SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive
PowPak Single Zone Control Module with DALI® Wireless Lighting Control
3691104c 1 09.24.19
PowPak Single Zone Control Module
with DALI
The PowPak Single Zone Control Module with DALI® is a
radio frequency (RF) control that operates 14 or 1–32*DALI®
LED drivers or fluorescent ballasts based on input from Pico
remote controls and RadioPowr Savr sensors. The control
module is ideal for small areas (e.g.,classrooms, conference
rooms, private offices).
Communication with RF input devices (e.g., Pico remote
controls, Radio Powr Savr sensors) is accomplished by using
Lutron Clear Connect RF technology.
These products are also compatible with the Vive hub which
enables a simple setup process using the free Lutron Vive
app (available for download from the App Store or Google
PlayR online marketplace) or by using web-based software
with any Wi-FiR enabled iOSR or AndroidR compatible device.
It also enables control and monitoring of all Vive devices. The
Vive hub can be added at any time. System reprogramming
will be required. For a complete list of features supported with
the Vive hub, see specification submittal 3691044 at
www.lutron.com
Features
Controls 14 or 1–32DALI® fixtures in a single zone
(see Models see below).
Configurable high- and low-end trim.
Receives wireless inputs from up to 10 Pico remote controls,
10 Radio Powr Savr occupancy / vacancy sensors, and 1
Radio Powr Savr daylight sensor.
Utilizes Lutron Clear Connect RF technology; refer to model
number chart below for frequency band data.
Mounts through a 20 mm knockout.
DALI® Compatibility
The Lutron PowPak Single Zone Control Module with DALI® is DALI-2® certified by the Digital Illumination Interface Alliance
(DiiA)®. In order to ensure compatibility with Lutron DALI® controllers, the connected DALI® LED drivers and fluorescent
ballasts must be DALI-2® certified and marked. In addition to compatibility, it is important to select high-quality and
high-performance LED drivers and fluorescent ballasts. DALI-2® certified devices are readily available from many
manufacturers and are tested for compatibility with the standard. For a complete list of available DALI-2® certified devices,
see the DiiA® website at https://www.digitalilluminationinterface.org/products. DALI® devices that are not listed on the DiiA®
website and are not marked DALI-2® cannot be considered DALI-2® certified.
The DALI® version-1 standard does not ensure compatibility. To apply the original DALI® version-1 mark on LED drivers and
fluorescent ballasts, no verification of the test results was required, and manufacturers could self-declare compliance and
apply the DALI® mark. If you would like to use an LED driver or fluorescent ballast that is not DALI-2® certified but carries a
DALI® version-1 logo, Lutron recommends that these devices be tested to ensure compatibility. Lutron is able to perform
this testing on request. Samples of the drivers and light engines must be submitted to Lutron and the expected turnaround
time is 6 to 8 weeks after the drivers are received. Fees for testing may apply. Lutron recommends that this testing be
performed before the fixtures and lighting controls are purchased and installed. Contact your Lutron sales representative
for more information.
Note: Contact Lutron for frequency band compatibility for your geographic region if it is not indicated above.
* See Models listed in chart.
Models
Model Number Description Region Operating Voltage Frequency Band
RMKS-DAL32-SZ 32 device controller U.K., Europe 220 –240 V~ 868.125 – 869.850 MHz
RMKS-DAL4-SZ 4 device controller U.K., Europe 220 –240 V~ 868.125 – 869.850 MHz
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive
PowPak Single Zone Control Module with DALI® Wireless Lighting Control
3691104c 2 09.24.19
Specifications
Regulatory Approvals
• CE
IEC 60669-2-5
• DALI-2
® Certified
Power
220 –240V~ 50 / 60Hz, max. current 50 mA
Other Power Specifications
Standby power:
220–240 V~ <0.5 W
System Communication
Operates using Clear Connect RF technology for
reliable wireless communication.
Wireless sensors and controls must be located within
9m of the associated control module.
Mounting*
This device can be installed on a fixture / troffer,
junction box, or marshalling box using the conduit
nut or with mounting screws. The device must NOT
be mounted inside a fixture / troffer or other metallic
enclosure.
Refer to the installation instructions and consult local
and national electric codes for proper installation.
The PowPak Control Module needs to be accessible
for some programming steps. Record where it is
mounted so that it can be easily located later.
Metal Ceiling Mounting
Metal ceiling grids must have a > 3 mm gap of non-
metal material which extends the entire length of
the tile on at least one edge. This is often achieved
by foam spacers that are used to prevent tile-to-tile
rattling.
Metal ceiling grids which are continuous (with no
gap) or those that are interlocked, must have a total
surface area that is less than 81m
2
for each section.
The overall space can be larger as long as there are
non-metal sections bordering or intersecting the
metal sections.
Environment
Ambient operating temperature: 0°C to 40°C
0% to 90% humidity, non-condensing.
For indoor use only.
All drivers and ballasts used with Vive wireless
controls must comply with EN 55015 / CISPR 15.
Key Design Features
LED status indicator shows load status and provides
programming feedback.
Configurable high-end and low-end trim.
Power failure memory: If power is interrupted,
connected loads will return to the previous level prior
to interruption.
Continued on next page...
* For more guidelines and installation best practices, refer to Lutron Application Note
#620 (P/N 048620) at www.lutron.com
NOTICE: Improper installation can result in
degraded wireless communication and/or
intermittent or sustained communication failures,
and will not be covered under warranty.
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive
PowPak Single Zone Control Module with DALI® Wireless Lighting Control
3691104c 3 09.24.19
Specifications (continued)
DALI® Link
18 V-
Controls 1–4 or 1–32 DALI
® ballasts or drivers (see
Models on page 1)
Multiple drivers / ballasts connected to a Control
Module will always work together as a single zone.
Guaranteed Supply Current
8 mA (RMKS-DAL4-SZ)
64 mA (RMKS-DAL32-SZ)
Maximum Supply Current: 250 mA
• DALI
® Digital Link carries basic isolation from line
voltage wires.
The PowPak Control Module is a single master
controller and therefore no other controllers may exist
on the same DALI
® bus.
Ensure that there is no greater than a 2 V~ drop
between the Control Module and the end of the
DALI
® Bus.
Consult all national and local electrical codes for
separation requirements.
Wire Gauge Total DALI®-compliant Bus
Wire Length
1.5 mm
2
(14 AWG) 300 m
0.75 mm
2
(18 AWG) 150 m
0.50 mm
2
(20 AWG) 100 m
Default Operation
Associated wireless input devices control all
connected fixtures together.
Occupancy Sensors:
Occupied:100%; Unoccupied:0% (OFF)
Pico Remote Controls:
On:100%; Favorite Level:50%; Off:0% (OFF)
Daylight Sensor: Decreases electric light in response
to additional available daylight
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive
PowPak Single Zone Control Module with DALI® Wireless Lighting Control
3691104c 4 09.24.19
Advanced Configurations
Pico Remote Controls
Up to 10 Pico remote controls.
Favorite levels can be set for each Pico remote control.
Radio Powr Savr Daylight Sensor
The Radio Powr Savr daylight sensor will affect all
connected LED drivers and ballasts equally.
For multiple rows of daylighting, a separate PowPak
Control Module must be used for each daylighting
row.
Minimum Light Level Setting (optional)
Certain applications, such as hallways, may require
that the lights never turn off. For these areas, select
the minimum light level option and the load will lower
to programed low-end level. Default operation lowers
to OFF.
High- and Low-End Trim
High-end and low-end trim affect all connected fixtures
equally, and can be configured from the PowPak
Control Module.
Adjustable low-end trim (0.1% –45%)*. Trimmable
low-end can ensure a stable light level. Some fixtures
will flicker or drop out if trimmed too low.
The maximum light output of connected fixtures can
be decreased down to 55% for energy savings in over-
lit spaces.
Note: The perceived light output of low-end trim may
vary between fixture manufacturers and model
numbers. For best results, do not mix different drivers
or ballasts on the same DALI
® circuit.
Radio Powr Savr Occupancy Sensors
Radio Powr Savr occupancy and vacancy sensors
control all connected drivers or ballasts.
Pico remote controls can be used to adjust the
occupied levels of fixtures that they control from
0.1%* to 100% (of output signal) or can make them
unaffected by occupancy events.
Vacancy events (area becomes unoccupied) turn all
driver or ballast models off or to minimum light level.
* Low-end depends on the minimum output of the connected
drivers or ballasts.
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive
PowPak Single Zone Control Module with DALI® Wireless Lighting Control
3691104c 5 09.24.19
System Diagram
Wiring Schematic
Radio Powr Savr occupancy sensor (up to 10)
Radio Powr Savr daylight sensor (up to 1)
Pico remote control (up to 10)
LED Drivers Fluorescent Ballasts
DALI
® control
* Can be installed in a junction box or marshalling box. Please follow all local and
national electric codes for proper installation methods.
Line / Hot
Junction Box*
Neutral
DA+
DA−
DALI® to LED Drivers / Fluorescent Ballasts
20 mm knockout opening
Adaptor
Note: Multiple drivers / ballasts connected to a PowPak
Control Module will always work together as a single zone.
Note: The perceived light output of low-end trim may vary
between fixture manufacturers and model numbers. For
best results, do not mix different drivers or ballasts on the
same DALI
® circuit.
To additional fixtures
(up to 4 or up to
32DALI® ballasts or
drivers – see Models on
page1)
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive
PowPak Single Zone Control Module with DALI® Wireless Lighting Control
3691104c 6 09.24.19
Dimensions
Dimensions are shown as: mm
87
72
100
Wireless Range Diagram
9 m
maximum
Radio Powr Savr
occupancy
sensor
Pico
remote
control
PowPak
Control Module
Install in center of room
to maximize RF coverage.
PowPak
Control
Module
Lutron, )Lutron, PowPak, Radio Powr Savr, Clear Connect, Vive, and Pico
are trademarks or registered trademarks of Lutron Electronics Co., Inc. in the
US and/or other countries.
All other product names, logos, and brands are property of their respective
owners.
App Store is a service mark of Apple Inc.
Note: Wireless sensors and controls must be located within
9m of the associated control module.
Metal ceiling grids must have a > 3mm gap of non-metal
material which extends the entire length of the tile on at least
one edge. This is often achieved by foam spacers that are
used to prevent tile-to-tile rattling.
Metal ceiling grids which are continuous (with no gap) or
those that are interlocked, must have a total surface area that
is less than 81 m
2
for each section. The overall space can be
larger as long as there are non-metal sections bordering or
intersecting the metal sections.
32
20 mm knockout opening
112
Adaptor
6