369357h 1 03.03.20
Power ModulesSwitching Power Module
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron
Switching Power Module
Description
• Provides capability for a zone on a GRAFIK Eye control unit
(or other product) to switch a fully loaded circuit of lighting.
• May be used to switch incandescent, electronic low-
voltage, magnetic low-voltage, HID, fluorescent ballasts,
and neon / cold cathode lighting sources.
• Utilizes Softswitch arcless switching technology.
• Provides power and switching for one zone.
• Up to 3 power modules may be wired on a single
GRAFIK Eye zone.
• Model available for 120 V~ control power.
• Model available for 120 –277 V~ load power.
Works with 120 V~ versions of:
• Lutron 3-wire fluorescent dimmers (consult Lutron for Vierti
products); see approved list in the dimmers & switches
specification guide at www.lutron.com
GRAFIK Eye QS control units
GRAFIK Eye 3000 Series control units
• LP, LCP, and GP dimming panels
• HomeWorks and HomeWorks QS remote power panels
• HomeWorks and HomeWorks QS neutral wire dimmers
• RadioRA 2 neutral wire dimmers
• Caséta Wireless neutral wire dimmers
• Energi Savr Node LED+ phase adaptive fixture controller
Models and Capacities
Model Number Control Power Load Power Capacity
PHPM-SW-DV-WH 120 V~ 120 – 277 V~ 16 A
1
369357h 2 03.03.20
Power ModulesSwitching Power Module
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron
Specifications
Regulatory Approvals
• UL® listed
CSA certified
NOM certified
Complies with requirements for use in other spaces
used for environmental air (plenums) per
NEC® 2017 300.22(C)(3)
Power
Control voltage: 120 V~
Load voltage: 120 – 277 V~
Capacity: Full 16 A
120 –277 V~: 1920 – 4432 W
Frequency: 50 / 60 Hz, phase-to-neutral.
• Load (output) power: Phase independent of control
device / control voltage.
Sources / Load Types
• Switches the following load types:
– Incandescent (tungsten)
Halogen
LED
CFL
Magnetic low-voltage transformer (iron core)
Electronic (solid-state) low-voltage transformer
Magnetic and electronic fluorescent dimming ballasts
– Neon/cold-cathode
– HID
• Motors:
– 1
1
2 HP at 277 V~
1/2 HP at 120 V~
• May be used with GFI / AFCI breaker protected loads.
Key Design Features
• Patented Softswitch technology.
• Two LEDs on front of unit provide diagnostic information
(visible when faceplate is removed).
Terminals
• Accepts up to two 12 AWG (2.5 mm
2
) wires.
Environment
• 32 to 104 °F (0 to 40 °C). Relative humidity less than
90% non-condensing.
• Indoor use only.
• Maximum heat output of module: 15 BTU/hour.
Mounting
• Surface- or recess-mount.
2
369357h 3 03.03.20
Power ModulesSwitching Power Module
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron
5.1
(129.5)
Dimensions
All dimensions shown as: in (mm)
1.0 (25)
1.2 (30.5)
6.3
(160)
3
369357h 4 03.03.20
Power ModulesSwitching Power Module
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron
Mounting
• Mount in 2-gang U.S. wallbox 3.5 in (89 mm) deep or
4 in x 4 in (102 mm x 102 mm) junction box 2.1 in
(53 mm) deep.
• Indoor use only.
• This device generates heat; mount only where ambient
temperature is 32 °F to 104 °F (0 °C to 40 °C).
• Mount with arrows facing up to ensure adequate
cooling.
• Allow 4.5 in (114 mm) above and below unit and
between faceplates when mounting several in a
vertical layout.
• Mount so line (mains) voltage wiring is at least 6 ft
(1.8 m) from sound or electronic equipment and
wiring.
• Mount within 7° of true vertical.
Mount to 2-gang U.S. wallbox
Mount to 4 in x 4 in (102 mm x 102 mm),
2.1 in (53 mm) deep U.S. junction box
Mount to 4 in x 4 in (102 mm x 102 mm), 2.1 in (53 mm) deep
U.S. junction box with barrier
(for 277 V~ model if required by local electrical code)
Barrier
4
369357h 5 03.03.20
Power ModulesSwitching Power Module
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron
• Pull 12 AWG (2.5 mm
2
) copper (Cu) wires [167 °F (75 °C) minimum] for input power and load circuit.
• Strip 1/2 in (12 mm) insulation from wires before connecting.
• Run separate neutral for load circuit - no common neutrals.
• May be used with GFI breaker protected loads. Load circuit wiring (from GFI breaker to power
module to load) must be run in its own non-metallic conduit, or nuisance tripping may occur.
Maximum 100 ft (30.5 m) between power module and load.
• May be used with AFCI breaker protected loads. An AFCI circuit can be loaded to the full allowable
NECR rating for switched lighting. If combining dimmed and switched lighting on the same AFCI
circuit, the amount of dimmed lighting should not exceed 1000 W, as this may trip the AFCI breaker.
Wiring
Note: The power module may be on the same circuit as the control unit only if the total load does not exceed
the rating of the breaker.
Single Power Feed
123456LN
L/H
N
SH
L/H
N
GRAFIK Eye QS
Zone in
Control Neutral
Wire to appropriate
zone
Circuit breaker
Legend
L /H Line / Hot
N Neutral
SH Switched Hot
Ground
Not Used
120 V~
Load (Switched)
120 V~
5
369357h 6 03.03.20
Power ModulesSwitching Power Module
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron
Multiple Power Feeds
Wiring
The load breaker may be on a different phase than the control breaker.
123456LN
L/H
N
SH
L/H
N
L/H
N
GRAFIK Eye QS
Zone in
Control Neutral
Wire to appropriate
zone
Legend
L / H Line / Hot
N Neutral
SH Switched Hot
Ground
Not Used
Load breaker
Control breaker
120 V~
Load wiring
Load (Switched)
6
369357h 7 03.03.20
Power ModulesSwitching Power Module
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron
Wiring Multiple Power Modules to a Single GRAFIK Eye Zone
Shown with separate feeds for control and loads. All breakers must be turned off prior to installing or servicing
the modules. Up to 3 power modules may be wired to a single zone.
123456LN
L/H
N
L/H
N
L/H
N
L/H
N
L/H
N
L/H
N
N
L/H
SH
SH
SH
GRAFIK Eye QS
Zone in
Control Neutral
Wire to appropriate zone
Load breaker
Zone in
Control Neutral
Load breaker
Zone in
Control Neutral
Load breaker
Control breaker
Load wiring
1
for Power
Module #1
Load wiring
1
for Power
Module #2
Load wiring
1
for Power
Module #3
1
Load feed: 120 – 277 V~ for PHPM-SW-DV-WH
120 V~
Load
(Switched)
Load
(Switched)
Load
(Switched)
7
369357h 8 03.03.20
Power ModulesSwitching Power Module
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron
Note: The power module may be on the same circuit/control zone as the control device only if the total load
does not exceed the rating of the breaker (120 V~ only).
Multi-location Wiring
L/H
N
SH
L/H
N
H/L
N
Load (Switched)
Circuit breaker
Legend
L/H Line / Hot
N Neutral
SH Switched Hot
DH Dimmed Hot
Ground
Not Used
3-wire
fluorescent
dimmer
120 V~
(main
dimmer)
3-wire
fluorescent
dimmer
120 V~
(accessory/
companion
dimmer or
3-way switch)
120 V~
Load wiring
(see Note
below)
SH
(red wire)
Cap off
DH
(yellow
or orange
wire)
Zone in
Control Neutral
For specific wire colors, see the wallbox lighting controls
catalog at www.lutron.com/wallbox catalog
8
369357h 9 03.03.20
Power ModulesSwitching Power Module
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron
DH
DH
DH
DH
H
N
N
N
N
N
L/H
N
SH
L/H
N
Wiring a Power Module to an LP, LCP, GP, or HomeWorks Panel
Up to three power modules may be wired to an output of a 120 V~ LP or LCP panel. The load type for the
output must be set as Eco-10 or Hi-lume fluorescent load type on the panel’s circuit selector (for an LP or
GP panel), controller (for an LCP panel), or HomeWorks software (for a HomeWorks panel).
(1) 14 to 10 AWG
(2.0 to 4.0 mm
2
)
(1) 14 to 10 AWG
(2.0 to 4.0 mm
2
)
Zone In
Control
Neutral
Dimmed
Hot
Neutral
120 V~ Branch Circuit
Breakers
Neutral Lug
Neutral (1) 14 to 2/0 AWG
(2.0 to 70 mm
2
)
Power (Line / Hot)
(3) 14 to 2/0 AWG (2.0 to 70 mm
2
)
1
Load feed:
120 – 277 V~ if used with PHPM-SW-DV-WH power module
Wire to appropriate output
Load
wiring
1
Load
(Switched)
)Lutron, Lutron, GRAFIK Eye, Softswitch, Vierti,
HomeWorks, RadioRA, Eco-10, Caseta, and Hi-lume
are trademarks of Lutron Electronics Co., Inc. registered
in the U.S. and other countries.
RadioRA 2 is a trademark of Lutron Electronics Co., Inc.
NEC is a registered trademark of National Fire Protection
Association, Quincy, Massachusetts.
9
369357h 10 03.03.20
Power ModulesSwitching Power Module
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron
L/ H
N
SH
Def
1
2
3
Opt
Ta > 70 ˚C
Prog
Input
Entrada
Entrée
120 V~
16 A
50 / 60 Hz
QSN-4A5-D
CCI
800 W
500 W 500 W 500 W
H
M
L
+1.844.LUTRON1
lutron.com
Zn 1 Zn 2
Zn 3
Zn 4
277 V
8.3 A
50 / 60 Hz
~
CCI
COM
MUX
MUX
COM
L N NL N N N
DL1 DL2 DL3 DL4
N
N DL
N
L/H
Phase Adaptive
Outputs
L/H
Control Feed
(120 V~)
Lighting
Loads
Zone In
Control
Neutral
Load breaker
L L
N N N N
N
DL1
DL2 DL3 DL4
Wiring to an Energi Savr Node LED+ Phase Adaptive Fixture Controller
Single or Multiple Power Modules to Single Power Panel
Control feed must be 120 V~ only.
Load feed must not exceed voltage rating of the load.
Up to three power modules may be wired to an output.
Load Wiring
1
1
Load feed: 120 – 277 V~ if used with
PHPM-SW-DV-WH power module
Legend
L/H Line / Hot
N Neutral
SH Switched Hot
DH Dimmed Hot
Ground
Not Used
10