369355d 1 09.14.17
3-Wire Fluorescent Power Module Power ModulesLutron
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
3-Wire Fluorescent Power Module
Description
• Provides capability for a zone on a GRAFIK Eye control
unit (or other product) to dim fluorescent lights that have
Lutron Hi-lume and Eco-10 (Eco Series) line-voltage
control electronic dimming ballasts.
• Utilizes Softswitch arcless switching technology.
• Up to 3 power modules may be wired on a single
GRAFIK Eye zone.
• Models available for 120 V~ control power.
• Models available for 120 V~ or 120 –277 V~
load power.
Works with 120 V~ versions of:
• Lutron 3-wire fluorescent dimmers (consult Lutron for
Vierti products); see approved list in the dimmers and
switches specification guide at www.lutron.com
• GRAFIK Eye QS control units
• GRAFIK Eye 3000 Series control units
• LP, LCP, and GP dimming panels
• HomeWorks and HomeWorks QS remote power panels
• HomeWorks and HomeWorks QS neutral wire dimmers
• RadioRA 2 neutral wire dimmers
• Caseta Wireless neutral wire dimmers
Models and Capacities
Model Number Control Power Load Power Capacity
PHPM-3F-DV-WH 120 V~
120 –277 V~ 16 A
PHPM-3F-120-WH 120 V~
120 V~ 16 A
1
369355d 2 09.14.17
3-Wire Fluorescent Power Module Power ModulesLutron
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Regulatory Approvals
• UL® listed
CSA certified
NOM certified
Complies with requirements for use in other spaces
used for environmental air (plenums) per
NEC
® 2014 300.22(C)(3)
Power
Control voltage: 120 V~
Load voltage: 120 V~ only for PHPM-3F-120-WH
120 –277 V~ for PHPM-3F-DV-WH
Capacity: Full 16 A
120 V~: 1920 W
120 –277 V~: 1920 – 4432 W
Frequency: 50 / 60 Hz, phase-to-neutral.
• Load (output) power: Phase independent of control
device / control voltage.
Sources/Load Types
• Operates Lutron Hi-lume, Eco-10 (Eco Series), Hi-lume
Compact SE, EcoSystem, and EcoSystem compact
line-voltage control electronic dimming ballasts with a
smooth continuous Square-Law dimming curve.
Key Design Features
• Patented RTISS Equiped circuitry compensates in real
time for incoming line-voltage variations: Compensates
for +/-2% change in RMS voltage / cycle and
+/-2% Hz change in frequency / second.
• Provides air-gap off.
• Module protects itself during temporary over-current
conditions on dimmed output.
• Two LEDs on front of unit provide diagnostic information
(visible when faceplate is removed).
Terminals
• Accept up to two 12 AWG (2.5 mm
2
) wires.
Specifications
Environment
• 32 °F to 104 °F (0 °C to 40 °C). Relative humidity
less than 90% non-condensing.
• Indoor use only.
• Maximum heat output of module: 15 BTU / hour.
Mounting
• Surface- or recess-mount.
2
369355d 3 09.14.17
3-Wire Fluorescent Power Module Power ModulesLutron
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
5.1
(129.5)
Dimensions
All dimensions shown as: in (mm)
1.0 (25)
1.2 (30.5)
6.3
(160)
3
369355d 4 09.14.17
3-Wire Fluorescent Power Module Power ModulesLutron
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Mounting
• Mount in 2-gang U.S. wallbox 3.5 in (89 mm) deep or
4 in x 4 in (102 mm x 102 mm) junction box 2.1 in
(53 mm) deep.
• Indoor use only.
• This device generates heat; mount only where ambient
temperature is 32 °F to 104 °F (0 °C to 40 °C).
• Mount with arrows facing up to ensure adequate
cooling.
• Allow 4.5 in (114 mm) above and below unit and
between faceplates when mounting several in a
vertical layout.
• Mount so line (mains) voltage wiring is at least 6 ft
(1.8 m) from sound or electronic equipment and
wiring.
• Mount within 7° of true vertical.
Mount to 2-gang U.S. wallbox
Mount to 4 in x 4 in (102 mm x 102 mm),
2.1 in (53 mm) deep U.S. junction box
Mount to 4 in x 4 in (102 mm x 102 mm), 2.1 in (53 mm) deep
U.S. junction box with barrier
(for 277 V~ model if required by local electrical code)
Barrier
4
369355d 5 09.14.17
3-Wire Fluorescent Power Module Power ModulesLutron
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
• Pull 12 AWG (2.5 mm
2
) copper (Cu) wires [167 °F (75 °C) minimum] for input power and load circuit.
• Strip 1/2 in (12 mm) insulation from wires before connecting.
• Run separate neutral for load circuit - no common neutrals.
Wiring
The power module may be on the same circuit as the control unit only if the total load does not exceed the
rating of the breaker.
Single Power Feed
123456LN
L/H
N
SH
DH
L/H
N
Lutron
Ballast
GRAFIK Eye QS
Zone in
Control Neutral
Wire to appropriate
zone
Circuit breaker
Legend
L /H Line / Hot
N Neutral
SH Switched Hot
DH Dimmed Hot
Ground
Not Used
120 V~
5
369355d 6 09.14.17
3-Wire Fluorescent Power Module Power ModulesLutron
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Multiple Power Feeds
Wiring (continued)
The load breaker may be on a different phase than the control breaker.
123456LN
L/H
N
SH
DH
L/H
N
L/H
N
Lutron
Ballast
GRAFIK Eye QS
Zone in
Control Neutral
Wire to appropriate
zone
Legend
L / H Line / Hot
N Neutral
SH Switched Hot
DH Dimmed Hot
Ground
Not Used
Load breaker
Control breaker
120 V~
Load wiring
1
1
Load feed: 120 V~ for PHPM-3F-120-WH; 120 – 277 V~ for PHPM-3F-DV-WH
6
369355d 7 09.14.17
3-Wire Fluorescent Power Module Power ModulesLutron
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wiring (continued)
Multiple Power Modules to a Single GRAFIK Eye Zone
Shown with separate feeds for control and loads. All breakers must be turned off prior to installing or servicing
the modules. Up to 3 power modules may be wired to a single zone.
123456LN
L/H
N
DH
L/H
N
DH
L/H
N
DH
L/H
N
L/H
N
L/H
N
N
L/H
SH
SH
SH
GRAFIK Eye QS
Zone in
Control Neutral
Wire to appropriate zone
Load breaker
Zone in
Control Neutral
Load breaker
Lutron
Ballast
Zone in
Control Neutral
Load breaker
Control breaker
Load wiring
1
for Power
Module #1
Load wiring
1
for Power
Module #2
Load wiring
1
for Power
Module #3
1
Load feed: 120 V~ for PHPM-3F-120-WH; 120 – 277 V~ for PHPM-3F-DV-WH
120 V~
Lutron
Ballast
Lutron
Ballast
7
369355d 8 09.14.17
3-Wire Fluorescent Power Module Power ModulesLutron
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
The power module may be on the same circuit/control zone as the control device only if the total load does not
exceed the rating of the breaker (120 V~ only).
Wiring (continued)
Multi-location Wiring
L/H
N
SH
DH
L/H
N
H/L
N
Lutron
Ballast
Circuit breaker
Legend
L/H Line / Hot
N Neutral
SH Switched Hot
DH Dimmed Hot
Ground
Not Used
3-wire
fluorescent
dimmer
120 V~
(main
dimmer)
3-wire
fluorescent
dimmer
120 V~
(accessory/
companion
dimmer or
3-way switch)
120 V~
Load wiring
1
1
Load feed: 120 V~ for PHPM-3F-120-WH; 120 – 277 V~ for PHPM-3F-DV-WH
SH
(red wire)
Cap off
DH
(yellow
or orange
wire)
Zone in
Control Neutral
For specific wire colors, see the wallbox lighting controls
catalog at www.lutron.com/wallbox catalog
8
369355d 9 09.14.17
3-Wire Fluorescent Power Module Power ModulesLutron
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
DH
DH
DH
DH
H
N
N
N
N
N
L/H
N
SH
L/H
N
DH
Wiring (continued)
Wiring a Power Module to an LP, LCP, GP, or HomeWorks Panel
Up to three 3-wire fluorescent power modules may be wired to an output of a 120 V~
LP or LCP panel. The
load type for the output must be set as Eco-10 or Hi-lume fluorescent load type on the panel’s circuit selector
(for an LP or GP panel), controller (for an LCP panel), or HomeWorks software (for a HomeWorks panel).
Lutron
Ballast
(1) 14 to 10 AWG
(2.0 to 4.0 mm
2
)
(1) 14 to 10 AWG
(2.0 to 4.0 mm
2
)
Zone In
Control
Neutral
Dimmed
Hot
Neutral
120 V~ Branch Circuit
Breakers
Neutral Lug
Neutral (1) 14 to 2/0 AWG
(2.0 to 70 mm
2
)
Power (Line / Hot)
(3) 14 to 2/0 AWG (2.0 to 70 mm
2
)
Wire to appropriate output
Load
wiring
1
1
Load feed: 120 V~ if used with PHPM-3F-120-WH power module
120 – 277 V~ if used with PHPM-3F-DV-WH power module
)Lutron, Lutron, Eco-10, Hi-lume, HomeWorks, RTISS Equiped,
Softswitch, Vierti, Caseta, and GRAFIK Eye are trademarks of
Lutron Electronics Co., Inc., registered in the U.S. and other
countries.
Hi-lume Compact SE, and RadioRA 2 are trademarks of Lutron
Electronics Co., Inc.
NEC is a registered trademark of National Fire Protection
Association, Quincy, Massachusetts.
UL and the UL logo are trademarks of UL LLC.
9