions (continued)
All dimensions shown as: in (mm)
Large-Size Panels 63 in (1600 mm)
Top View
22.00
(559)
Bottom View
6.10
(155)
Right Side View
6.30 (160)
0.15 (4)
Left Side View
63.00
(1600)
Front View
23.50
(597)
22.75
(578)
45.00
(114 3)
63.50
(1613)
2.50 (64)
3.34 (85)
18.50
(470)
Cover
(continued on next page…)
18
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 19 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
0 10 V Dimming Panels: Dimensions (continued)
All dimensions shown as: in (mm)
Extra-Large-Size Panels 82 in (2082 mm)
Top View
22.00
(559)
Right Side View
6.30 (160)
0.15 (4)
Left Side View
82.00
(2083)
Bottom View
6.10
(155)
22.75
(578)
Front View
23.50
(597)
18.50
(470)
68.00
(1727)
82.50
(2096)
2.50 (64)
3.34 (85)
Cover
19
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 20 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
0 10 V Dimming Panels: Mounting
Mini-Size Panels
Surface- or recess-mount indoors.
• Consult Dimensions page for dimensions, conduit
knockouts, and mounting holes and hardware.
Mount only where ambient temperature is 32°F to
104°F (0°C to 40°C).
Mount panel where audible noise is acceptable
(internal relays click).
Mount panel so line (mains) voltage wiring is at least
6ft (1.8m) from sound or electronic equipment and
wiring.
Mount panel within 7° of true vertical.
Maximum Feed and Wire Sizes
Consult wiring tables on pages 8 and 10: Mini-Size
Panels.
Surface-Mounting
Surface-mounting keyholes accept 1/4in (6mm)
mounting bolts. This size is recommended.
Recess-Mounting
Mount to wall stud by screwing through slots in
corners of panel.
Mount panel between flush and 1/8in (3mm) below
finished wall surface.
Front View Side View
Feed wiring and
switch legs to loads
Feed wiring and
switch legs to loads
IEC PELV/NEC®
Class 2 wiring
0–10 V-
load wiring
Terminal blocks for
switch legs to
loads
Switch legs
to loads
Front View Side View
Feed wiring and
switch legs to loads
Feed wiring and
switch legs to loads
IEC PELV/NEC®
Class 2 wiring
0–10 V-
load wiring
Terminal blocks for
switch legs to
loads
Switch legs
to loads
(continued on next page…)
20
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 21 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Standard-Size Feed-Through Panels (without
branch circuit breakers)
Surface- or recess-mount indoors.
• Consult Dimensions page for dimensions, conduit
knockouts, and mounting holes and hardware.
Mount only where ambient temperature is 32°F to
104°F (0°C to 40°C).
Standard-Size 0 10 V panel weighs 80lb (37kg).
Reinforce wall structure for weight and local codes.
Mount panel where audible noise is acceptable
(internal relays click).
Mount panel so line (mains) voltage wiring is at least
6ft (1.8m) from sound or electronic equipment and
wiring.
Mount panel within 7° of true vertical.
Maximum Feed and Wire Sizes
Consult wiring table on page 8: Standard-Size
Panels.
Surface-Mounting
Surface-mounting keyholes accept 1/4in (6mm)
mounting bolts. This size is recommended.
Recess-Mounting
Mount to wall stud by screwing through slots in
corners of panel.
Mount panel between flush and 1/8in (3mm) below
finished wall surface.
Front View Side View
Feed wiring
and switch
legs to loads
Feed and switch
leg wiring
Feed wiring
and switch legs
IEC PELV/NEC®
Class 2 wiring
0–10 V-
load wiring
0–10 V-
modules
Distribution
panel
Terminal blocks
for switch legs to
loads
Front View Side View
Feed wiring
and switch
legs to loads
Feed wiring
and switch legs
IEC PELV/NEC®
Class 2 wiring
0–10 V-
load wiring
0–10 V-
modules
Terminal blocks
for switch legs to
loads
(continued on next page…)
0 10 V Dimming Panels: Mounting (continued)
21
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 22 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Standard-Size Main Lug Panels (with branch
circuit breakers)
Surface- or recess-mount indoors.
• Consult Dimensions page for dimensions, conduit
knockouts, and mounting holes and hardware.
Mount only where ambient temperature is 32°F to
104°F (0°C to 40°C).
Standard-Size 0 10 V panel weighs 80lb (37kg).
Reinforce wall structure for weight and local codes.
Mount panel where audible noise is acceptable
(internal relays click).
Mount panel so line (mains) voltage wiring is at least
6ft (1.8m) from sound or electronic equipment and
wiring.
Mount panel within 7° of true vertical.
Maximum Feed and Wire Sizes
Consult wiring tables on pages 9 and 10:
Standard-Size Panels.
Surface-Mounting
Surface-mounting keyholes accept 1/4in (6mm)
mounting bolts. This size is recommended.
Recess-Mounting
Mount to wall stud by screwing through slots in
corners of panel.
Mount panel between flush and 1/8in (3mm) below
finished wall surface.
OK
r
Front View Side View
Preferred
feed wiring
Main lugs
Neutral
buses
Feed wiring
and switch
legs to loads
IEC PELV/NEC®
Class 2 wiring
0–10 V-
load wiring
0–10 V-
modules
Terminal blocks
for switch legs
to loads
OK
r
Front View Side View
Preferred
feed wiring
Main lugs
Neutral
buses
Feed wiring
and switch
legs to loads
IEC PELV/NEC®
Class 2 wiring
0–10 V-
load wiring
0–10 V-
modules
Terminal blocks
for switch legs
to loads
(continued on next page…)
0 10 V Dimming Panels: Mounting (continued)
22
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 23 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Large- and Extra-Large-Size Panels
Surface-mount indoors.
• Consult Dimensions page for dimensions, conduit
knockouts, and mounting holes and hardware.
Mount only where ambient temperature is 32°F to
104°F (0°C to 40°C).
Large 0 10 V panel weighs 135lb (61.3kg). Reinforce
wall structure for weight and local codes.
Extra-Large 0 10 V panel weighs 200lb (90.7kg).
Reinforce wall structure for weight and local codes.
Mount Panel where audible noise is acceptable
(Internal relays click).
Mount Panel so line (mains) voltage wiring is at least
6ft (1.8m) from sound or electronic equipment and
wiring.
Mount Panel within 7° of true vertical.
• Lutron
® recommends 1/4in (6mm) mounting bolts.
Maximum Feed and Wire Sizes
Consult wiring tables on pages 8, 9, and 10:
Large-Size Panels and Extra-Large-Size Panels.
1 2 3 4 5
Front View Side View
Feed wiring
and switch
legs to loads
Switch legs
to loads
Preferred
feed wiring
Main lugs
Neutral
busses
IEC PELV/NEC®
Class 2 wiring
0–10 V-
load wiring
0–10 V-
modules
Terminal blocks
for switch legs
to loads
0 10 V Dimming Panels: Mounting (continued)
23
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 24 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
0 10 V Dimming Panels: Wiring
Feed-Through Panels (without branch circuit
breakers)
Use a trough when the 0 10 V panel is far away from
the distribution panel. Splice neutrals in trough.
Wire the 0 10 V panel similarly to a lighting distribution
panel. Run feed and load wiring.
Use the 0 10 V panel to provide temporary lighting by
leaving the bypass jumpers in place and using branch
circuit breakers to switch lights on and off.
Wire Sizes
Power Feed (Line/Hot): 14AWG to 10AWG (2.5mm
2
to 4.0mm
2
)
Switched-Line Hot: 14AWG to 10AWG (2.5mm
2
to
4.0mm
2
)
Control Circuit
Supplies power for internal operation.
• Lutron
® recommends a dedicated 120 or 277V~,
20A, 1-phase, 2-wire feed to power the control circuit
in the panel.
If control circuit is tapped from a circuit that powers a
relay in the panel, it draws a maximum of 1.5A toward
the total load for that circuit.
SH
SH
SH
SH
H
H
H
H
N
GND
GND
N
277H
120H
I
O
I
O
IEC PELV/NEC®
Class2 wiring
entrance
277 V~
Control
Feed
Distribution
Panel
0–10 V-
or
LED Load
+
Terminal Block
010 V Module
Power Feed (Line/Hot)
Switched Line/Hot
Load Neutral
Ground
277 V~
Neutral
Neutral
Ground
120 V~
OR
(continued on next page…)
Neutral must be provided for control power to module.
Hot 1 of each switching module must be powered. This hot
circuit also provides control power to module.
Bypass Jumpers Do Not Remove
Line/Hot Jumper
Ties all line/hot terminals together so that a single 20 A feed
can be used per module.
Can be removed if multiple 20 A feeds per module are
required for higher capacity loads.
120 V~
Control
Feed
24
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 25 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
0 10 V Dimming Panels: Wiring (continued)
Main Lug Panels (with branch circuit breakers:
4breakers per module, 1 breaker per switching
circuit)
Wire the 0 10 V panel similarly to a lighting distribution
panel. Run feed and load wiring.
Use the 0 10 V panel to provide temporary lighting by
leaving the bypass jumpers in place and using branch
circuit breakers to switch lights on and off.
Wire Sizes
Power Feed (Line/Hot):
100 –127 V~: 4 AWG (25 mm
2
) to 250 kcmil (mcm)
(120 mm
2
)
277 V~: 4 AWG (25 mm
2
) to 300 kcmil (mcm)
(150mm
2
)
Switched Line/Hot: 14 AWG to 10 AWG (2.5 mm
2
to
4.0 mm
2
)
Load Neutral: 14 AWG to 10 AWG (2.5 mm
2
to
4.0mm
2
)
Control Circuit
Supplies power for internal operation.
For 120 V~ and 277 V~ panels that have
28 or fewer switch legs, a dedicated 20 A
breaker is provided to power the control
circuit.
For 120 V~ and 277 V~ panels that have
32 or more switch legs, the control circuit
is powered from circuit breaker #1 which
also powers relay #1. The control circuit
could draw a maximum of 1.5A
toward the total load capacity for
that circuit.
H
SH
H
SH
SH
H
SH
H
H
N
0–10 V-
or
LED Load
Bypass Jumpers Do Not Remove
Terminal Block
Main Lugs
Neutral Bus
Power Feed (Line/Hot)
Neutral Bus
Branch Circuit Breakers
for temporary lighting
Switched Line/Hot
Load Neutral
010 V Module
+
(continued on next page…)
25
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 26 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
0 10 V Dimming Panels: Wiring (continued)
Main Lug Panels (with branch circuit breakers:
1breaker per module)
Wire the 0 10 V panel similarly to a lighting distribution
panel. Run feed and load wiring.
Use the 0 10 V panel to provide temporary lighting by
leaving the bypass jumpers in place and using branch
circuit breakers to switch lights on and off.
Wire Sizes
Power Feed (Line/Hot):
Mini-size panel: 14 AWG to 8 AWG (2.5 mm
2
to
8.5mm
2
)
Standard-size panel: 14 AWG to 2/0 AWG (2.5 mm
2
to 70mm
2
)
Large-size panel: 14 AWG to 2/0 AWG (2.5 mm
2
to
70mm
2
)
Switched Line/Hot: 14 AWG to 10 AWG (2.5 mm
2
to
4.0 mm
2
)
Load Neutral: 14 AWG to 10 AWG (2.5 mm
2
to
4.0mm
2
)
Control Circuit
A dedicated 20 A breaker is provided
to power the control circuit.
Supplies power for internal operation.
SH
SH
SH
SH
H
H
H
H
H
N
N
N
N
N
0–10 V-
or
LED Load
Bypass Jumper Do Not Remove
Terminal Block
Power Feed (Line/Hot)
Neutral Feed
Switched Line/Hot
Load Neutral
010 V Module
+
26
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 27 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
0 10 V Dimming Panels: Low-Voltage IEC PELV / NEC® Class 2 Wiring (All Models)
System communications use Low-Voltage IEC PELV/NEC® Class 2 wiring.
Wiring must be daisy-chained.
Wiring must run separately from line (mains) voltage.
GRAFIK Eye® 4000 System
IEC PELV/NEC® Class 2 wiring link requires:
Two 12 AWG (4.0 mm
2
) conductors for control power.
One twisted, shielded pair of 18 AWG (0.75 mm
2
) for data link.
One 18 AWG (0.75 mm
2
) conductor for emergency (essential) sense line, from panel to panel.
Total length of control link may be no more than 2000 ft (610 m).
Approved low-voltage cable is available from Lutron
®*, Belden, and Liberty. These are approved with 22 AWG
(0.34mm
2
) data link wires.
GRAFIK 5000TM/GRAFIK 6000®/GRAFIK 7000TM Systems
IEC PELV/NEC® Class 2 wiring link requires:
Two 12 AWG (4.0 mm
2
) conductors for control power.
One twisted, shielded pair of 18 AWG (0.75 mm
2
) for data link.
One 18 AWG (0.75 mm
2
) conductor for emergency (essential) sense line, from panel to panel.
Total length of control link may be no more than 2000 ft (600 m).
If MUX-RPTR interface and GRX-CBL-46L cable* is used, length may be up to 4000 ft (1200 m).
* GRX-CBL-46L – IEC PELV/NEC® Class 2 wiring cable is available from Lutron® and contains:
Two 12 AWG (4.0 mm
2
) conductors for control power.
One twisted, shielded pair of 22 AWG (0.34 mm
2
) for data link.
One 18 AWG (0.75 mm
2
) conductor for emergency (essential) sense line.
0–10 V- Panel
Control Unit
Control Interface
Wallstations
0–10 V- Panel
Processor
Panel
Refer to GRAFIK 5000
TM/GRAFIK 6000®/GRAFIK 7000TM Specification
Power Panel Link
Control Unit
Control Interface
Wallstations
27
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 28 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Notes
* Emergency Power: The additional 18 AWG (0.75 mm
2
) wire is a “sense” line from terminal 5 of another panel. This sense line allows an emergency
(essential) lighting panel to “sense” when normal (non-essential) power is lost. If more than one emergency lighting panel needs to sense from a specific
normal panel, a dedicated wire between each pair of normal (non-essential) and emergency (essential) panels may be required.
Shield/Drain: Connect shielding as shown. Do not connect to ground (earth) or circuit selector. Connect the bare drain wires and cut off the outside
shield.
0 10 V Dimming Panels: IEC PELV / NEC® Class 2 Panel-to-Panel Wiring (All Models)
SELECT CIRCUIT
Data A OK Power Data B OK
1234D5
1234D5 C D
Common
Common
+24VFW
Sense
MUX
MUX
Drain
Drain
MUX
MUX
Circuit
1
2
Link
A
Link
B
SELECT CIRCUIT
Data A OK Power Data B OK
1234D5
1234D5 C D
Common
Common
+24VFW
Sense
MUX
MUX
Drain
Drain
MUX
MUX
Circuit
1
2
Link
A
Link
B
C+–D C+–D
Control Wiring
(2) 12 AWG (4.0 mm
2
)
1: Common
2: 24 V-
To
Additional
Power
Panels
0–10 V- Panel 1 0–10 V- Panel 2
To Lighting
Controls or
Processors
To
Stageboard
Receptacle
From
Additional
Panels
(1) 18 AWG (0.75 mm
2
)
5: Sense Line*
Data Link
(1) twisted, shielded pair 18 AWG (0.75 mm
2
)
3: MUX
4: MUX
1
2
3, 4
5
1
2
3, 4
Shield/
Drain
Shield/
Drain
28
0 –10 V Dimming PanelsGRAFIK SystemsTM Power Equipment
369827c 29 10.26.16
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
0 10 V Dimming Panels: IEC PELV / NEC® Class 2 Terminal Connections
Each low-voltage IEC PELV/NEC® Class 2 terminal can accept only two 18 AWG (0.75 mm
2
) wires. Two 12AWG
(4.0mm
2
) conductors will not fit. Connect asshown.
SELECT CIRCUIT
2
1
Data A OK
Power
1234 5D
Common
24VFW
MUX
MUX
Drain
Sense
1234
D
5
Data B OK
B
Comm
Drain
MUX
MUX
C
D
Link
A
Link
C+ D
(4) 12 AWG (4.0 mm