Installation Overview
Sensor Setup
• SensorsetupisavailableasaservicebyLutron.Formore
information see the Sensor Layout and Tuning service
document(LutronP/N3601235).
Sensor Placement
• Todetectmotion,thesensorrequiresline-of-sightof
room occupants. The sensor must have an unobstructed
viewoftheroom.DONOTmountbehindorneartall
cabinets, shelves, hanging fixtures, ceiling fans, etc. The
sensorcannotseethroughglassobjectssuchaspatio-or
shower doors.
• Hotobjectsandmovingaircurrentscanaffectthe
performance of the sensor. To ensure proper operation,
the sensor should be mounted at least 4 ft (1.2 m) away
fromHVACventsandlightbulbsthatarebelowtheceiling
line.
• Theperformanceofthesensordependsonatemperature
differential between the ambient room temperature and
thatofroomoccupants.Warmerroomsmayreducethe
ability of the sensor to detect occupants.
• DevicesemittingRadioFrequency(RF)energycanaffect
the performance of sensors. To ensure proper operation,
sensors should be mounted at least 4 ft (1.2 m) away from
devices that emit radio waves (e.g., microwave ovens,
wireless routers or other wireless devices).
• Foradditionalinformationonplacingsensors,pleasesee
theOccupancy/VacancySensorDesignandApplication
Guide(P/N368-3197)locatedatwww.lutron.com.
Mounting
Temporary mounting is optional to test sensor coverage
and wireless communication before permanently installing
the sensor.
Drop Ceiling (Compressed Fiber Ceiling Tile)
The mounting wire is provided for both temporary and
permanent mounting of the sensor to ceiling tiles. It is
designed to allow temporary mounting, testing, and
repositioning (if necessary) of the sensor without
damaging a ceiling tile. Once the final position of the
sensor has been chosen, the mounting wire should be
twisted together to permanently secure the sensor in
place.
Solid Ceiling (Drywall, Plaster, Concrete, or
Wood)
• Temporarymounting:Ten(10)temporarymountingstrips
canbepurchasedinthekit,L-CMDPIRKIT,fortemporarily
mounting and testing the sensor.
• Permanentmounting:Screwsandanchors(fordrywallor
plaster) provided to mount the sensor.
Recess-Mount
• Donotrecess-mountsensorinametalsurface.
• Recess-mountingringrequiresanopeningof3in(76mm)
in diameter.
• Recess-mountingringsecuresinternallytoceiling.Sensor
twists into the recess mounting ring and sits flush with
ceiling (see image below).
• Recess-mountingringpurchasedasaseparatekit:
L-CRMK-WH.