SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Pico Lutron Hospitality Guestroom Solution Wallstations
369705e 2 10.03.19
Specifications
Regulatory
• Design ed for SELV / PELV / NECR Class 2 operation
only
• Not a wireless device
• Meets IEC 801‑2. Tested to withstand 15 kV
electrostatic discharge without damage or memory
loss
• Install according to all applicable national and local
wiring regulations
Mechanical
• Mounts easily in any 1‑column or 2‑column Lutron
Pico faceplate (not included)
Power
• Do not exceed 36 V-
• Operating Voltage: 24–36 V- (SELV / PELV / NECR
Class 2)
• Current Draw: 30 mA maximum
• Consumes 1 Power Draw Unit (PDU) on the QS link
• Powered by the QS link or an external 24 V- supply
System Communications and Capacity
• Low‑voltage type IEC PELV / NECR Class 2 wiring
connects wallstations and other devices on the
QSlink to the Lutron myRoom Guestroom
Control Unit
• Counts as one device and no zones on the QS link
Environment
• Indoor use only, 0 °C to 40 °C (32 °F to 104 °F)
• Relative Humidity: Less than 90% non‑condensing
Wiring
Black = Common (1)
Red = V+ (2)
Purple = MUX (3)
White = MUX (4)
1. Turn OFF the supply breaker
that provides power to the
Lutron myRoom Guestroom
Control Unit to which the Pico Privacy Control is
connected
2. Connect the four (4) conductors to the appropriate
terminals of the Lutron myRoom Guestroom
Control Unit
• Total wire length from Lutron myRoom
Guestroom Control Unit to device must not exceed
610 m (2000 ft)
3. Turn ON the power