SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
HomeWorks QS LQSE-4M-120-D Motor Control Power Module
3691107b 2 02.28.2019
Specifications
Power
• 120 V~ 50/60 Hz
• 16 A maximum total input current
• At standby (no motors being driven), power is
less than 1 W
• BTU / hour when fully loaded: 5
• Lightning strike protection meets ANSI/IEEE standard
62.31-1980. Can withstand voltage surges of up to
6000 V~ and current surges of up to 3000 A
• Contact Lutron for ungrounded delta feed applications
Output Capacity
• 5 A maximum motor load per zone
(not for lighting control)
• 16 A maximum total motor load per unit
• Each zone supports only one motor; do not wire motors
in parallel
• Raise and Lower outputs for each zone are mechanically
interlocked to prevent simultaneously activating
Raise / Lower outputs
Regulatory Requirements
• Lutron Quality Systems registered to ISO 9001.2015
• cULus Listed
• FCC Compliant
• RoHS Compliant
• NOM Certied
Environment
• Ambient temperature operating range
(outside mounting panel): 32 ºF to 104 ºF
(0 ºC to 40 ºC)
• Calibration point maximum: 131 ºF (55 ºC)
• Surrounding air temperature: T
a
≤ 131 ºF (55 ºC)
• Relative humidity: less than 90% non-condensing
• For indoor use only
Terminals
• Mains Wiring: 14 to 10 AWG (2.5 to 4.0 mm
2
)
5 in-lbs (0.6 N•m)
• Zone Wiring: 14 to 10 AWG (2.5 to 4.0 mm
2
)
5 in-lbs (0.6 N•m)
• QS Link Wiring: See Wiring: QS Link section on page 5
Mounting
• Use an IP20 (minimum) rated consumer panel or
breaker panel with integrated DIN rail
• Width = 9 DIN units (6.4 in / 161.7 mm)
QS Link Limits
• A QS link can have up to 100 zones (outputs) and
100 devices
• Each motor control power module counts as 4 zones
(outputs) and 1 device on the QS link
Normal Mode Operation
• Zone Select button selects the desired zone; raise /
lower buttons control the selected zone
• Supports Open, Close, Stop, and Unaffected presets
only; all other presets are ignored
• Only supports load type: motor
• Does not support discrete shade levels
• Does not support motor speed control
Configurable Parameters
• Minimum On time (also called Jog Time): The
minimum time for which the Raise/Lower relay will be
turned on
Congurable from 80 ms to 3520 ms in 80 ms
increments
Default: 80 ms
• Interlock delay: The time both relays are de-energized
while switching from Raise to Lower, or from Lower to
Raise
Congurable to 320 ms, 560 ms, or 960 ms
Default: 560 ms
• Maximum On time (also called Travel Time or Time
to Off): after this time, the relay is turned off as a
precaution
Congurable from 10 seconds to 450 seconds in
10 second increments
Default: 80 seconds