Energi Savr Node T-Series Digital Fixture Controller
3691096d 4 01.21.19
Specifications (continued)
Occupancy Sensors
•UseLutronLOSseriesofwiredoccupancysensorsin
occupancy mode to control one or more areas.
•UseLutronoccupancysensorsinvacancymode
to automatically turn the lights off in an area after it
becomes vacant.
•UseLutronoccupancysensorstoautomaticallyturn
the lights on in area when it becomes occupied and
to automatically turn the lights off in an area after it
becomes vacant.
•Eachofthefouroccupancyinputscanpowerone
Lutron occupancy sensor.
•UptofouradditionalLutronWiredOccupancy
SensorsortenadditionalRadioPowrSavr
Occupancy/VacancySensorscanbeassignedper
QS Sensor Module (QSM) on the QS link.
seeTouch QS Controls
•RefertoseeTouchQSSpecSubmittalforfurther
information.
•CongurableseeTouchQSwallstations,refertothe
QSWallstationProgrammingGuideforconguration
options
IR Controls
•UseLutronIRreceiversorwiredPicokeypadsfor
personalcontrolofindividuallightingzones.
•FourIRdevicescanconnectdirectlytotheT-Series
Energi Savr Node unit.
Daylight Sensors
•Lutrondaylightsensorsallowdaylightharvestingwith
programmable effect on light output.
•Fourdaylightsensorscanbeconnecteddirectlytothe
T-Series Energi Savr Node unit.
•UseLutronEC-DIR-WHsensorstocontroloneor
more daylight rows.
•Alternatively,uptofouradditionalLutronWired
DaylightSensorsortenadditionalRadioPowrSavr
Daylight Sensors can be assigned per QSM on the
QS link.
Contact Closure Input (CCI)
•Inputsmustbedrycontactclosure,solidstate,open
collector,oractive-low(NPN)/activehigh(PNP)
output.
–OpencollectorNPNoractive-lowon-statevoltage
mustbelessthan2Vandsink3.0mA.
–OpencollectorPNPoractive-highon-statevoltage
mustbegreaterthan12Vandsource3.0mA.
– Opencircuitvoltage:24Vmaximum.
– Off-stateleakagecurrentmustbelessthan100μA.
– Acceptsmaintainedinputsandmomentaryinputs
with40msecminimumpulsetimes
•Congurablefornormallyopen(NO)ornormally
closed (NC) operation.
•Inputismiswire-protectedupto36V-.
•FunctionalitydenedbyQuantumsystem
programming.
Emergency Contact Closure Input
•Bydefault,contactclosureinputfromLutron
EmergencyLightingInterface(LUT-ELI-3PH),security,
orrealarmsystemsturnsallzonesontofulloutput
when emergency state is detected.
•Emergencycontactclosureinputisnormallyclosed
(NC). The T-Series Energi Savr Node unit is shipped
withajumperpre-installed.
•Responseofeachzoneiscongurable.
•Attacheddevices,bydefault,willgotomaximum
output and ignore control inputs.
•Nooperationswillbealloweduntilemergencysignal
is cleared.
•Inputsmustbedrycontactclosure,solidstate,open
collector,oractive-low(NPN)/activehigh(PNP)output.
–OpencollectorNPNoractive-lowon-statevoltage
mustbelessthan2Vandsink3.0mA.
–OpencollectorPNPoractive-highon-statevoltage
mustbegreaterthan12Vandsource3.0mA.
– Opencircuitvoltage:24Vmaximum.
– Off-stateleakagecurrentmustbelessthan100μA.
– Acceptsmaintainedinputsandmomentaryinputs
with40msecminimumpulsetimes
•Inputismiswire-protectedupto36V-.
•EmergencyCCIcannotcontrolother
Energi Savr Node units.
•SeeApplicationNote#106,“EmergencyLighting”at
www.lutron.com for more details.