GP Dimming PanelsGRAFIK Systems Power Equipment
369401f 1 09.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GP dimming panels provide power and dimming for
up to 144 load circuits and control any light source,
including full-conduction, non-dimming.
Models available with:
•120V~and277V~ input power.
•3to144circuits.
•Differentfeedtypesandbreakers.
GP Dimming Panels work with:
•GRAFIKEye4000ControlUnits.
•GRAFIK5000,GRAFIK6000,GRAFIK7000Systems
andQuantumSystems.
•LPDimmingPanels.
•XPSoftswitchPanels.
•DMX512dimmingsystemsviathe2LINKoption.
GP Dimming Panels: 120/277 V~
GP3/4
Mini-Size
Panels
GP8-24
Standard-Size
Panels
GP36
Large-Size
Panels
GP48-144
Large-Size
Panels
1
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f209.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GP dimming panels provide power and dimming for up to
24loadcircuitsandcontrolanylightsource,including
full-conduction, non-dimming.
Models available with:
•230V~ input power.
•3to24circuits.
•Differentfeedtypesandbreakers.
GP Dimming Panels work with:
•GRAFIKEye4000ControlUnits.
•GRAFIK5000,GRAFIK6000,GRAFIK7000Systemsand
QuantumSystems.
•LPDimmingPanels.
•XPSoftswitchPanels.
•DMX512dimmingsystemsviathe2LINKoption.
GP3/4
Mini-Size
Panels
GP8-24
Standard-Size
Panels
GP Dimming Panels: 230 V~ (CE)
2
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f 3 09.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
GP dimming panels provide power and dimming for up to
24loadcircuitsandcontrolanylightsource,including
full-conduction, non-dimming.
Models available with:
•220–240V~ input power.
•3to24circuits.
•Differentfeedtypesandbreakers.
GP Dimming Panels work with:
•GRAFIKEye4000ControlUnits.
•GRAFIK5000,GRAFIK6000,GRAFIK7000Systemsand
QuantumSystems.
•LPDimmingPanels.
•XPSoftswitchPanels.
•DMX512dimmingsystemsviathe2LINKoption.
GP3/4
Mini-Size
Panels
GP8-24
Standard-Size
Panels
GP Dimming Panels: 220240 V~ (non-CE)
3
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f 4 09.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Standards
•ULRListed(Reference:ULFileE42071).
•ComplieswithCSAorNOM(whereappropriate).
•CaliforniaEnergyCommissionListed
•SeismicCertied(TestMethodAC156.Reference
OSHPDPreapprovalOSP-0215-10).
Power
•Inputpower:120V~and277V~,50/60Hz,phase-
to-neutral.
•BranchCircuitCapacity:
–120V~(upto2000W/VA)
–277V~(4500W/VA)
–Minimumload:0W
•NumberofCircuits:3–144
•BranchCircuitBreakers:ULR rated thermal magnetic.
AICratings(otherratingsavailable):
–120V~(10,000A)
–277V~(14,000A)
•Lightningstrikeprotection:MeetsANSI/IEEEstandard
62.41-1980.Canwithstandvoltagesurgesofupto
6000V~andcurrentsurgesofupto3000A.
•10-yearpowerfailurememory:Automaticallyrestores
lighting to scene selected prior to power interruption.
Sources/Load Types
Operatesthesesourceswithasmoothcontinuous
SquareLawdimmingcurveoronafull-conduction,
non-dimmingbasis:
•Incandescent(Tungsten)/Halogen
•MagneticLow-VoltageTransformer
•LEDdriversspeciedbythemanufacturertowork
with forward-phase dimming controls. *
•Electroniclow-voltagetransformersspeciedbythe
manufacturertoworkwithforward-phasedimming
controls.
•LutronElectronicFluorescentDimmingBallasts
•MagneticFluorescentLampBallasts
•Optionalmodulesallowforcontrolof010V-,DSI,
andPWMloadtypes.
•OperatesHIDsourcesonafull-conduction,
non-dimmingbasis.
Wiring
•Internal:Pre-wiredbyLutron.
•Systemcommunications:Low-voltageIECPELV/NEC®
Class2wiringconnectsdimmingpanelstoother
components.
•Line(mains)voltage:Feed,load,andcontrolcircuit
wiringonly;nootherwiringorassemblyrequired.
Filter Chokes
•Loadcurrentrisetimeismeasuredata90-degree
conduction angle.
•10–90%ofload-currentwaveform:
–350µSecrisetimeat50%dimmercapacity.
–400µSecrisetimeat100%dimmercapacity.
•0100%ofload-currentwaveform:
–525µSecrisetimeat50%dimmercapacity.
–600µSecrisetimeat100%dimmercapacity.
•Atnopointinthewaveformcantherateofcurrent
changeexceed300mAperµSec.
•ConsultLutronforhigherrisetimeoptions.
Dimming Cards
•Panelcurrentratingsarelistedforcontinuous
operation;UL®listedspecicallyforeachlightsource.
•RTISSltercircuittechnologycompensatesfor
incominglinevoltagevariations;novisibleickerwith
+/–2%changeinRMSvoltage/cycleand+/–2%Hz
changeinfrequency/second.
•Arclessrelayair-gapOFFswitches(oneperload
circuit)ensureopenloadcircuitswhenOFFfunction
is selected; eliminate arcing at mechanical contacts
when loads are switched.
Physical Design
•Enclosure:NEMA-Type1(Type2availableonrequest);
IP-20protection;16U.S.GaugeSteel;indooruseonly.
•Weight:30to1300lb(14to590kg).
•Mounting:Surface-mountonly.Allowspacefor
ventilating.
•SeismicCerticationLimits:SDS=2.5g,z/h=1.0,
IP=1.5forwallorwall/oormountedpanels.
SDS=1.5gforoor-mountpanelsonly.Contact
Lutronfordetails.
Environment / Heat Dissipation
•Patented,ribbedaluminumheatsinkbasecoolspanel
byconvection;nofans.
•32°F–104°F(0°C–40°C);relativehumiditylessthan
90%,non-condensing.
Specifications: 120/277 V~
continued on next page…
* LutroncannotguaranteecompatibilitywithuntestedLEDdrivers.RefertotheLEDProductSelectiontoolatwww.lutron.com/ledtoolforalistof
compatibleproducts.
4
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f509.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Short Circuit Current Ratings(otherratingsavailable)
Panel Type Voltage Std. Min. SCCR Rating
GPMainLug(standard-andlarge-size) 120V~;277V~ 25,000A
GPMainBreaker(standard-size)
120V~ 10,000A
277V~ 18,000A
GPMainBreaker(large-size)
120V~ 25,000A
277V~ 25,000A
GPMini-Size
120V~ 10,000A
277V~ 14,000A
GPMini-Size(feed-through)
120V~ 10,000A
277V~ 14,000A
Specifications: 120/277 V~(continued)
5
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f 6 09.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wiring
•Internal:Pre-wiredbyLutron.
•Systemcommunications:Low-voltageIECPELV/NEC®
Class2wiringconnectsdimmingpanelstoother
components.
•Line(mains)voltage:Feed,load,andcontrolcircuit
wiringonly;nootherwiringorassemblyrequired.
Filter Chokes
•Loadcurrentrisetimeismeasuredata90-degree
conductionangle,with120V~ input power.
•10-90%ofloadcurrentwaveform:
–350µSecrisetimeat50%dimmercapacity.
–400µSecrisetimeat100%dimmercapacity.
•0100%ofloadcurrentwaveform:
–525µSecrisetimeat50%dimmercapacity.
–600µSecrisetimeat100%dimmercapacity.
•Atnopointinthewaveformcantherateofcurrent
changeexceed300mAperµSec.
•ConsultLutronforhigherrisetimeoptions.
Dimming Cards
•Panelcurrentratingsarelistedforcontinuous
operation.
•RTISSltercircuittechnologycompensatesfor
incominglinevoltagevariations;novisibleickerwith
+/–2%changeinRMSvoltage/cycleand+/–2%Hz
changeinfrequency/second.
•Arclessrelayair-gapOFFswitches(oneperload
circuit)ensureopenloadcircuitswhenOFFfunction
is selected; eliminate arcing at mechanical contacts
when loads are switched.
Physical Design
•Enclosure:NEMA-Type1(Type2availableonrequest),
IP-20protection;16U.S.GaugeSteel;indooruseonly.
•Weight:30to175lb(14to80kg).
•Mounting:Surface-mountonly;allowspacefor
ventilating.
Environment/Heat Dissipation
•Patented,ribbedaluminumheatsinkbasecoolspanel
byconvection;nofans.
•32°F–104°F(0°C–40°C);relativehumiditylessthan
90%,non-condensing.
Standards
•ComplieswithCE.
Power
•Inputpower:230V~50/60Hz,phase-to-neutral.
•BranchCircuitCapacity:10A
–Minimumload:0W
•NumberofCircuits:3–24
•BranchCircuitBreakers:IEC-ratedthermalmagnetic.
AICrating(otherratingsavailable):6000A
•Lightningstrikeprotection:MeetsANSI/IEEEstandard
62.41-1980.Canwithstandvoltagesurgesofupto
6000V~andcurrentsurgesofupto3000A.
•10-yearpowerfailurememory:Automaticallyrestores
lighting to scene selected prior to power interruption.
Sources/Load Types
Operatesthesesourceswithasmoothcontinuous
SquareLawdimmingcurveoronafullconduction,
non-dimmingbasis:
•Incandescent(Tungsten)/Halogen
•MagneticLow-VoltageTransformer
•LEDdriversspeciedbythemanufacturertowork
with forward-phase dimming controls. *
•Electroniclow-voltagetransformersspeciedbythe
manufacturertoworkwithforward-phasedimming
controls.
•LutronElectronicFluorescentDimmingBallasts
•MagneticFluorescentLampBallasts
•Optionalmodulesallowforcontrolof010V-,DSI,
andPWMloadtypes.
•OperatesHIDsourcesonafull-conduction,
non-dimmingbasis.
Specifications: 230 V~ (CE)
* LutroncannotguaranteecompatibilitywithuntestedLEDdrivers.RefertotheLEDProductSelectiontoolatwww.lutron.com/ledtoolforalistof
compatibleproducts.
6
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f 7 09.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wiring
•Internal:PrewiredbyLutron.
•Systemcommunications:Low-voltageIECPELV/NEC®
Class2wiringconnectsdimmingpanelstoother
components.
•Line(mains)voltage:Feed,load,andcontrolcircuit
wiringonly;nootherwiringorassemblyrequired.
Filter Chokes
•Loadcurrentrisetimeismeasuredata90-degree
conductionangle,with120V~ input power.
•10–90%ofloadcurrentwaveform:
–350µSecrisetimeat50%dimmercapacity.
–400µSecrisetimeat100%dimmercapacity.
•0–100%ofloadcurrentwaveform:
–525µSecrisetimeat50%dimmercapacity.
–600µSecrisetimeat100%dimmercapacity.
•Atnopointinthewaveformcantherateofcurrent
changeexceed300mAperµSec.
•ConsultLutronforhigherrisetimeoptions.
Dimming Cards
•Panelcurrentratingsarelistedforcontinuous
operation.
•RTISSltercircuittechnologycompensatesfor
incominglinevoltagevariations:Novisibleickerwith
+/–2%changeinRMSvoltage/cycleand+/–2%Hz
changeinfrequency/second.
•Arclessrelayair-gapOFFswitches(oneperload
circuit)ensureopenloadcircuitswhenOFFfunction
is selected; eliminate arcing at mechanical contacts
when loads are switched.
Physical Design
•Enclosure:NEMA-Type1(Type2availableonrequest),
IP-20protection;16U.S.GaugeSteel;indooruseonly.
•Weight:30to175lb(14to80kg).
•Mounting:Surface-mountonly;allowspacefor
ventilating.
Environment/Heat Dissipation
•Patented,ribbedaluminumheatsinkbasecoolspanel
byconvection;nofans.
•32°F–104°F(0°C–40°C);relativehumiditylessthan
90%,non-condensing.
Power
•Inputpower:220–240V~50/60Hz,
phase-to-neutral.
•BranchCircuitCapacity:16Aor10A
–Minimumload:0W
•NumberofCircuits:3–24
•BranchCircuitBreakers:IEC-ratedthermalmagnetic.
AICrating(otherratingsavailable):6000A
•Lightningstrikeprotection:MeetsANSI/IEEEstandard
62.41-1980.Canwithstandvoltagesurgesofupto
6000V~andcurrentsurgesofupto3000A.
•10-yearpowerfailurememory:Automaticallyrestores
lighting to scene selected prior to power interruption.
Sources/Load Types
Operatesthesesourceswithasmoothcontinuous
SquareLawdimmingcurveoronafull-conduction,
non-dimmingbasis:
•Incandescent(Tungsten)/Halogen
•MagneticLow-VoltageTransformer
•LEDdriversspeciedbythemanufacturertowork
with forward-phase dimming controls. *
•Electroniclow-voltagetransformersspeciedbythe
manufacturertoworkwithforward-phasedimming
controls.
•LutronElectronicFluorescentDimmingBallasts
•MagneticFluorescentLampBallasts
•Optionalmodulesallowforcontrolof0–10V-,DSI,
andPWMloadtypes.
•OperatesHIDsourcesonafull-conduction,
non-dimmingbasis.
Specifications: 220 – 240 V~ (non-CE)
* LutroncannotguaranteecompatibilitywithuntestedLEDdrivers.RefertotheLEDProductSelectiontoolatwww.lutron.com/ledtoolforalistof
compatibleproducts.
7
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f809.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Prefix
•GP:GPDimmingPanel
Number of Load Circuits
•Indicatesnumberofloadcircuitsinthepanel
Voltage
•120:120V~
•277
:277V~
Feed Type
•2:1-phase,2-wire
•3:1-phase,3-wire(splitphase)
•4:3-phase,4-wire
Panel Feed
•ML:MainLugsonly
•Mxx:MainBreakerwithxx=breakersizeinAmps
Branch Circuit Breakers
•20:20Abranchcircuitbreakers
•15:15Abranchcircuitbreakers
Custom Panel Suffix
•Indicatespanelwithspecialoptions
How to Build a GP Model Number: 120/277 V~
Prefix Feed
Type
Number
of Load
Circuits
Voltage Panel
Feed
Branch
Circuit
Breakers
Custom Panel Suffix
G P 12 120 4 ML 20 CGPXXX
8
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f 9 09.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Prefix
•GP:GPDimmingPanel
Number of Load Circuits
•Indicatesnumberofloadcircuitsinthepanel
Voltage
•230:CE
Feed Type
•2:1-phase,2-wire
•4:3-phase,4-wire
Panel Feed
•IS:IsolatorSwitch
Branch Circuit Breakers
•10:10Abranchcircuitbreakers
Region Suffix
•CE:230V~
Custom Panel Suffix
•Indicatespanelwithspecialoptions
How to Build a GP Model Number: 230 V~
Prefix Feed
Type
Number
of Load
Circuits
Voltage Panel
Feed
Branch
Circuit
Breakers
Custom Panel Suffix
G P 12 230 4 IS 1 0 CE CGPXXX
Region
Suffix
9
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f 10 09.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Prefix
•GP:GPDimmingPanel
Number of Load Circuits
•Indicatesnumberofloadcircuitsinthepanel
Voltage
•240:220–240V~
Feed Type
•2:1-phase,2-wire
•4:3-phase,4-wire
Panel Feed
•IS:IsolatorSwitch
Branch Circuit Breakers
•16:16Abranchcircuitbreakers
•10:10Abranchcircuitbreakers
Region Suffix
•AU:220–240V~
Custom Panel Suffix
•Indicatespanelwithspecialoptions
How to Build a GP Model Number: 220 240 V~
Prefix Feed
Type
Number
of Load
Circuits
Voltage Panel
Feed
Branch
Circuit
Breakers
Custom Panel Suffix
G P 12 240 4 IS 1 6 AU CGPXXX
Region
Suffix
10
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f 11 09.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Ratings: 120/277 V~
GP3/4 Mini-Size Models
1
120 V~ Power
Panel Branch Ratings
Number
of Circuits
Feed Type
Maximum
Feed
Circuit
Breakers
2
Maximum Dimmed
Hot Load
3
GP3
1-phase,2-wire
40A 15A 1500W/VA
40A 20A 2000W/VA
1-phase, 3-wire
30A 15A 1500W/VA
40A 20A 2000W/VA
3-phase, 4-wire
15A 15A 1500W/VA
20A 20A 2000W/VA
GP4 Feed-through
20A 15A
4
1500W/VA
20A 20A
4
2000W/VA
277 V~ Power
Panel Branch Ratings
Number
of Circuits
Feed Type
Maximum
Feed
Circuit
Breakers
2
Maximum Dimmed
Hot Load
3
GP3
1-phase,2-wire 40A 20A 4500W/VA
3-phase, 4-wire 20A 20A 4500W/VA
GP4 Feed-through 20A 20A
4
4500W/VA
1
Onlystandardpanelslisted.ConsultLutronforfurtheroptions.
2
20/16A,15/12Acontinuousloadrating.
3
Measuredcurrentwillnotexceedcontinuousloadratingduetovoltagedropinthedimmer.
4
Breakerslocatedindistributionpanelsuppliedbyothers.
continued on next page…
11
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f1209.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Ratings: 120/277 V~(continued)
GP8 – 24 Standard-Size Models
1
120 V~ Power
Panel Branch Ratings
Number
of Circuits
Feed Type Panel Feed
Maximum
Feed
Circuit
Breakers
2
Maximum Dimmed
Hot Load
3
GP8
1-phase,2-wire MainLugsOnly
175A 15A 1500W/VA
175A 20A 2000W/VA
1-phase, 3-wire
MainLugsOnly
175A 15A 1500W/VA
175A 20A 2000W/VA
60AMainBreaker 60A 15A 1500W/VA
80AMainBreaker 80A 20A 2000W/VA
3-phase, 4-wire
MainLugsOnly
175A 15A 1500W/VA
175A 20A 2000W/VA
50AMainBreaker 50A 15A 1500W/VA
60AMainBreaker 60A 20A 2000W/VA
GP12
1-phase, 3-wire
MainLugsOnly
175A 15A 1500W/VA
175A 20A 2000W/VA
3-phase, 4-wire
MainLugsOnly
175A 15A 1500W/VA
175A 20A 2000W/VA
60AMainBreaker 60A 15A 1500W/VA
80AMainBreaker 80A 20A 2000W/VA
GP16
1-phase, 3-wire
MainLugsOnly
175A 15A 1500W/VA
175A 20A 2000W/VA
125AMainBreaker 125A 15A 1500W/VA
175AMainBreaker 175A 20A 2000W/VA
3-phase, 4-wire
MainLugsOnly
175A 15A 1500W/VA
175A 20A 2000W/VA
100AMainBreaker 100A 15A 1500W/VA
125AMainBreaker 125A 20A 2000W/VA
GP20 3-phase, 3-wire
MainLugsOnly
175A 15A 1500W/VA
175A 20A 2000W/VA
110AMainBreaker 110A 15A 1500W/VA
150AMainBreaker 150A 20A 2000W/VA
GP24 3-phase, 4-wire
MainLugsOnly
175A 15A 1500W/VA
175A 20A 2000W/VA
125AMainBreaker 125A 15A 1500W/VA
175AMainBreaker 175A 20A 2000W/VA
1
Onlystandardpanelslisted.ConsultLutronforfurtheroptions.
2
20/16A,15/12Acontinuousloadrating.
3
Measuredcurrentwillnotexceedcontinuousloadratingduetovoltagedropinthedimmer.
continued on next page…
12
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f 13 09.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Ratings: 120/277 V~(continued)
GP8 – 24 Standard-Size Models
1
(continued)
277 V~ Power
Panel Branch Ratings
Number
of Circuits
Feed Type Panel Feed
Maximum
Feed
Circuit
Breakers
Maximum Dimmed
Hot Load
2
GP8
1-phase,2-wire MainLugsOnly 175A 20A 4500W/VA
3-phase, 4-wire
MainLugsOnly 175A 20A 2000W/VA
60AMainBreaker 60A 20A 2000W/VA
GP12 3-phase, 4-wire
MainLugsOnly 175A 20A 2000W/VA
80AMainBreaker 80A 20A 2000W/VA
GP16 3-phase, 4-wire
MainLugsOnly 175A 20A 2000W/VA
125AMainBreaker 125A 20A 2000W/VA
1
Onlystandardpanelslisted.ConsultLutronforfurtheroptions.
2
Measuredcurrentwillnotexceedcontinuousloadratingduetovoltagedropinthedimmer.
continued on next page…
13
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f 14 09.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Ratings: 120/277 V~(continued)
GP36 – 144 Large-Size Models
1
120 V~ Power
Panel Branch Ratings
Number
of Circuits
Feed Type Panel Feed
Maximum
Feed
Circuit
Breakers
2
Maximum Dimmed
Hot Load
3
GP36 3-phase, 4-wire
MainLugsOnly
750A 15A 1500W/VA
750A 20A 2000W/VA
200AMainBreaker 200A 15A 1500W/VA
250AMainBreaker 250A 20A 2000W/VA
GP48 3-phase, 4-wire
MainLugsOnly
750A 15A 1500W/VA
750A 20A 2000W/VA
250AMainBreaker 250A 15A 1500W/VA
350AMainBreaker 350A 20A 2000W/VA
GP60 3-phase, 4-wire
MainLugsOnly
750A 15A 1500W/VA
750A 20A 2000W/VA
300AMainBreaker 300A 15A 1500W/VA
400AMainBreaker 400A 20A 2000W/VA
GP72 3-phase, 4-wire
MainLugsOnly
750A 15A 1500W/VA
750A 20A 2000W/VA
350AMainBreaker 350A 15A 1500W/VA
400AMainBreaker 400A 20A 2000W/VA
GP9 6 -144 3-phase, 4-wire MainLugsOnly
750A 15A 1500W/VA
750A 20A 2000W/VA
277 V~ Power
Panel Branch Ratings
Number
of Circuits
Feed Type Panel Feed
Maximum
Feed
Circuit
Breakers
2
Maximum Dimmed
Hot Load
3
GP36 3-phase, 4-wire
MainLugsOnly 750A 20A 4500W/VA
250AMainBreaker 250A 20A 4500W/VA
GP48 3-phase, 4-wire
MainLugsOnly 750A 20A 4500W/VA
350AMainBreaker 350A 20A 4500W/VA
GP60 3-phase, 4-wire
MainLugsOnly 750A 20A 4500W/VA
400AMainBreaker 400A 20A 4500W/VA
GP72 3-phase, 4-wire
MainLugsOnly 750A 20A 4500W/VA
400AMainBreaker 400A 20A 4500W/VA
GP9 6 -144 3-phase, 4-wire MainLugsOnly 750A 20A 4500W/VA
1
Onlystandardpanelslisted.ConsultLutronforfurtheroptions.
2
20/16A,15/12Acontinuousloadrating.
3
Measuredcurrentwillnotexceedcontinuousloadratingduetovoltagedropinthedimmer.
14
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f1509.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Ratings: 230 V~
GP3/4 Mini-Size Models
1
230 V~ (CE) Power
Number
of Circuits
Feed Type
Maximum
Feed
Panel Feed /
Branch Circuit Breakers
GP3
1-phase,2-wire 30A 10A
3-phase, 4-wire 10A 10A
GP4 Feed-through 10A 10A
2
1
Onlystandardpanelslisted.ConsultLutronforfurtheroptions.
2
Breakerslocatedindistributionpanelsuppliedbyothers.
GP8 – 24 Standard-Size Models
1
230 V~ (CE) Power
Number
of Circuits
Feed Type Panel Feed
Maximum
Feed
Branch Circuit Breakers
GP8
1-phase,2-wire IsolatorSwitch 125A 10A
3-phase, 4-wire IsolatorSwitch 125A 10A
GP12 3-phase, 4-wire IsolatorSwitch 125A 10A
GP16 3-phase, 4-wire IsolatorSwitch 125A 10A
GP20 3-phase, 4-wire IsolatorSwitch 125A 10A
GP24 3-phase, 4-wire IsolatorSwitch 125A 10A
1
Onlystandardpanelslisted.ConsultLutronforfurtheroptions.
15
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f 16 09.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Ratings: 220 – 240 V~
GP3/4 Mini-Size Models
1
220 – 240 V~ Power
Number
of Circuits
Feed Type
Maximum
Feed
Panel Feed /
Branch Circuit Breakers
GP3
1-phase,2-wire
48A 16A
30A 10A
3-phase, 4-wire
16A 16A
10A 10A
GP4 Feed-through
16A 16A
10A 10A
GP8 – 24 Standard-Size Models
1
220 – 240 V~ Power
Number
of Circuits
Feed Type Panel Feed
Maximum
Feed
Branch Circuit Breakers
GP8
1-phase,2-wire IsolatorSwitch 125A
16A
10A
3-phase, 4-wire IsolatorSwitch 125A
16A
10A
GP12 3-phase, 4-wire IsolatorSwitch 125A
16A
10A
GP16 3-phase, 4-wire IsolatorSwitch 125A
16A
10A
GP20 3-phase, 4-wire IsolatorSwitch 125A
16A
10A
GP24 3-phase, 4-wire IsolatorSwitch 125A
16A
10A
1
Onlystandardpanelslisted.ConsultLutronforfurtheroptions.
16
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f 17 09.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimensions: GP3/4 Mini-Size Panels
Alldimensionsshownas:in(mm)
Top View
11
(279)
6
1
4
(160)
3
5
8(92)
5
1
8
(130)
1
5
8(41)
7/8in(22mm)diameter
IECPELV/NEC®Class2
wiring only.
Left-Side View
18
(457)
19
1
2
(495)
21
1
8
(537)
11
(279)
9
5
8
(244)
Front View
Keyholesaccept1/4in
(6mm)mountingbolts,
maximum.#10M6
recommended.
Right-Side View
2
3
4(70)
5
1
4(133)
1
1
8(29)
1
3
16(30)
Bottom View
Loadcircuitwiring Feedwiring
2
3
4(70)
1
1
2(38)
5
1
2(140)
1
1
2(38)
11
(279)
17
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f1809.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimensions: GP8 24 Standard-Size Panels
Alldimensionsshownas:in(mm)
Bottom View
Top View
28(711)
12
(304)
4(100)
Suggestedload
wiring entries.
Suggestedfeed
wiring entry.
2(50)2(50)
13
(330)
12
(304)
Right-Side View
Removable
top cover
7/8in(22mm)
diameterIEC
PELV/NEC®
Class2wiring
only.
2(50)
Left-Side View
33
(838)
35
(889)
Front View
28(711)
12(304)
37
(940)
Keyholesaccept5/16in
(8mm)mountingbolts,
maximum.1/4in(M8)
recommended.
18
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f 19 09.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimensions: GP36 Large-Size Panels
Alldimensionsshownas:in(mm)
* Availabletopunchforalternatefeedwiring.
** Availabletopunchforalternateloadcircuitwiring.
Top View
26
1
8(653)
23(580)
14
1
8
(360)
6(150)
5
1
2(140)
Suggestedloadand
feed wiring entry.
Back View
26
1
8(653)
25
1
16(627)
1
7
8(47)
9/16in(14mm)diameter
mountinghole.Use1/2in
(13mm)hardware.
9
1
2
(237)
54
5
16
(1358)
80
(2000)
11
3
4
(294)
Right-Side View
6in(150mm)
diameter*
3/4in(20mm)
diameterIEC
PELV/NEC®
Class2wiring
only.
Left-Side View
10
1
2
(263)
14
1
8
(353)
87
(2175)
84
3
4
(2120)
86
(2170)
54
1
2
(1363)
30
1
2
(763)
6
1
2
(163)
4in(100mm)
diameter**
Bottom View
24
1
14(633)
23
5
16(583)
26
1
8(653)
2
3
16(55)2(50)
1
7
8(47)1
1
8(28)
9/16in(14mm)diameter
mountinghole.Use1/2in
(13mm)hardware.
3in(75mm)squarearea*
8(200)
1
5
16(33)
11
(275)
11
15
16
(298)
14
1
8
(353)
19
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f2009.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimensions: GP48/60/72 Large-Size Panels
Alldimensionsshownas:in(mm)
* Availabletopunchforalternatefeedwiring.
** Availabletopunchforalternateloadcircuitwiring.
52
5
16(1308)
23(580) 23(580)
14
1
8
(360)
6(150)
5
1
2(140)
Top View
Suggestedloadand
feed wiring entry.
51
1
8(1278)
27
1
4(681)
25
1
16(627) 1
7
8(48)
50(1250)
Back View
9/16in(14mm)diameter
mountinghole.Use1/2in
(13mm)hardware.
9
1
2
(237)
54
5
16
(1358)
80
(2000)
11
3
4
(294)
Right-Side View
6in(150mm)
diameter*
3/4in(20mm)
diameterIEC
PELV/NEC®
Class2wiring
only.
10
1
2
(263)
14
1
8
(353)
Left-Side View
87
(2175)
84
3
4
(2120)
86
(2170)
54
1
2
(1363)
30
1
2
(763)
6
1
2
(163)
4in(100mm)
diameter**
Bottom View
50
7
16(1261)
49
7
16(1236)
24
5
16(633)
28
15
16(723)
23
5
16(583)
28(700)
2
3
16(55)
1
7
8(48)
8(200)
1
5
16(33)
11
(275)
11
15
16
(298)
14
1
8
(353)
9/16in(14mm)diameter
mountinghole.Use1/2in
(13mm)hardware.
3in(75mm)squarearea*
20
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f2109.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimensions: GP96 144 Large-Size Panels(twounitsinstalledback-to-back)
Alldimensionsshownas:in(mm)
* Availabletopunchforalternatefeedwiring.
** Availabletopunchforalternateloadcircuitwiring.
52
5
16(1308)
23(580) 23(580)
28
1
4
(720)
14
1
8
(360)
6(150)
5
1
2(140)
Top View
Suggestedloadand
feed wiring entry.
51
1
8(1278)
27
1
4(681)
25
1
16(627) 1
7
8(48)
50(1250)
Back View of One Unit
9/16in(14mm)diameter
mountinghole.Use1/2in
(13mm)hardware.
87
(2175)
84
3
4
(2120)
86
(2170)
54
1
2
(1363)
30
1
2
(763)
6
1
2
(163)
10
1
2
(263)
14
1
8
(353)
Left-Side View
4in(100mm)
diameter**
3/4in(20mm)
diameterIEC
PELV/NEC®
Class2wiring
only.
Bottom View
50
7
16(1261)
49
7
16(1236)
24
5
16(633)
28
15
16(723)
23
5
16(583)
28(700)
2
3
16(55)
1
7
8(47)
3in(75mm)
squarearea*
8(200)
1
5
16(33)
11
(275)
11
5
16
(298)
14
1
8
(353)
9/16in(14mm)diameter
mountinghole.Use1/2in
(13mm)hardware.
9
1
2
(237)
54
5
16
(1358)
80
(2000)
11
3
4
(294)
Right-Side View
6in(150mm)
diameter*
3/4in(20mm)
diameterIEC
PELV/NEC®
Class2wiring
only.
21
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f2209.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
•Surfacemountindoors.
•Panelgeneratesheat.Mountonlywhereambient
temperaturewillbe0–40°C(32–104°F).
•Thisequipmentisaircooled.Donotblockventsor
warrantywillbevoid.Leave12in(310mm)clearances
above,below,andinfrontofpanel.Noclearance
necessary on sides.
•Reinforcewallstructureforweightandlocalcodes.
Panel Maximum
BTUs/Hour
Weight (without
packaging)
G P 3 / 4 685 30lb(14kg)
•Dimmingpanelswillhumslightlyandinternalrelayswill
clickwhileinoperation.Mountwhereaudiblenoiseis
a c c e p t a b l e .
•Mountpanelssoline(mains)voltagewiringisatleast
6ft(1.8m)fromsoundorelectronicequipmentand
wiring.
•GPpanelsmustbemountedwithin7°oftruevertical.
•Formaximumfeedandwiresizes,consultWiring
Overview page.
Note
:Waterdamagespanels.Installwheretheywill
not get wet.
Mounting: GP3/4 Mini-Size Panels
Front View
IECPELV/NEC®
Class2wiring
Terminalblocks
for load circuits
Branchcircuit
breakers
Feedwiring
Loadcircuit
wiring
Raceway
Side View
12in(310mm)
minimum
12in(310mm)
minimum
IECPELV/NEC®
Class2wiring
12in(310mm)
minimum
Wall
22
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f2309.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
•Surfacemountindoors.
•Panelgeneratesheat.Mountonlywhereambient
temperaturewillbe32–104°F(0–40°C).
•Thisequipmentisaircooled.Donotblockventsor
warrantywillbevoid.Leave12in(310mm)clearances
above,below,andinfrontofpanel.Leaveclearance
onsidesforIECPELV/NEC®Class2wiring.
•Reinforcewallstructureforweightandlocalcodes.
Panel Maximum
BTUs/Hour
Weight (without
packaging)
GP8 1365
115lb(52kg)
GP12 2045 130lb(59kg)
GP16 2725 145lb(66kg)
GP20 3405 160lb(73kg)
GP24 4085 175lb(80kg)
•Dimmingpanelswillhumslightlyandinternalrelayswill
clickwhileinoperation.Mountwhereaudiblenoiseis
a c c e p t a b l e .
•Mountpanelssoline(mains)voltagewiringisatleast
6ft(1.8m)fromsoundorelectronicequipmentand
wiring.
•GPpanelsmustbemountedwithin7°oftruevertical.
•Formaximumfeedandwiresizes,consultWiring
Overview page.
Note
:Waterdamagespanels.Installwheretheywill
not get wet.
Mounting: GP8 24 Standard-Size Panels
Front View
Ceiling
Raceway
Feedwiring
Loadcircuit
wiring
Terminalblocks
for load circuits
IECPELV/NEC®
Class2wiring
Mainlugsor
mainbreaker
Side View
12in(310mm)
minimum
12in(310mm)
minimum
IECPELV/NEC®
Class2wiring
Airow
12in(310mm)
minimum
Wall
23
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f2409.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Atleast8.67ft(2650mm)betweentheoorandthe
suspendedceilingisrequiredforthislayout.
Note:Waterdamagespanels.Installwheretheywill
not get wet.
Mounting One Panel Above Another
* 6in(160mm)minimumapprovedforthislayoutonly.
Side View(GP8–24)
Suspended
ceiling depth
Mountingholes
IECPELV/NEC®
Class2wiring
Airow
Mountingholes
Wall
Front View(GP8–24)
Ceiling
Raceway
Loadcircuit
wiring
Feedwiring
Mainlugsor
mainbreaker
IECPELV/NEC®
Class2wiring
12in
(310mm)
minimum
8.67ft
(2650mm)
minimum
7.5ft
(2280mm)
6.5ft
(1950mm)
3 ft 4
5
8in
(1030mm)
6in(160mm)
minimum*
12in
(310mm)
minimum
24
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f2509.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
•Surfacemountindoors.
•Panelgeneratesheat.Mountonlywhereambient
temperaturewillbe32–104°F(0–40°C).
•Thisequipmentisaircooled.Donotblockventsor
warrantywillbevoid.Leave12in(310mm)clearances
aboveandinfrontofpanel.Leaveclearanceonsides
forIECPELV/NEC®Class2wiring.
Panel Maximum
BTUs/Hour
Weight (without
packaging)
GP36 4350
325lb(147kg)
GP48 5800 550lb(250kg)
GP60 7250 600lb(273kg)
GP72 8700 650lb(295kg)
•Mountpanelonoorandagainstawall.Use1/2in
(13mm)mountingbolts.
•Dimmingpanelswillhumslightlyandinternalrelayswill
clickwhileinoperation.Mountwhereaudiblenoiseis
a c c e p t a b l e .
•Mountpanelssoline(mains)voltagewiringisatleast
6ft(1.8m)fromsoundorelectronicequipmentand
wiring.
•GPpanelsmustbemountedwithin7°oftruevertical.
GP36-72 Mounting
GP36consistsoftherightsidemoduleonly.Mountas
shown.
Alternate Conduit Locations
•Runfeedwiringinfrombottom.
•Runloadcircuitwiringinfromleftside.
Note:Waterdamagespanels.Installwheretheywill
not get wet.
Mounting: GP36 72 Large-Size Panel
Side View
12in(310mm)
minimum
3ft(930mm)
minimum
IECPELV/NEC®
Class2wiring
Airow
Wall
Front View
Ceiling
Raceway
Feedandload
circuit wiring
Mainlugsor
mainbreaker
IECPELV/NEC®
Class2wiring
Terminalblocks
for load circuits
GP36
G P4 8 – 7 2
25
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f2609.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
•Surfacemountindoors.
•Panelgeneratesheat.Mountonlywhereambient
temperaturewillbe32–104°F(0–40°C).
•Thisequipmentisaircooled.Donotblockventsor
warrantywillbevoid.Leave12in(310mm)clearances
aboveandinfrontofpanel.Leaveclearanceonsides
forIECPELV/NEC®Class2wiring.
Panel Maximum
BTUs/Hour
Weight (without
packaging)
GP9 6 -144 174 0 0
1300lb(590kg)
•Mountpanelonoorandagainstawall.Use1/2in
(13mm)mountingbolts.
•Dimmingpanelswillhumslightlyandinternalrelayswill
clickwhileinoperation.Mountwhereaudiblenoiseis
a c c e p t a b l e .
•Mountpanelssoline(mains)voltagewiringisatleast
6ft(1.8m)fromsoundorelectronicequipmentand
wiring.
•GPpanelsmustbemountedwithin7°oftruevertical.
GP96-144 Mounting
•Allowairowand3ft(92cm)clearancefromfronts/
sides of panel as shown.
•NotetheextraIECPELV/NEC®Class2wiring.
Alternate Conduit Locations
•Runfeedwiringinfrombottom.
•Runloadcircuitwiringinfromleftside.
Note:Waterdamagespanels.Installwheretheywill
not get wet.
Mounting: GP96 144 Large-Size Panel
Front View
Ceiling
Raceway
Feedandload
circuit wiring
Mainlugsor
mainbreaker
IECPELV/NEC®
Class2wiring
Terminalblocks
for load circuits
Side View
12in(310mm)
minimum
3ft(930mm)
minimum
IECPELV/NEC®
Class2wiring
Airow
Wall
26
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f2709.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wire Sizes
120/277 V~
•PowerFeed:14AWG(2.0mm
2
)to8AWG(6.0mm
2
)
•NeutralFeed:14AWG(2.0mm
2
)to6AWG(10.0mm
2
)
•DimmedLine/Hot:14AWG(2.0mm
2
)to10AWG(4.0mm
2
)
•LoadNeutral:14AWG(2.0mm
2
)to6AWG(10.0mm
2
)
230 V~
(CE), 220 240 V~
•PowerFeed:18AWG(1.0mm
2
)to4AWG(25.0mm
2
)
•NeutralFeed:14AWG(2.0mm
2
)to6AWG(10.0mm
2
)
•DimmedLine/Hot:14AWG(2.0mm
2
)to10AWG(4.0mm
2
)
•LoadNeutral:14AWG(2.0mm
2
)to6AWG(10.0mm
2
)
Wiring Tips
WireGP3Mini-Sizepanelssimilarlytoalighting
distributionpanel:
•Runfeedandloadwiring;nootherwiringorassembly
required.
•Commonneutralsarenotpermitted.Runseparate
neutrals for each load circuit.
GP3 panels can provide temporary lighting.
•Wireallloads.
•Donotremovethebypassjumpersthatprotectthe
dimming modules.
•Usebranchcircuitbreakerstoswitchlightsonandoff.
Wiring Overview: GP3 Mini-Size Panels(120/277V~,230V~[CE],220–240V~)
SH
1
H
1
DH
2
SH
2
DH
3
SH
3
DH
1
H
2
H
3
SL
1
L
1
DL
2
SL
2
DL
3
SL
3
DL
1
L
2
L
3
IECPELV/NEC®
Class2wiring
Terminalblock
Ground
PanelFeedWiring
PowerFeed
(Line/Hot)
Neutral
Feed
SH
1
H
1
DH
2
SH
2
DH
3
SH
3
DH
1
H
2
H
3
SL
1
L
1
DL
2
SL
2
DL
3
SL
3
DL
1
L
2
L
3
Load
Bypassjumpers
(Donotremove)
TypicalLoadCircuit
Dimmed
Line/Hot
Load
Neutral
120/277 V~
SH
1
H
1
DH
2
SH
2
DH
3
SH
3
DH
1
H
2
H
3
SL
1
L
1
DL
2
SL
2
DL
3
SL
3
DL
1
L
2
L
3
Load
Bypassjumpers
(Donotremove)
TypicalLoadCircuit
Dimmed
Line/Hot
Load
Neutral
230 V~ (CE),
220 – 240 V~
OR
27
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f2809.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wire Sizes
•PowerFeed:14AWG(2.0mm
2
)to10AWG(4.0mm
2
)
•NeutralFeed:14AWG(2.0mm
2
)to10AWG(4.0mm
2
)
•DimmedLine/Hot:14AWG(2.0mm
2
)to10AWG(4.0mm
2
)
•LoadNeutral:14AWG(2.0mm
2
)to10AWG(4.0mm
2
)
Wiring Tips
WireGP4Mini-Sizepanelssimilarlytoalighting
distributionpanel:
•Runfeedandloadwiring;nootherwiringorassembly
required.
•Commonneutralsarenotpermitted.Runseparate
neutrals for each load circuit.
GP4 panels can provide temporary lighting.
•Wireallloads.
•Donotremovethebypassjumpersthatprotectthe
dimming modules.
Wiring Overview: GP4 Mini-Size Panels(120/277V~,230V~[CE],220–240V~)
PanelFeedWiring
PowerFeed
(Line/Hot)
Neutral
Feed
IECPELV/NEC®
Class2wiring
Terminalblock
Ground
DH
1
SH
1
H
1
N
1
N
1
DH
2
SH
2
H
2
N
2
N
2
Load
Bypassjumpers
(Donotremove)
TypicalDimmingLeg
Dimmed
Line/Hot
Load
Neutral
28
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f2909.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wire Sizes
•PowerFeedStandardMainLugs:14AWG(2.0mm
2
)to2/0AWG(70.0mm
2
)
•PowerFeedDual-TapMainLugs:6AWG(10.0mm
2
)to4/0AWG(120mm
2
)
•NeutralFeed:6AWG(10.0mm
2
)to350mcm(177.0mm
2
)
•DimmedLine/Hot:14AWG(2.0mm
2
)to10AWG(4.0mm
2
)
•LoadNeutral:14AWG(2.0mm
2
)to6AWG(10.0mm
2
)
Wiring Tips
WireGP8–24Standard-Size
panels similarly to a lighting
distributionpanel:
•Runfeedandloadwiring;noother
wiringorassemblyrequired.
•Commonneutralsarenotpermitted.
Runseparateneutralsforeachload
circuit.
GP8–24panelscanprovide
temporary lighting.
•Wireallloads.
•Donotremovethebypassjumpers
that protect the dimming modules.
•Usebranchcircuitbreakerstoswitch
lights on and off.
Wiring Overview: GP8 24 Standard-Size Panels(120/277V~)
DH
1
SH
1
H
1
DH
1
SH
1
PanelFeedWiring
PowerFeed
(Line/Hot)
Neutral
Feed
DH
1
SH
1
H
1
DH
1
SH
1
TypicalLoadCircuit
Load
Bypassjumpers
(Donotremove)
Load
Neutral
Dimmed
Line/Hot
Terminalblock
Branchcircuit
breakers
IECPELV/NEC®
Class2wiring
29
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f 30 09.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wire Sizes
•PowerFeed:14AWG(2.0mm
2
)to2AWG(35.0mm
2
)
•NeutralFeed:14AWG(2.0mm
2
)to2AWG(35.0mm
2
)
•DimmedLine/Hot:14AWG(2.0mm
2
)to10AWG(4.0mm
2
)
•LoadNeutral:14AWG(2.0mm
2
)to10AWG(4.0mm
2
)
Wiring Tips
WireGP8–24Standard-Size
panels similarly to a lighting
distributionpanel.
•Runfeedandloadwiring;noother
wiringorassemblyrequired.
•Commonneutralsarenot
permitted.Runseparateneutrals
for each load circuit.
GP8–24panelscanprovide
temporary lighting.
•Wireallloads.
•Donotremovethebypassjumpers
that protect the dimming modules.
•Usebranchcircuitbreakersto
switch lights on and off.
Wiring Overview: GP8 24 Standard-Size Panels(230V~[CE],220–240V~)
DL
1
SL
1
L
1
DL
2
SL
2
L
2
N
1
N
1
PanelFeedWiring
PowerFeed
(Line/Hot)
Neutral
Feed
DL
1
SL
1
L
1
DL
2
SL
2
L
2
N
1
N
1
TypicalLoadCircuit
Load
Bypassjumpers
(Donotremove)
Dimmed
Live
Load
Neutral
Terminalblock
Branchcircuit
breakers
IECPELV/NEC®
Class2wiring
30
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f 31 09.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Wire Sizes
•PanelFeedWiring:
–Mainlugsonly:Parallel4AWGto500kcmil(mcm)
–200Ato400Amainbreakers:1/0AWG(50mm
2
)to600kcmil(mcm)
•DimmedLine/Hot:14AWG(2.0mm
2
)to10AWG(4.0mm
2
)
•LoadNeutral:14AWG(2.0mm
2
)to6AWG(10.0mm
2
)
Wiring Tips
WireGP36–144Large-Sizepanelssimilarlytoa
lightingdistributionpanel:
•Runfeedandloadwiring;nootherwiringorassembly
required.
•Commonneutralsarenotpermitted.Runseparate
neutrals for each load circuit.
GP36–144panelscanprovidetemporarylighting.
•Wireallloads.
•Donotremovethebypassjumpersthatprotectthe
dimming modules.
•Usebranchcircuitbreakerstoswitchlightsonandoff.
Wiring Overview: GP36 144 Large-Size Panels(120/277V~)
* VariesdependingonMBorMLO.Seemodelnumberspage.
DH SH HDHSH
PanelFeedWiring
PowerFeed
(Line/Hot)*
Neutral
Feed*
DH SH HDHSH
TypicalLoadCircuit
Load
Bypassjumpers
(Donotremove)
Load
Neutral
Dimmed
Line/Hot
Branchcircuitbreakers
IECPELV/NEC®Class2wiring
Terminalblock
31
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f3209.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
•Allloadcircuitwiringis14AWG(2.0mm
2
)to10AWG(4.0mm
2
).
•SwitchedHot(SH)mustbeusedfor3-wirecontrolledloadsonly;usetheDimmedHot(DH)forallnon-dimload
types.
•ConsultWiring Overview page for appropriate neutral location.
Load Circuits: 120/277 V~ (GP3–144)
Wiring for Lutron Hi-lume A-Series L3D drivers, and Lutron Hi-lume fluorescent dimming ballasts
SH
1
H
1
DH
1
N
GPDimmingPanel
LoadTerminals
Lutron3-Wire
BallastorLED
Driver
Load
Neutral(White)
Red
Red
Blue
Blue
Ground
DimmedHot(Orange)
SwitchedHot(Black)
Bypassjumpers
(Donotremove)
Wiring for 2-Wire Load Types
N
SH
1
H
1
DH
1
GPDimmingPanel
LoadTerminals
Load
Neutral(White)
DimmedHot(Orange)
Bypassjumpers
(Donotremove)
LutronHi-lume120V~
dimmingballastshown.
Wiring for Lutron GRX-TVM2 for 0– 10 V, PWM, DSI, and DALI (intensity broadcast only) Load Types
1
+
_
1
2
+
_
2
L
1
N
1
DL
1
L
2
N
2
DL
2
GPDimmingPanel
H
+
N
GR X-T VMTerminalBlock
Load
Neutral(White)
DimmedLive(Orange)
Bypassjumpers
(Donotremove)
32
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f 33 09.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
•Allloadcircuitwiringis14AWG(2.0mm
2
)to10AWG(4.0mm
2
).
•UsetheDimmedLive(DL)forallnon-dimloadtypes.
•ConsultWiring Overview page for appropriate neutral location.
Load Circuits: 230 V~ (CE)(GP3–24)
Wiring for Lutron GRX-TVM2 for 0– 10 V, PWM, DSI, and DALI (intensity broadcast only) Load Types
1
+
_
1
2
+
_
2
L
1
N
1
DL
1
L
2
N
2
DL
2
GPDimmingPanel
H
+
N
GR X-T VMTerminalBlock
Load
Neutral(White)
DimmedLive(Orange)
Bypassjumpers
(Donotremove)
Wiring for 2-Wire Load Types
SL
1
L
1
N
1
DL
1
GPDimmingPanel
LoadTerminals
Load
Neutral(White)
DimmedLive(Orange)
Bypassjumpers
(Donotremove)
33
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f 34 09.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
•Allloadcircuitwiringis14AWG(2.0mm
2
)to10AWG(4.0mm
2
).
•SwitchedLive(SL)mustbeusedforHi-lumeFDBorEco-10loadsonly;usetheDimmedLive(DL)forallnon-dim
load types.
•ConsultWiring Overview page for appropriate neutral location.
Load Circuits: 220 240 V~(GP3–24)
Wiring for Lutron Hi-lume or Eco-10(ECO-Series)Fluorescent Dimming Ballasts
SL
1
L
1
N
1
DL
1
GPDimmingPanel
LoadTerminals
Lutron3-Wire
BallastorLED
Driver
Load
Neutral(White)
Red
Red
Blue
Blue
Ground
DimmedLive(Orange)
SwitchedLive(Black)
Bypassjumpers
(Donotremove)
Wiring for 2-Wire Load Types
SL
1
L
1
N
1
DL
1
GPDimmingPanel
LoadTerminals
Load
Neutral(White)
DimmedLive(Orange)
Bypassjumpers
(Donotremove)
LutronHi-lume
220240V~ dimming
ballastshown.
Wiring for Lutron GRX-TVM2 for 0– 10 V, PWM, DSI, and DALI (intensity broadcast only) Load Types
1
+
_
1
2
+
_
2
L
1
N
1
DL
1
L
2
N
2
DL
2
GPDimmingPanel
H
+
N
GR X-T VMTerminalBlock
Load
Neutral(White)
DimmedLive(Orange)
Bypassjumpers
(Donotremove)
34
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f3509.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Low-Voltage IEC PELV/NEC® Class 2 Wiring (AllModels)
•Systemcommunicationsuseslow-voltageIECPELV/NEC®Class2wiring.
•Wiringmustbedaisy-chained.
•Wiringmustrunseparatelyfromline(mains)voltage.
GRAFIK Eye 4000 System
•IECPELV/NEC®Class2wiringlinkrequires:
–Two12AWG(2.5mm
2
)conductorsforcontrolpower.
–Onetwisted,shieldedpairof18AWG(1.0mm
2
)fordatalink.
–One18AWG(1.0mm
2
)conductorforemergency(essential)senseline,frompaneltopanel.
•Totallengthofcontrollinkmaybenomorethan2000ft(610m).
•Approvedlow-voltagecableisavailablefromLutron
1
andBelden.Theseareapprovedwith22AWG(0.5mm
2
)
datalinkwires.
Quantum System
•IECPELV/NEC®Class2wiringlinkrequires:
–Two12AWG(2.5mm
2
)conductorsforcontrolpower.
–Onetwisted,shieldedpairof22AWG(0.5mm
2
)fordatalink.
–One18AWG(1.0mm
2
)conductorforemergency(essential)senseline,frompaneltopanel.
•Totallengthofcontrollinkmaybenomorethan2000ft(610m).
•IfMUX-RPTRinterface
2
andGRX-CBL-46Lcable
1
isused,lengthmaybeupto4000ft(1219m).
•Maximumof32circuitselectorsperlinkor512switchlegs(controllableoutputs)perlink.
•ItisnotnecessarytopositiontheQuantumpanelattheendofthelink;itmaybeinthemiddle.
1
GRX-CBL-46LIECPELV/NEC®Class2wiringcableisavailablefromLutronandcontains:
Two12AWG(2.5mm
2
)conductorsforcontrolpower.
Onetwisted,shieldedpairof22AWG(0.5mm
2
)fordatalink.
One18AWG(1.0mm
2
)conductorforemergency(essential)senseline.
2
OnlytheMUX-RPTRinterfacecanonlybeusedtoextendthelengthofapowerpanellinkinQuantum.ToextendaQSwallstationlink,aQSPS-P1-10-60
mustbeused.
3
Linkterminators(LT-1)arerequiredatthebeginningandENDofeverypowerpanellink.
DimmingPanel
ControlUnit
ControlInterface
Wallstations
DimmingPanel
Quantum
Processor
RefertoQuantumSpecication
ControlUnit
ControlInterface
Wallstations
PowerPanelLink
3
35
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f 36 09.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
* Emergencypower:Theadditional18AWG(1.0mm
2
)wireisa“sense”linefromterminal5ofanotherpanel.Thissenselineallowsanemergency(essential)
lightingpanelto“sense”whennormal(non-essential)powerislost.Ifmorethanoneemergencylightingpanelneedstosensefromaspecicnormal
panel,adedicatedwirebetweeneachpairofnormal(non-essential)andemergency(essential)panelsmayberequired.
Shield/Drain:Connectshieldingasshown.Donotconnecttoground(earth)orcircuitboardofcircuitselector.Connectthebaredrainwiresandcutoff
the outside shield.
IEC PELV/NEC® Class 2 Terminal
Connections: GRAFIK SystemsTM
EachLow-VoltageIECPELV/NEC®Class2terminalcan
acceptonlytwo18AWG(1.0mm
2
)wires.Two12AWG
(2.5mm
2
)conductorswillnott.Connectasshown,
using appropriate wire connectors.
IEC PELV/NEC® Class 2 Panel-to-Panel Wiring: GRAFIK Systems (AllModels)
SELECT CIRCUIT
Data A OK Power Data B OK
1234D5
1234D5 C D
Common
Common
+24VFW
Sense
MUX
MUX
Drain
Drain
MUX
MUX
Circuit
1
2
Link
A
Link
B
SELECT CIRCUIT
Data A OK Power Data B OK
1234D5
1234D5 C D
Common
Common
+24VFW
Sense
MUX
MUX
Drain
Drain
MUX
MUX
Circuit
1
2
Link
A
Link
B
ControlWiring
(2)12AWG(2.5mm
2
)
1:Common
2:24VFW
To
additional
power
panels
Dimming Panel 1 Dimming Panel 2
Tolighting
controls or
processors
Shield/Drain
Shield/Drain
(1)18AWG(1.0mm
2
)
5:SenseLine*
DataLink
(1)shielded,twistedpair22AWG(0.5mm
2
)
3:MUX
4:MUX
1
2
3, 4
5
1
2
3, 4
SELECT CIRCUIT
2
1
Circuit
Data A OK
Power
1234 5D
Common
24VF
W
MUX
MUX
Drain
Sense
1234
D
5
Data B OK
B
Comm
Drain
MUX
MUX
C
D
Link
A
Link
(4)12AWG(2.5mm
2
)
36
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f 37 09.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
* Emergencypower:Theadditional18AWG(1.0mm
2
)wireisa“sense”linefromterminal5ofanotherpanel.Thissenselineallowsanemergency(essential)
lightingpanelto“sense”whennormal(non-essential)powerislost.Ifmorethanoneemergencylightingpanelneedstosensefromaspecicnormal
panel,adedicatedwirebetweeneachpairofnormal(non-essential)andemergency(essential)panelsmayberequired.
Shield/Drain:Connectshieldingasshown.Donotconnecttoground(earth)orcircuitboardofcircuitselector.Connectthebaredrainwiresandcutoff
the outside shield.
** 24V-:OnlyconnectPin2(24V-)betweenpowerpanelsandLUT-ELI-3PHunits.Pin2shouldnotbeconnectedtotheQuantumprocessoronthelink.
IEC PELV/NEC® Class 2 Terminal
Connections: Quantum
EachLow-VoltageIECPELV/NEC®Class2terminalcan
acceptonlytwo18AWG(1.0mm
2
)wiresorone12AWG
to22AWG(2.5mm
2
to0.5mm
2
)wire.Connectas
shown, using appropriate wire connectors.
IEC PELV/NEC® Class 2 Panel-to-Panel Wiring: Quantum
SELECT CIRCUIT
Data A OK Power Data B OK
1234D5
1234D5 C D
Common
Common
+24VFW
Sense
MUX
MUX
Drain
Drain
MUX
MUX
Circuit
1
2
Link
A
Link
B
SELECT CIRCUIT
Data A OK Power Data B OK
1234D5
1234D5 C D
Common
Common
+24VFW
Sense
MUX
MUX
Drain
Drain
MUX
MUX
Circuit
1
2
Link
A
Link
B
ControlWiring
(2)12AWG(2.5mm
2
)
1:Common
2:24VFW
To
additional
power
panels
Dimming Panel 1 Dimming Panel 2
Tolighting
controls or
processors
Shield/Drain
Shield/Drain
(1)18AWG(1.0mm
2
)
5:SenseLine*
DataLink
(1)shielded,twistedpair22AWG(0.5mm
2
)
3:MUX
4:MUX
1
2 * *
3, 4
5
1
2
3, 4
SELECT CIRCUIT
2
1
Circuit
Data A OK
Power
1234 5D
Common
24VF
W
MUX
MUX
Drain
Sense
1234
D
5
Data B OK
B
Comm
Drain
MUX
MUX
C
D
Link
A
Link
(4)12AWG(2.5mm
2
)
37
GP Dimming PanelsGRAFIK Systems Power Equipment
369401f3809.01.17
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Custom Options
Option Description Application
CustomMainBreaker Panelfeaturesacustommainbreakersize Jobswithspecialloadrequirements.
DualTapLugSet Panelacceptsupto225Afeed AsinglefeedwithmultipleGPDimming
Panelsisrequired.
BranchCircuit
Protection
BranchCircuitBreakerswithhigherAICratingsorspecial
breakertypessuchasGFI(GroundFaultInterrupt)
LutronTen-Volt
Module(TVM)
AllowspaneltooperateuorescentballaststhatmeetIEC929
standardsfor0–10V-controlincluding:
•LutronTVEballasts
•0–10V- neon
•PWMuorescent
•Tridonic®DSI(DigitalSerialInterface).
TheTVMcansinkorsource50mA(typically25–50ballasts)
on each circuit
Jobswithuorescentballaststhat
require0–10V-,PWM,orDSIcontrol
MRI PaneldimsDC(DirectCurrent)lightinginMagneticResonance
Imaging(MRI)facilities.
MRIfacilitiesorsoundstudioswhere
standardlighting-controlequipment
won'tworkbecauseofRFIandEMI.
LockingCover •Preventsaccidentalswitchingofcircuitbreakers.
•Addsanadditional2.25in(57.2mm)tothefrontofthepanel.
•AvailableforGP8–GP24only.
Servicecorridorsandpublicareas.
2Link •AllowsaDMX512theatricalconsoletooperatetheload
circuits in the dimming panel.
•AllowsaGRAFIKEye4000Systemtohandle128zones(two
linksof64zones)
•AllowstwoGRAFIKEye4000Systemstosharethesame
dimming panel.
•Controlofarchitecturallightingfrom
DMX512theatricalconsoleisrequired.
•Amixofarchitecturalandtheatrical
lightingexistsonthejob.
•Multiplesystemswherespacefor
panels is limited.
)Lutron,Lutron,GRAFIKEye,GRAFIK6000,Quantum,Softswitch,Hi-lume,andEco-10aretrademarksofLutronElectronicsCo.,Inc.,registeredinthe
U.S.andothercountries.
GRAFIK5000,GRAFIK7000,2LINK,andRTISSaretrademarksofLutronElectronicsCo.,Inc.
TridonicisaregisteredtrademarkofZumtobelAG.
38