SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak® CCO Module Energi TriPak® Series Wireless Lighting Control
369-673b 1 09.05.12
PowPak® CCO Module for Japan
The PowPak® CCO Module is a low-voltage radio frequency
(RF) control that provides a single dry contact closure
output based on input from Pico
® controls and Radio Powr
Savr
occupancy and daylight sensors. It can be powered
by to 24 V ~ or 24 V - for easy connection and integration
into building management, HVAC, VAV, and other 3rd-party
systems.
Communication with RF input devices, such as Pico
®
controls and Radio Powr Savr
sensors, is accomplished
using Lutron Clear Connect
® RF Technology.
Features
•Singlecontactclosureoutputincludingbothnormallyopen
(NO) and normally closed (NC) dry contacts
•Maintainedoutputtype
•Operatesat24V ~ or 24 V -
•ReceiveswirelessinputsfromuptoninePico
® controls, six
Radio Powr Savr
occupancy/vacancy sensors, and one
Radio Powr Savr
daylight sensor
•UtilizesLutronClearConnect
® RF Technology – refer to
model number chart below for frequency band data
•Screwtabsprovidedforsurfacemounting(recommended);
junction box mounting available via 21.7 mm knockout
Model Number Operating Voltage Frequency Band Region
RMP-CCO1-24-JA-B
24 V~ / 24 V-
312.3314.8MHz Japan
NOTE: Contact Lutron for frequency band compatibility for your geographic region if it is not indicated above.
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak® CCO Module Energi TriPak® Series Wireless Lighting Control
369-673b 2 09.05.12
Specifications
Power
•IECPELV/NEC
® Class 2
•Operatingvoltage:24V~ / 24 V-
•Operatingcurrent,nominal:45mA(24V ~)
35 mA (24 V -)
System Communication
•OperatesusingClearConnect
® RF Technology for
reliablewirelesscommunication;refertomodel
number chart on page 1 for frequency band details
•RFrangeis7m
Environment
•Ambientoperatingtemperature:0°Cto55°C
•0%to90%humidity,non-condensing
•Forindooruseonly
Contact Closure Output
•Acceptsinputvoltagesof0-24V ~ / 0-24 V -;see
chart below for load switching capacities
•Providesbothnormallyopen(NO)andnormally
closed (NC) dry contacts
•Maintainedoutputtype
•CCOterminalsaccept0.5 to 1.5 mm
2
(20 to 16 AWG)
solid or stranded wire
•Outputislatching
•TheCCOisnotratedtocontrolunclamped,
inductive loads. Inductive loads include, but are not
limited to, relays, solenoids, and motors. To control
these types of equipment, a flyback diode must be
used (DC voltages only). See diagram below. For
more information, please see Application Note #434
(p/n 048434).
Switching
Voltage
0-24 V-
0-24 V~
24 V-
max.
Inductive
Load
CCO
Output
NO
NC
COM
Flyback
Diode
(required for
inductive
loads)
Resistive
Load
1.0 A
0.5 A
R
+
-
Switching
Voltage
0-24 V-
0-24 V~
24 V-
max.
Inductive
Load
CCO
Output
NO
NC
COM
Flyback
Diode
(required for
inductive
loads)
Resistive
Load
1.0 A
0.5 A
R
+
-
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak® CCO Module Energi TriPak® Series Wireless Lighting Control
369-673b 3 09.05.12
Test
System Diagram
Wiring Diagram
Radio Powr Savr
Occupancy Sensor (up to 6)
Radio Powr Savr
Daylight Sensor (up to 1)
Pico® Control (up to 9)
To 3rd-Party
Equipment
To power source
COM
NO
NC
To 3rd-Party
Equipment
Black
Contact Closure Output
Switching
Voltage
1.0 A
0.5 A
0-24 V-
0-24 V~
R
Resistive
Load
Supply Voltage
24 V~ /24 V-
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak® CCO Module Energi TriPak® Series Wireless Lighting Control
369-673b 4 09.05.12
Wiring Diagram
NOTE: When wiring CCO output,
use 0.5 to 1.5 mm
2
(20 to 16 AWG)
solid or stranded wire.
To CCO controlled device.
NO
(Normally Open)
NC
(Normally Closed)
COM
(Common)
Supply Voltage
24 V~ /24 V-
NOTE: CCO Module supply wires can be
connected in any polarity.
Mounting screw
(2 Supplied)
Wire Nut
(2 Supplied)
NOTE: The CCO output may be wired using either the NO or NC terminal.
Refer to the Default Operation chart on page 6 for more information
regarding the behavior of the CCO output terminals.
Please use 1.6 mm
2
or 2.0 mm
2
diameter copper wire.
Strip off 10 mm of the insulated coating on the wire and
straighten the wire if it bends.
Shown,
actualsize
1
2
3
10 mm
1
2
3
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak® CCO Module Energi TriPak® Series Wireless Lighting Control
369-673b 5 09.05.12
PowPak® Installation Inside Junction Box
(Dimming Module RMP-ECO32-JA-B shown)
Antenna
BOX ABOX B
In some applications, a PowPak® module can be installed inside a junction box.
A) Remove the label tab by tearing at the perforation.
B) Lift the flexible antenna on the PowPak® module from the cutout on the right side of the antenna trough.
C) Extend the antenna out from the left side of the PowPak® as indicated.
+
-
+
-
+
-
+
-
Remove label tab
at perforations
Lift out
antenna
here
A
B
C
Extend
antenna
here
Mounting within a Junction Box
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak® CCO Module Energi TriPak® Series Wireless Lighting Control
369-673b 6 09.05.12
Dimensions
Dimensionsareshownas:mm
Range Diagram
•ContactLutronrstforapplicationsusingfoil-backedormetallicceilingtiles.
41.7
Mounting Tabs
M3 screws
recommended
79.4
86.9
100.1
31.871.6
All Wireless Transmitters must be installed within
7 m of the PowPak® CCO Module.
Test
Radio Powr Savr
Occupancy Sensor
7 m
Maximum
12 m
10 m
PowPak®
CCO Module
Install in center of room to
maximizeRFcoverage.
Pico®
Wireless
Transmitter
21.7 mm
diameter
6
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak® CCO Module Energi TriPak® Series Wireless Lighting Control
369-673b 7 09.05.12
Default Operation
Transmitting Device Transmitted Command CCO Default Action
Pico
®
Wireless Control
On NO = Close, NC = Open
Off NO = Open, NC = Close
Raise No Action
Lower No Action
Preset NO = Close, NC = Open
Radio Powr Savr
Occupancy Sensor
Occupied NO = Close, NC = Open
Unoccupied NO = Open, NC = Close
Radio Powr Savr
Vacancy Sensor
Occupied No Action
Unoccupied NO = Open, NC = Close
Radio Powr Savr
Daylight Sensor
Ambient Light Below
Target Level
NO = Close, NC = Open
Ambient Light Above
Target Level
NO = Open, NC = Close
7