SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive
PowPak Single Zone Control Module with EcoSystem Wireless Lighting Control
3691103d 2 12.21.18
Specifications
Regulatory Approvals
• ULListed
• FCCapproved.ComplieswiththelimitsforaClassB
device,pursuanttoPart15oftheFCCrules
• DALI-2Certified
• cULandIC
• NOM
• UL2043PlenumRated
• ListedinaccordancetoCAN/ULCS102.2-2010with
a Flame Spread Rating of 0 and a Smoke Developed
Classificationof40,withaminimumspacingof6ft
(1.83m)offcenter.
• CompatiblewithDALI-compliantloads
Power
• 120–277V~50/60Hz,max.current80mA
Other Power Specifications
• Standbypower:
120–277V~<1.0W
System Communication
• OperatesusingClearConnectRFTechnologyfor
reliable wireless communication
• Wirelesssensorsandcontrolsmustbelocatedwithin
30ft (9m) of the associated control module.
Key Design Features
• LEDstatusindicatorshowsloadstatusandprovides
programming feedback
• Configurablehigh-endandlow-endtrim
• Powerfailurememory:Ifpowerisinterrupted,
connected loads will return to the previous level prior
to interruption
Environment
• Ambientoperatingtemperature:32°Fto104°F
(0°Cto40°C)
• 0%to90%humidity,non-condensing
• Forindooruseonly
Mounting
• Thisdevicecanbeinstalledonajunctionbox
ormarshallingboxusingtheconduitnutorwith
mounting screws and must be installed away from
afixture/troffer.ThedevicemustNOTbemounted
insideoronafixture/trofferorothermetallic
enclosure.
• ForapplicationswherecoderequiresthePowPak
Control Module to be installed inside an additional
junctionbox(e.g.,U.S.A.),pleaseseeLutron
ApplicationNote#423(P/N048423)at
www.lutron.com. For all other installations, refer to
the installation instructions and consult local and
national electric codes for proper installation.
• ThePowPakControlModuleneedstobeaccessible
for some programming steps. Record where it is
mounted so that it can be easily located later.
Metal Ceiling Mounting
• Metalceilinggridsmusthavea>0.12in(3mm)gap
ofnon-metalmaterialwhichextendstheentirelength
of the tile on at least one edge. This is often achieved
by foam spacers that are used to prevent tile-to-tile
rattling.
• Metalceilinggridswhicharecontinuous(withno
gap) or those that are interlocked, must have a total
surface area that is less than 900ft
2
(81m
2
) for
each section. The overall space can be larger as
long as there are non-metal sections bordering or
intersecting the metal sections.
Continuedonnextpage...
NOTICE:Improperinstallationcanresultin
degraded wireless communication and/or
intermittent or sustained communication failures,
and will not be covered under warranty.