SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr NodeTM QSE-CI-AP-D Programming Interface
369282d 2 04.01.16
Specifications
Power
• SELV / PELV / NEC
® Class 2
• Operating voltage: 24–36 V- 40 mA
• Consumes two (2) power draw units on the QS link.
Refer to the QS Link Power Draw Units specification
submittal (Lutron
® P/N369405) for more information
concerning Power Draw Units.
Standards
• CE Certified
• Lutron
® Quality Systems registered to ISO 9001.2000
• NOM Compliant
Environment
• Ambient Temperature Operating Range: 32 ºF to 140 ºF
(0 ºC to 60 ºC)
• Relative humidity: less than 90% non-condensing
• For indoor use only
Terminals
• Ethernet port
• QS Link Wiring: 22 AWG to 12 AWG (0.5 mm
2
to 4.0 mm
2
)
Mounting
• DIN rail - occupies three DIN rail mount spaces at
2.125in (53 mm) wide
• Surface mount
• Junction box
Programming Requirements
• An Apple iPod touch or iPhone mobile digital device
with the Energi Savr Node
TM app is required for
programming Energi Savr Node
TM units.
• The Energi Savr Node
TM app for Apple iPod touch or
iPhone is used to program the Energi Savr Node
TM
unit in installations requiring an Energi Savr Node
TM
Programming Interface for commissioning. The Energi
Savr Node
TM app is available from the iTunes Store
online marketplace.
• The Energi Savr Node
TM app cannot be used to
program the Energi Savr Node
TM units when installed as
part of a Quantum
® system.
• The Apple iPod touch or iPhone communicates with the
Energi Savr Node
TM unit via a WiFi router (not included).
• See “Programming Options” section for further
information.
Ethernet Connection
• Standard CAT5 (or better) cable connects the
QSE-CI-AP-D interface to a wireless router.
• Supports MDI / MDIX auto-crossover (no crossover
cable needed).
• Total cable length must be 327 ft (100 m) or less.
• Ethernet network and cable provided by others.
QS Link Limits
• Each Energi Savr Node
TM Programming Interface
counts as 1 device towards the 100 device QS link
limit.
• QS communication link uses SELV / PELV / NEC
®
Class2 wiring. Follow all local and national electrical
codes when installing SELV / PELV / NEC
® Class 2
wiring with line voltage wiring.
• The total length of the QS link must not exceed
2000ft (610m). See table below.
Table 1: QS Link Wiring Options
QS Link Wiring
Length
Wire Gauge Lutron® Cable Part Number
Less than 500ft
(153 m)
Power (terminals 1 and 2)
1 pair 18 AWG (1.0 mm
2
)
GRX-CBL-346S (non-plenum)
GRX-PCBL-346S (plenum)
Data (terminals 3 and 4)
1 twisted, shielded pair
22AWG (0.5 mm
2
)
Up to 2000 ft
(610 m)
Power (terminals 1 and 2)
1 pair 12 AWG (4.0 mm
2
)
GRX-CBL-46L (non-plenum)
GRX-PCBL-46L (plenum)
Data (terminals 3 and 4)
1 twisted, shielded pair
22AWG (0.5 mm2)
QS Link Terminal Connections
• Each QS link terminal can accept only two 18AWG
(1.0 mm
2
) wires. Two 12 AWG (4.0 mm
2
) conductors
will not fit. Connect as shown below using appropriate
wire connectors.
Apple, iPhone, iPod touch, and iTunes Store are trademarks of Apple Inc., registered in the
U.S. and other countries.
12AWG
(4.0mm
2
)
18AWG
(1.0mm
2
)