SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node T-Series Digital Fixture Controller
3691096d 1 01.21.19
T-Series Energi Savr Node Unit for
Quantum
The Energi Savr Node family is a group of intelligent,
modular products for the control of lighting loads. This
document describes the T-Series Energi Savr Node for
digital addressable loads. It provides T-Series digital link
power and control for two independent T-Series digital
links with up to 32 Lutron T-Series LED drivers on each
link to create a smoothly integrated tunable-white
solution for both color temperature (CCT) control and
light intensity control. The T-Series Energi Savr Node unit
also provides direct connections and power for the
following Lutron devices in a Quantum system:
•Occupancysensors
•Daylightsensors
•IRreceivers
•QSdevices
Model Number
•QSN-TW
Features
•Supports32LutronT-SeriesLEDdriversperdigitallink,
64 Lutron T-Series LED drivers per unit.
•Supports0.1%dimmingLEDdrivers.SeeT-SeriesLED
driver spec for more details.
•Forbesttunable-whiteperformance,operateat1%or
higher. See T-Series LED driver spec for more details.
•Providesintuitive,perceivedlinearcontrolofbothcolor
and intensity.
•IncludesQScontrollinkforseamlessintegrationoflights
in a Quantum system.
•Providescommunicationpowerforupto2loopsof
T-Seriesdigitallyaddressableloads(upto250mAper
loop).
•EachT-Seriesdigitallinkcancontrolamaximumof
16zones.
•Powerfailurememoryretainscontrolunitprogramming
in the event of a power loss.
•Fouroccupancysensorinputsforautomatedcontrolof
lights.
2 T-Series Digital Links
Enlaces digital
l
Buses numérique
Capacity
l
Capacidad
l
Capacité :
18 V- 250 mA per link | por enlace | par bus
QSN-TW
120
277 V~
50
/
60 Hz 500 mA
T-Series
Coopersburg, PA 18036, U.S.A.
saving energy since 1961
Energi Savr Node
IEC PELV
/
NEC
®
Class 2
Input Groups | Grupos de entrada
Groupes d’entreés :
20 V- 4 X 65 mA
QS Link | Enlace | Liaison :
24 V- 1 A
32 T-Series LED drivers per link
Controladores de LED por enlace
Pilotes de LED par bus
WARNING
Risk of Electric Shock. May Result in serious injury or death.
More than one disconnect may be required to de-energize
this device. Disconnect all power sources before servicing
unit.
ADVERTENCIA
AVERTISSEMENT
Risque d'électrocution. Peut causer le décès de la personne
ou de graves lésions. Plus d’un débranchement peut être
requis an de proceder à la deconnection totale de l’unité.
Débrancher toutes les sources d’énergie avant de procéder
à l’entretien de cette unité.
Riesgo de choque eléctrico. Puede resultar en lesiones
graves o muerte. Puede necesitarse más de una desconexión
para desenergizar este dispositivo. Desconecte todas las
fuentes de alimentación antes de prestar servicio a la unidad.
24
/
7 Help | Ayuda | Aide
U.S.A., Canadá, Caribbean | E.U.A., Caribe | É.-U., Caraïbes
México
+1.888.235.2910
1.844.LUTRON1
www.lutron.com/support
•Fourdaylightsensorinputsautomaticallyadjustlight
levels based on the amount of natural light entering
through the windows.
•FourIRreceiverinputsforpersonalcontrol.
•Supportspresetscenefadetimesfrom0seconds
to16minutes.
1
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node T-Series Digital Fixture Controller
3691096d 2 01.21.19
2 T-Series Digital Links
Enlaces digital
l
Buses numérique
Capacity
l
Capacidad
l
Capacité :
18 V- 250 mA per link | por enlace | par bus
QSN-TW
120
277 V~
50
/
60 Hz 500 mA
T-Series
Coopersburg, PA 18036, U.S.A.
saving energy since 1961
Energi Savr Node
IEC PELV
/
NEC
®
Class 2
Input Groups | Grupos de entrada
Groupes d’entreés :
20 V- 4 X 65 mA
QS Link | Enlace | Liaison :
24 V- 1 A
32 T-Series LED drivers per link
Controladores de LED por enlace
Pilotes de LED par bus
WARNING
Risk of Electric Shock. May Result in serious injury or death.
More than one disconnect may be required to de-energize
this device. Disconnect all power sources before servicing
unit.
ADVERTENCIA
AVERTISSEMENT
Risque d'électrocution. Peut causer le décès de la personne
ou de graves lésions. Plus d’un débranchement peut être
requis an de proceder à la deconnection totale de l’unité.
Débrancher toutes les sources d’énergie avant de procéder
à l’entretien de cette unité.
Riesgo de choque eléctrico. Puede resultar en lesiones
graves o muerte. Puede necesitarse más de una desconexión
para desenergizar este dispositivo. Desconecte todas las
fuentes de alimentación antes de prestar servicio a la unidad.
24
/
7 Help | Ayuda | Aide
U.S.A., Canadá, Caribbean | E.U.A., Caribe | É.-U., Caraïbes
México
+1.888.235.2910
1.844.LUTRON1
www.lutron.com/support
QS link
ControlPower
120-277V~
Emergency Contact
Closure Input
ProgrammableContact
Closure Input
Wireless
Communication
WiredDaylight
Sensors (up to 4)
WiredDaylight
Sensors
(up to 4)
1
T-Series Digital Links
(upto32T-Series
LED drivers per link)
WiredOccupancy
Sensors (up to 4)
WiredOccupancy
Sensors
(up to 4)
1
IRreceivers
(up to 4)
IRreceivers
(up to 4)
1
QSM
IRTransmitter
IRTransmitter
OR
OR
seeTouch QS
Wallstation
RadioPowrSavr
OccupancySensor
(upto10perQSM)
RadioPowrSavr
Daylight Sensor (new!)
(upto10perQSM)
PicoWireless
Controller (up to
10perQSM)
Note:
1 Upto4wiredinputstotal(ofanytype).
System Example
Quantum Hub
Note:ThisdeviceisnotcompatiblewiththeEnergiSavrNodeiOSprogrammingapp.Itisonlyforusein
a Quantum system
2
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node T-Series Digital Fixture Controller
3691096d 3 01.21.19
Specifications
Regulatory Approvals
•cUL
® Listed
•NOMCertied
•LutronQualitySystemsregisteredtoISO9001.2015
•IEC62386-101Ed.1
•Forcommercialuse,FCCClassAonly.
Power
•ControlPower:120-277V~50/60Hz
•Maximumcurrentdraw:0.5A
•LightningstrikeprotectionmeetsANSI/IEEEstandard
62.31-1980.Canwithstandvoltagesurgesofupto
6000V~andcurrentsurgesofupto3000A.
•T-Seriesdigitallinkoutput:18V-250mAmaximum
per loop
•10-yearpowerfailurememory:restoreslightingto
levels prior to power interruption.
Environment
•AmbientTemperatureOperatingRange:32ºFto
104ºF(0ºCto40ºC).
•Relativehumidity:lessthan90%non-condensing.
•Forindooruseonly.
•Complieswithrequirementsforuseinotherspaces
used for environmental air (plenums) per NECR2014
300.22(C)(3).
Terminals
Controlpowerwiring:14AWGto12AWG
(2.5 mm
2
to4.0mm
2
)
•T-Seriesdigitallinkwiring:20AWGto16AWG
(0.5mm
2
to1.5mm
2
)
•Inputgroupwiring:22AWGto12AWG
(0.5mm
2
to4.0mm
2
)
QSlinkwiring:22AWGto12AWG(0.5mm
2
to4.0mm
2
)
Physical Design
•NEMAType1,IP-20protection.
Mounting
•Surface-mount.
T-Series Digital Links
•Upto32LutronT-SeriesLEDdriversoneachloopcan
beaddressedandgroupedinto16zones.
•T-SeriesEnergiSavrNodeunitsupplies250mAto
power each loop.
•T-Seriesdigitallinkwiresarepolarityinsensitiveand
topology free.
•DonotconnectEcoSystemdevicestoT-Seriesdigital
links.
QS Link Limits
•EachT-SeriesEnergiSavrNodeunitcanprovideup
to30PowerDrawUnitsforotherQSdevices.Referto
theQSLinkPowerDrawUnitsspecicationsubmittal
(LutronP/N369405)formoreinformationconcerning
PowerDrawUnits.
•TheQSLinkcanhaveupto100devicesand
100zones.
•EachT-SeriesEnergiSavrNodeunitcountsas
1devicetowardsthe100devicelimit.
•EachT-SeriesEnergiSavrNodeunitcancountas
1to32zonestowardsthe100zonelimit,depending
onthenumberofzonescreated(upto32zonesina
Quantum system).
•Amaximumof8T-Seriesdigitallinksmaybe
connected to the QS link.
•T-SeriesEnergiSavrNodeunitcountsasupto
128switchlegs.
QS Link Sensor Limits
•100wiredandwirelessoccupancysensors.
•100wiredandwirelessdaylightsensors.
•100wiredwallstationsorPicowirelesscontrollers.
Sensors Connected to the T-Series Energi Savr
Node Units
•Fourpowersupplyoutputs
•20V-65mAmaximum
3
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node T-Series Digital Fixture Controller
3691096d 4 01.21.19
Specifications (continued)
Occupancy Sensors
•UseLutronLOSseriesofwiredoccupancysensorsin
occupancy mode to control one or more areas.
•UseLutronoccupancysensorsinvacancymode
to automatically turn the lights off in an area after it
becomes vacant.
•UseLutronoccupancysensorstoautomaticallyturn
the lights on in area when it becomes occupied and
to automatically turn the lights off in an area after it
becomes vacant.
•Eachofthefouroccupancyinputscanpowerone
Lutron occupancy sensor.
•UptofouradditionalLutronWiredOccupancy
SensorsortenadditionalRadioPowrSavr
Occupancy/VacancySensorscanbeassignedper
QS Sensor Module (QSM) on the QS link.
seeTouch QS Controls
•RefertoseeTouchQSSpecSubmittalforfurther
information.
•CongurableseeTouchQSwallstations,refertothe
QSWallstationProgrammingGuideforconguration
options
IR Controls
•UseLutronIRreceiversorwiredPicokeypadsfor
personalcontrolofindividuallightingzones.
•FourIRdevicescanconnectdirectlytotheT-Series
Energi Savr Node unit.
Daylight Sensors
•Lutrondaylightsensorsallowdaylightharvestingwith
programmable effect on light output.
•Fourdaylightsensorscanbeconnecteddirectlytothe
T-Series Energi Savr Node unit.
•UseLutronEC-DIR-WHsensorstocontroloneor
more daylight rows.
•Alternatively,uptofouradditionalLutronWired
DaylightSensorsortenadditionalRadioPowrSavr
Daylight Sensors can be assigned per QSM on the
QS link.
Contact Closure Input (CCI)
•Inputsmustbedrycontactclosure,solidstate,open
collector,oractive-low(NPN)/activehigh(PNP)
output.
OpencollectorNPNoractive-lowon-statevoltage
mustbelessthan2Vandsink3.0mA.
OpencollectorPNPoractive-highon-statevoltage
mustbegreaterthan12Vandsource3.0mA.
Opencircuitvoltage:24Vmaximum.
Off-stateleakagecurrentmustbelessthan100μA.
Acceptsmaintainedinputsandmomentaryinputs
with40msecminimumpulsetimes
•Congurablefornormallyopen(NO)ornormally
closed (NC) operation.
•Inputismiswire-protectedupto36V-.
•FunctionalitydenedbyQuantumsystem
programming.
Emergency Contact Closure Input
•Bydefault,contactclosureinputfromLutron
EmergencyLightingInterface(LUT-ELI-3PH),security,
orrealarmsystemsturnsallzonesontofulloutput
when emergency state is detected.
•Emergencycontactclosureinputisnormallyclosed
(NC). The T-Series Energi Savr Node unit is shipped
withajumperpre-installed.
•Responseofeachzoneiscongurable.
•Attacheddevices,bydefault,willgotomaximum
output and ignore control inputs.
•Nooperationswillbealloweduntilemergencysignal
is cleared.
•Inputsmustbedrycontactclosure,solidstate,open
collector,oractive-low(NPN)/activehigh(PNP)output.
OpencollectorNPNoractive-lowon-statevoltage
mustbelessthan2Vandsink3.0mA.
OpencollectorPNPoractive-highon-statevoltage
mustbegreaterthan12Vandsource3.0mA.
Opencircuitvoltage:24Vmaximum.
Off-stateleakagecurrentmustbelessthan100μA.
Acceptsmaintainedinputsandmomentaryinputs
with40msecminimumpulsetimes
•Inputismiswire-protectedupto36V-.
•EmergencyCCIcannotcontrolother
Energi Savr Node units.
•SeeApplicationNote#106,“EmergencyLighting”at
www.lutron.com for more details.
4
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node T-Series Digital Fixture Controller
3691096d 5 01.21.19
QS LINK
LOOP 2
LOOP 1
RESET
LOOP 2
TEST
GROUP 1
+20V
OCC 1
PHOTO 1
IR 1
COM
+24V
MUX
PWR
TEMPTEST
MUX
COM
GROUP 2
+20V
OCC 2
PHOTO 2
IR 2
COM
GROUP 3
+20V
OCC 3
PHOTO 3
IR 3
COM
GROUP 4
+20V
OCC 4
PHOTO 4
IR 4
COM
CONTACT CLOSURE ETHERNET
CCI
COM
EMERG
COM
LOOP 1
H/LN N/C
Mechanical Dimensions
Alldimensionsshownasin(mm)
11.25
(285.75)
0.20
(5.16)dia.
0.95
(24.13)
1.41
(35.81)
1.80
(45.72)
1.03
(26.16)
Do not
use side
knockouts
0.83
(21.08)
9.25
(234.95)
7.50
(190.50)
3.16
(80.26)
13.25
(336.55)
5
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node T-Series Digital Fixture Controller
3691096d 6 01.21.19
Wiring: QS Link
•QSlinkcommunicationusesIECPELV/NEC® Class 2 wiring.
Followalllocalandnationalelectricalcodeswheninstalling
IECPELV/NEC® Class 2 wiring with line voltage wiring.
•ThetotaldistanceoftheQSlinkwiringmustnotexceed
2000ft(610m).
Wiring Distance Wire Gauge Lutron Cable
Less than 500ft
(152m)
Power (terminals 1 and 2):
1 pair 18 AWG (1.0mm
2
)
GRX-CBL-346S (non-plenum)
GRX-PCBL-346S (plenum)
Data (terminals 3 and 4):
1 pair 22 AWG (0.5mm
2
),
twisted and shielded*
500ft to 2000ft
(152m to 610m)
Power (terminals 1 and 2):
1 pair 12 AWG (4.0mm
2
)
GRX-CBL-46L (non-plenum)
GRX-PCBL-46L (plenum)
Data (terminals 3 and 4):
1 pair 22 AWG (0.5mm
2
),
twisted and shielded*
*AlternateData-onlycable:Useapproveddatalinkcable22AWG
(0.5mm
2
)twisted/shieldedfromBelden,model#9461.
(4)
(3)MUX
(2)24V-
(1)COM
QS Link Wiring:
22AWGto12AWG
(0.5mm
2
to4.0mm
2
)
Drain
2 12 AWG
(4.0 mm
2
)
2 12 AWG
(4.0 mm
2
)
IEC PELV/NEC
® Class 2
control wiring
(2) 18 AWG (1.0 mm
2
)
1: Common
2: 24 V-
Control Link Wiring
Data link: (1) twisted,
shielded pair
22 AWG (0.5 mm
2
)
3: MUX
4: MUX
Wiring for QS link for 500 ft to
2000 ft (152m to 610 m).
Terminal block will not accept
12 AWG (4.0 mm
2
) directly.
6
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node T-Series Digital Fixture Controller
3691096d 7 01.21.19
Wiring: QS Link (continued)
Onlyterminals1,3,and4connected
betweendevicesthatsupplyPDUs
Terminal 2 NEVER connected between
devices that supply PDUs
Terminal2(+24V)
NEVERconnected*
Devices that
supplyPDUs
Devices that
consumePDUs
COM
+24 V
MUX
MUX
COM
MUX
MUX
T-Series Energi
Savr Node unit
T-Series Energi
Savr Node unit
QS Input/
Output
Interface
Wired QS
Keypad
QSM
QSMQSM
Wired QS
Keypad
Wired QS
Keypad
Wired QS
Keypad
QS Input/
Output
Interface
Quantum
Hub**
QS link;
all 4 terminals
QS link;
no terminal 2
QS link;
no terminal 2
QS link;
all 4 terminals
QS link;
all 4 terminals
Terminal2(+24V)
NEVERconnected*
Terminal2(+24V)
NEVERconnected*
All4terminalsconnectedtoQSlink
devicesthatconsumePDUs
QS Link Wiring Rules
* Terminal2(+24V)shouldNEVERbeconnectedbetweendevicesthatsupplyPDUs.
** ForQuantumHubwiringconnectiondetails,refertotheinstallationinstructionsforthe
specific Quantum Hub model being used.
NOTE:
RefertotheQSLinkPowerDrawUnitsspecicationsubmittal(LutronP/N369405)forinformationconcerning
PowerDrawUnits(PDUs)."
7
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node T-Series Digital Fixture Controller
3691096d 8 01.21.19
Wiring: IEC PELV / NEC® Class 2 Inputs
NOTE: There are four input groups. Each group has
the same inputs as shown in the diagram below.
Note: Maximumwire
run length to each
inputnottoexceed
150ft(45.7m).
Input Group Wiring:
22AWGto12AWG
(0.5mm
2
to4.0mm
2
)
* Note:OnlyoneIRdevicemaybeconnectedperIRinput.IftheIRsignalfromadaylightsensor
isconnected,anIRreceivermaynotbeconnectedtothesameinput,andvice-versa.
** Connectthegraywireon-Rmodeloccupancysensors.
OccupancySensor
IRReceiver*
Red
Red
20V
Black
Black COM
Yellow
Blue**
Black
Red
White*
20V:20V
OCC:OccupancySensor
PHOTO:DaylightSensor
IR:IRReceiver*
COM:Common
Group1shown Group2shown
White* IR
LUTRON
Daylight/IRSensor*
LUTRO
N
R
IRTransmitter
8
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node T-Series Digital Fixture Controller
3691096d 9 01.21.19
Wiring Diagram: T-Series Digital Link
The T-Series Energi Savr Node unit will supply
power to an independent T-Series digital link, which
supportsamaximumof32LutronT-SeriesLED
drivers per link.
T-Series Digital Link Wiring
•TheT-SeriesDigitalLinkmaybewiredClass1
or Class 2. Consult applicable electrical codes
forproperwiringpractices.PleaserefertoLutron
ApplicationNotes#106and#142atwww.lutron.com
for more information.
•Ensurethatthereisnotgreaterthana2V- drop
between the T-Series Energi Savr Node unit and the
end of the T-Series digital link.
•Consultallnationalandlocalelectricalcodesfor
separationrequirements.
Wire Gauge Maximum Wire Length
12AWG(4.0mm
2
) 1000ft(305m)
14AWG(2.5mm
2
) 1000ft(305m)
16AWG(1.5mm
2
) 900ft(275m)
18AWG(1.0mm
2
) 550ft(167m)
QS LINK
Loop 1
Loop 1
RESET
TEST
GROUP 1
+20V
OCC 1
PHOTO 1
IR 1
COM
+24V
MUX
PWR
TEMPTEST
MUX
COM
GROUP 2
+20V
OCC 2
PHOTO 2
IR 2
COM
GROUP 3
+20V
OCC 3
PHOTO 3
IR 3
COM
GROUP 4
+20V
OCC 4
PHOTO 4
IR 4
COM
CONTACT CLOSURE ETHERNET
CCI
COM
EMERG
COM
HNG
N/C
LOOP 2
LOOP 1
QS LINK
Loop 1
Loop 1
RESET
TEST
GROUP 1
+20V
OCC 1
PHOTO 1
IR 1
COM
+24V
MUX
PWR
TEMPTEST
MUX
COM
GROUP 2
+20V
OCC 2
PHOTO 2
IR 2
COM
GROUP 3
+20V
OCC 3
PHOTO 3
IR 3
COM
GROUP 4
+20V
OCC 4
PHOTO 4
IR 4
COM
CONTACT CLOSURE ETHERNET
CCI
COM
EMERG
COM
HNG
N/C
LOOP 2
LOOP 1
T-Series
Digital Link 1
T-Series
Digital Link 2
T1
T1
T2
T2
9
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node T-Series Digital Fixture Controller
3691096d 10 01.21.19
QS LINK
Loop 1
Loop 1
RESET
TEST
GROUP 1
+20V
OCC 1
PHOTO 1
IR 1
COM
+24V
MUX
PWR
TEMPTEST
MUX
COM
GROUP 2
+20V
OCC 2
PHOTO 2
IR 2
COM
GROUP 3
+20V
OCC 3
PHOTO 3
IR 3
COM
GROUP 4
+20V
OCC 4
PHOTO 4
IR 4
COM
CONTACT CLOSURE ETHERNET
CCI
COM
EMERG
COM
HNG
N/C
LOOP 2
LOOP 1
Wiring: Control Power
Hot/Line(H/L)
Neutral (N)
Ground( )
Donotuse(N/C)
Wiring Notes
•ControlPowerwiringshouldbefromanormal,
non-emergency feed for proper operation of the
T-Series Energi Savr Node unit.
•Powerterminalsaccept(1)or(2)14AWGto
12AWG(2.5mm
2
to4.0mm
2
) solid or
stranded wire.
QS LINK
Loop 1
Loop 1
RESET
TEST
GROUP 1
+20V
OCC 1
PHOTO 1
IR 1
COM
+24V
MUX
PWR
TEMPTEST
MUX
COM
GROUP 2
+20V
OCC 2
PHOTO 2
IR 2
COM
GROUP 3
+20V
OCC 3
PHOTO 3
IR 3
COM
GROUP 4
+20V
OCC 4
PHOTO 4
IR 4
COM
CONTACT CLOSURE ETHERNET
CCI
COM
EMERG
COM
HNG
N/C
LOOP 2
LOOP 1
10
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node T-Series Digital Fixture Controller
3691096d 11 01.21.19
Wiring: Contact Closure Inputs
COM:Common
COM:Common
CCI: Contact Closure Input
EMERG:EmergencyContactClosureInput
Emergency CCI
•Theattacheddevicemustprovideacloseddry
contact closure or solid-state output.
•Inputismiswire-protectedupto36V-.
•TheT-SeriesEnergi Savr Node unit is shipped with
ajumperpre-installedintheEmergencyContact
Closure Input.
•Emergencymodeisactivatedbyopeningthe
EmergencyContactClosure.Pre-installedjumper
mustberemovedtoutilizethisfunction.
•SeeApplicationNote#106,“EmergencyLighting” at
www.lutron.com for more details.
•Accepts22AWGto12AWG
(0.5mm
2
to4.0mm
2
) solid or
stranded wires.
•Maximumwirerundistance:
250ft(76m).
Programmable CCI
•Theattacheddevicemustprovideadrycontact
closure or solid-state output.
•Inputismiswire-protectedupto36V-.
Jumper
11
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node T-Series Digital Fixture Controller
3691096d 12 01.21.19
Typical Application: Requires Quantum system commissioning
Occupancy
Sensor
Daylight
Sensor
Loop 2
Loop 1
Versaplex
QS
LUTRO
N
Wired to
sensor
group 4
LUTRON
LUTRON
LUTRON
LUTRON
LUTRO
N
OpenOfces Corridor PrivateOfces
seeTouchQSWallstation
seeTouch QS
Wallstation
QS Link
QS Link
QS Link
WindowWindowWindow
Daylight
Sensor
Daylight
Sensor
Daylight
Sensor
Daylight
Sensor
Daylight
Sensor
Occupancy
Sensor
T-Series Energi
Savr Node unit
T-Series Energi
Savr Node unit
Occupancy
Sensor
Occupancy
Sensor
Occupancy
Sensor
Occupancy
Sensor
Occupancy
Sensor
T-Series
Digital Link
T-Series
Digital Link
T-Series
Digital Link
T-Series
Digital Link
T-Series
Digital Link
T-Series
Digital Link
Quantum
Hub
12
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node T-Series Digital Fixture Controller
3691096d 13 01.21.19
Troubleshooting and Maintenance Features
•Maintainsredundantmemoryofdriverprogrammingforeaseofsingleormultipledriverreplacement.
•Afterinstallation,"TEST"buttonveriesT-Seriesdigitallinkwiringonallxtures.Thetestmodeallowsallxtures
onthedigitallinktobeadjustedtohigh-end,low-end,ashing,oroff.Totestthecolor,high-endwillsendthe
lights to the coolest color and highest intensity, low-end will send it to the warmest color and lowest intensity,
ashingwillalternatebetweenwarm/dim,andcool/bright,andoffwillturnoffthelights.
•StatusLEDsverifyconnectionstocontrolstationsandsensors.
)Lutron,Lutron,EcoSystem,Pico,Quantum,EnergiSavrNode,T-Series,RadioPowrSavr,andseeToucharetrademarksofLutronElectronicsCo.,Inc.
registeredintheU.S.andothercountries.
NECisaregisteredtrademarkofNationalFireProtectionAssociation,Quincy,Massachusetts.
ULisatrademarkofULLLC.