SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Fluorescent Dimming Ballasts International EcoSystem® H-Series Architectural Dimming
369382D 1 09.21.12
EcoSystem® H-Series Ballasts
EcoSystem® H-Series digitally addressable ballasts
provide a low-cost, flexible solution for any space in
any application. Architectural dimming to 1% meets
the needs of the most demanding applications.
Individual control with the EcoSystem
® Digital Link
eliminates the need to rewire, reduces design time,
and provides a scalable solution from a small area to
an entire building.
Features
•Continuous,icker-freedimmingfrom100%to1%
for T5, T5HO and T8 lamps
•100%compatible with all EcoSystem
® controls
•CE-marked;ENEC,InMetro,andCCCCertied
•RegisteredundertheConsumerProtection
RegistrationSchemeinSingapore
•S-MarkCertiedforArgentina
•CompatiblewithGRAFIKEye
® QS with EcoSystem®
control units, EnergiSavrNode
TM with EcoSystem®
unit and Quantum
® software, allowing for integration
into an existing or planned EcoSystem
® lighting
control solution
•RoHSCompliant
•100%performancetestedatfactory
•100%burnedinatfactory
•Ballastisprotectedfrommiswiresofanyinput
power to EcoSystem
® control lead, or from lamp
leads to each other and/or ground
•Programmedrapidstartdesignpreheatslamp
cathodes before applying full arc voltage to ensure
full-rated lamp life while dimming and cycling
•Lampsturnontoanydimmedlevelwithoutgoingto
full brightness
•Lowharmonicdistortionthroughouttheentire
dimming range maintains power quality
•Frequencyofoperationensuresthatballastdoes
not interfere with infrared devices operating between
38kHz and 42kHz
EcoSystem
® H-Series, case type M
30mmWx25mmHx359mmL
•Ultra-quietoperation
•End-of-lamp-lifeprotectioncircuitryensuressafe
operation throughout entire lamp life
•Nonvolatilememoryrestoresallballastsettingsafter
power failure
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Fluorescent Dimming Ballasts International EcoSystem® H-Series Architectural Dimming
369382D 2 09.21.12
Specifications
Regulatory Approvals
•ManufacturingfacilitiesemployESDreduction
practices that comply with the requirements of
ANSI/ESDS20.20
•RegisteredundertheConsumerProtection
RegistrationSchemeinSingapore
•S-MarkCertiedforArgentina
•Lutron
® Quality Systems registered to
ISO9001:2008
IEC
•Safety:IEC61347-1;IEC61347-2-3
•Performance:IEC60929
•EMC-Emissions:CISPR15
•EMC-Immunity:IEC61547
•EMC-Harmonics:IEC61000-3-2
CE-Marked; ENEC Certified
•Safety:EN61347-1;EN61347-2-3
•EMC-Emissions:EN55015
•EMC-Immunity:EN61547
•EMC-Harmonics:IEC61000-3-2
•EnergyEfciency:EN50294
InMetro Certified
•Safety:ABNTNBR14417
•Performance:ABNTNBR14418
CCC Certified
•Safety:GB19510.4
•EMC-Emissions:GB17743
•EMC-Harmonics:GB17625.1
Environment
•Minimumlampstartingtemperature:10°C
•Relativehumidity:lessthan90%non-condensing
•SoundRating:ClassA
•Maximumballasttemperature:t
C
=70°C
Performance
•DimmingRange:100%to1%measuredrelativelight
output for T5, T5HO and T8
•LampStarting:programmedrapidstart
•LampCurrentCrestFactor:lessthan1,7
•LampFlicker:nonevisible
•LightOutputVariation:constant±2%lightoutputfor
linevoltagevariationsof±10%
•LampLife:averagelamplifemeetsorexceeds
rating of lamp manufacturer
•PowerFactor:greaterthan0,95
TypicalTotalHarmonicDistortion(THD)lessthan10%*
•FrequencyofOperation:greaterthan42KHz
•BallastFactor(BF):1,0forT5,T5HOandT8lamps
Dimming Range for T5, T5HO and T8 lamps:
BF Dimming Range
(Max/Min)
Dimming
Ratio
1,0 1,00/0,01 100:1
Ballast Wiring & Mounting
•Ballastisearthedtothextureviaamountingscrew
•Ballastmountsusingtwoscrews(orsheetmetal
featureandonescrew)withinauorescentxture.
•Powerandlampwiringterminalsacceptone
0,75mm
2
to 1,5mm
2
solid copper wire per terminal
Lamp Seasoning
Priortodimminglamps,refertothelamp
manufacturer’s lamp seasoning requirements.
Warranty
Forwarrantyinformation,pleasesee:
www.lutron.com/TechnicalDocumentLibrary/
Ballast%20and%20Driver%20Warranty.pdf
* TypicalTHDformodelsEHDT514ME110andEHDT521ME110lessthan15%.
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Fluorescent Dimming Ballasts International EcoSystem® H-Series Architectural Dimming
369382D 3 09.21.12
EcoSystem® H-Series ballasts for T5 Linear Lamps
For proper dimming, all lamps must comply to accepted standards, 14 W (60081-IEC-6520), 21 W (60081-IEC-6530) and 28 W (60081-IEC-6640)
Not for use with Reduced Wattage Lamps
Lamp
Type
Lamp
Watts
(length)
Lamps
per
Ballast
Case
Size
EcoSystem®
H-Series
Input
Voltage
(V~)
Input
Current
(A)
Ballast
Factor
(BF)
Input
Power
(W)
System
Lumens*
(lm)
System
Efficacy*
(lm/W)
Ballast
Efficacy
Factor
(BEF)
Relative
System
Efficacy
(RSE)
T5 Linear
14W
(549mm)
1 M EHDT514ME110 220
240
0,09
0,08
1,00
1,00
19,8
19,2
1350
1350
68
70
5,05
5,21
0,71
0,73
2 M EHDT514ME210 220
240
0,16
0,15
1,00
1,00
35,2
36,0
2700
2700
77
75
2,84
2,78
0,80
0,78
21W
(848mm)
1 M EHD T521 ME110 220
240
0,12
0,11
1,00
1,00
26,4
26,4
2 100
2 100
80
80
3,79
3,79
0,80
0,80
2 M EHD T521 ME210 220
240
0,22
0,20
1,00
1,00
48,4
48,0
4 200
4 200
87
88
2,07
2,08
0,87
0,88
28W
(1148mm)
1 M EHDT528ME110 220
240
0,15
0,13
1,00
1,00
33,0
31,2
2900
2900
88
93
3,03
3,21
0,85
0,90
2 M EHDT528ME210 220
240
0,29
0,26
1,00
1,00
63,8
62,4
5800
5800
91
93
1,57
1,60
0,88
0,90
Models for Europe and Singapore (CE
, ENEC
Certification, Registered
under the Consumer Protection Registration Scheme in Singapore)
EcoSystem
® H-Series ballasts for T5HO Linear Lamps
For proper dimming, all lamps must comply to accepted standards, 24 W (60081-IEC-6620), 39 W (60081-IEC-6730) and 54 W (60081-IEC-6840)
Not for use with Reduced Wattage Lamps
Lamp
Type
Lamp
Watts
(length)
Lamps
per
Ballast
Case
Size
EcoSystem®
H-Series
Input
Voltage
(V~)
Input
Current
(A)
Ballast
Factor
(BF)
Input
Power
(W)
System
Lumens*
(lm)
System
Efficacy*
(lm/W)
Ballast
Efficacy
Factor
(BEF)
Relative
System
Efficacy
(RSE)
T5HO
Linear
24W
(549mm)
1 M EHD T524 ME110 220
240
0,13
0,12
1,00
1,00
28,6
28,8
2 000
2 000
70
69
3,50
3,47
0,84
0,83
2 M EHD T524 ME210 220
240
0,25
0,23
1,00
1,00
55,0
55,2
4 000
4 000
73
73
1,82
1,81
0,87
0,87
39W
(848mm)
1 M EHDT539ME110 220
240
0,20
0,18
1,00
1,00
44,0
43,2
3 500
3 500
80
81
2,27
2,31
0,89
0,90
2 M EHDT539ME210 220
240
0,37
0,34
1,00
1,00
81,4
81,6
7 000
7 000
86
86
1,23
1,23
0,96
0,96
54W
(1148mm)
1 M EHDT554ME110 220
240
0,29
0,26
1,00
1,00
63,8
62,4
5000
5000
78
80
1,57
1,60
0,85
0,87
2 M EHDT554ME210 220
240
0,51
0,48
1,00
1,00
112,2
115, 2
10000
10000
89
87
0,89
0,87
0,96
0,94
Certicationisapplicabletoanycountryrecognizingthecerticationbody.
*Actualnumbermayvarywithlampmodel.Pleaseconsultlampmanufacturerforlamp-specicdata.
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Fluorescent Dimming Ballasts International EcoSystem® H-Series Architectural Dimming
369382D 4 09.21.12
EcoSystem® H-Series ballasts for T5 Linear Lamps
For proper dimming, all lamps must comply to accepted standards, 14 W (60081-IEC-6520), 21 W (60081-IEC-6530) and 28 W (60081-IEC-6640)
Not for use with Reduced Wattage Lamps
Lamp
Type
Lamp
Watts
(length)
Lamps
per
Ballast
Case
Size
EcoSystem®
H-Series
Input
Voltage
(V~)
Input
Current
(A)
Ballast
Factor
(BF)
Input
Power
(W)
System
Lumens*
(lm)
System
Efficacy*
(lm/W)
Ballast
Efficacy
Factor
(BEF)
Relative
System
Efficacy
(RSE)
T5 Linear
14W
(549mm)
1 M EHDT514ME110-R 220
240
0,09
0,08
1,00
1,00
19,8
19,2
1350
1350
68
70
5,05
5,21
0,71
0,73
2 M EHDT514ME210-R 220
240
0,16
0,15
1,00
1,00
35,2
36,0
2700
2700
77
75
2,84
2,78
0,80
0,78
28W
(1148mm)
1 M EHDT528ME110-R 220
240
0,15
0,13
1,00
1,00
33,0
31,2
2900
2900
88
93
3,03
3,21
0,85
0,90
2 M EHDT528ME210-R 220
240
0,29
0,26
1,00
1,00
63,8
62,4
5800
5800
91
93
1,57
1,60
0,88
0,90
Models for Argentina (S-Mark
Certification)
EcoSystem
® H-Series ballasts for T5HO Linear Lamps
For proper dimming, all lamps must comply to accepted standards, 24 W (60081-IEC-6620), 39 W (60081-IEC-6730) and 54 W (60081-IEC-6840)
Not for use with Reduced Wattage Lamps
Lamp
Type
Lamp
Watts
(length)
Lamps
per
Ballast
Case
Size
EcoSystem®
H-Series
Input
Voltage
(V~)
Input
Current
(A)
Ballast
Factor
(BF)
Input
Power
(W)
System
Lumens*
(lm)
System
Efficacy*
(lm/W)
Ballast
Efficacy
Factor
(BEF)
Relative
System
Efficacy
(RSE)
T5HO
Linear
54W
(1148mm)
1 M EHDT554ME110-R 220
240
0,29
0,26
1,00
1,00
63,8
62,4
5000
5000
78
80
1,57
1,60
0,85
0,87
2 M EHDT554ME210-R 220
240
0,51
0,48
1,00
1,00
112,2
115, 2
10000
10000
89
87
0,89
0,87
0,96
0,94
Certicationisapplicabletoanycountryrecognizingthecerticationbody.
*Actualnumbermayvarywithlampmodel.Pleaseconsultlampmanufacturerforlamp-specicdata.
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Fluorescent Dimming Ballasts International EcoSystem® H-Series Architectural Dimming
369382D 5 09.21.12
EcoSystem® H-Series ballasts for T5 Linear Lamps
For proper dimming, all lamps must comply to accepted standards, 14 W (60081-IEC-6520), 21 W (60081-IEC-6530) and 28 W (60081-IEC-6640)
Not for use with Reduced Wattage Lamps
Lamp
Type
Lamp
Watts
(length)
Lamps
per
Ballast
Case
Size
EcoSystem
®
H-Series
Input
Voltage
(V~)
Input
Current
(A)
Ballast
Factor
(BF)
Input
Power
(W)
System
Lumens*
(lm)
System
Efficacy*
(lm/W)
Ballast
Efficacy
Factor
(BEF)
Relative
System
Efficacy
(RSE)
T5 Linear
14W
(549mm)
1 M EHDT514ME110-B 127
220
0,15
0,09
1,00
1,00
19,6
19,8
1350
1350
69
68
5,12
5,05
0,72
0,71
2 M EHDT514ME210-B 127
220
0,28
0,16
1,00
1,00
35,0
35,4
2700
2700
77
76
2,86
2,82
0,80
0,79
21W
(848mm)
1 M EHD T521 ME110-B 127
220
0,20
0,12
1,00
1,00
25,4
26,4
2100
2100
82
80
3,94
3,79
0,83
0,80
2 M EHD T521 ME210-B 127
220
0,39
0,22
1,00
1,00
49,5
48,4
4200
4200
85
87
2,02
2,07
0,85
0,87
28W
(1148mm)
1 M EHDT528ME110-B 127
220
0,26
0,15
1,00
1,00
33,5
33,7
2900
2900
86
86
2,98
2,97
0,84
0,83
2 M EHDT528ME210-B 127
220
0,50
0,29
1,00
1,00
63,6
63,4
5800
5800
91
92
1,57
1,58
0,88
0,88
EcoSystem® H-Series ballasts for T5HO Linear Lamps
For proper dimming, all lamps must comply to accepted standards, 24 W (60081-IEC-6620), 39 W (60081-IEC-6730) and 54 W (60081-IEC-6840)
Not for use with Reduced Wattage Lamps
Lamp
Type
Lamp
Watts
(length)
Lamps
per
Ballast
Case
Size
EcoSystem
®
H-Series
Input
Voltage
(V~)
Input
Current
(A)
Ballast
Factor
(BF)
Input
Power
(W)
System
Lumens*
(lm)
System
Efficacy*
(lm/W)
Ballast
Efficacy
Factor
(BEF)
Relative
System
Efficacy
(RSE)
T5HO
Linear
24W
(549mm)
1 M EHD T524 ME110-B 127
220
0,23
0,13
1,00
1,00
29,2
28,6
2000
2000
68
70
3,42
3,50
0,82
0,84
2 M EHD T524 ME210-B 127
220
0,44
0,25
1,00
1,00
53,9
55,0
4000
4000
72
73
1,79
1,82
0,86
0,87
39W
(848mm)
1 M EHDT539ME110-B 127
220
0,35
0,20
1,00
1,00
44,5
44,0
3500
3500
79
80
2,25
2,27
0,88
0,89
2 M EHDT539ME210-B 127
220
0,66
0,37
1,00
1,00
83,8
81,4
7000
7000
84
86
1,19
1,23
0,93
0,96
54W
(1148mm)
1 M EHDT554ME110-B 127
220
0,50
0,29
1,00
1,00
64,0
62,7
5000
5000
78
80
1,56
1,59
0,84
0,86
2 M EHDT554ME210-B 127
220
0,93
0,55
1,00
1,00
118,4
120,8
10000
10000
84
83
0,84
0,83
0,91
0,89
Models for Brazil (InMetro
Certification)
Certicationisapplicabletoanycountryrecognizingthecerticationbody.
*Actualnumbermayvarywithlampmodel.Pleaseconsultlampmanufacturerforlamp-specicdata.
Continued on next page
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Fluorescent Dimming Ballasts International EcoSystem® H-Series Architectural Dimming
369382D 6 09.21.12
EcoSystem® H-Series ballasts for T8 Linear Lamps
For proper dimming, all lamps must comply to accepted standards, 32 W (NEMA LL9-2009)
Not for use with Reduced Wattage Lamps
Lamp
Type
Lamp
Watts
(length)
Lamps
per
Ballast
Case
Size
EcoSystem
®
H-Series
Input
Voltage
(V~)
Input
Current
(A)
Ballast
Factor
(BF)
Input
Power
(W)
System
Lumens*
(lm)
System
Efficacy*
(lm/W)
Ballast
Efficacy
Factor
(BEF)
Relative
System
Efficacy
(RSE)
T8 Linear
32W
(1220mm)
1 M EHDT832ME110-B 127
220
0,28
0,16
1,00
1,00
35,7
35,2
3000
3000
84
85
2,80
2,84
0,90
0,91
2 M EHDT832ME210-B 127
220
0,53
0,31
1,00
1,00
67, 2
67, 8
6000
6000
89
89
1,49
1,48
0,95
0,94
Models for Brazil (InMetro
Certification) (continued)
Certicationisapplicabletoanycountryrecognizingthecerticationbody.
*Actualnumbermayvarywithlampmodel.Pleaseconsultlampmanufacturerforlamp-specicdata.
6
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Fluorescent Dimming Ballasts International EcoSystem® H-Series Architectural Dimming
369382D 7 09.21.12
Models for China (CCC
Certification)
EcoSystem® H-Series ballasts for T5 Linear Lamps
For proper dimming, all lamps must comply to accepted standards, 14 W (60081-IEC-6520) and 28 W (60081-IEC-6640)
Not for use with Reduced Wattage Lamps
Lamp
Type
Lamp
Watts
(length)
Lamps
per
Ballast
Case
Size
EcoSystem®
H-Series
Input
Voltage
(V~)
Input
Current
(A)
Ballast
Factor
(BF)
Input
Power
(W)
System
Lumens*
(lm)
System
Efficacy*
(lm/W)
Ballast
Efficacy
Factor
(BEF)
Relative
System
Efficacy
(RSE)
T5 Linear
14W
(549mm)
1 M EHDT514ME110-C 220
240
0,09
0,08
1,00
1,00
19,8
19,2
1350
1350
68
70
5,05
5,21
0,71
0,73
2 M EHDT514ME210-C 220
240
0,16
0,15
1,00
1,00
35,2
36,0
2700
2700
77
75
2,84
2,78
0,80
0,78
28W
(1148mm)
1 M EHDT528ME110-C 220
240
0,15
0,13
1,00
1,00
33,0
31,2
2900
2900
88
93
3,03
3,21
0,85
0,90
2 M EHDT528ME210-C 220
240
0,29
0,26
1,00
1,00
63,8
62,4
5800
5800
91
93
1,57
1,60
0,88
0,90
EcoSystem® H-Series ballasts for T5HO Linear Lamps
For proper dimming, all lamps must comply to accepted standards, 54 W (60081-IEC-6840)
Not for use with Reduced Wattage Lamps
Lamp
Type
Lamp
Watts
(length)
Lamps
per
Ballast
Case
Size
EcoSystem®
H-Series
Input
Voltage
(V~)
Input
Current
(A)
Ballast
Factor
(BF)
Input
Power
(W)
System
Lumens*
(lm)
System
Efficacy*
(lm/W)
Ballast
Efficacy
Factor
(BEF)
Relative
System
Efficacy
(RSE)
T5HO
Linear
54W
(1148mm)
1 M EHDT554ME110-C 220
240
0,29
0,26
1,00
1,00
63,8
62,4
5000
5000
78
80
1,57
1,60
0,85
0,87
2 M EHDT554ME210-C 220
240
0,51
0,48
1,00
1,00
112,2
115, 2
10000
10000
89
87
0,89
0,87
0,96
0,94
Certicationisapplicabletoanycountryrecognizingthecerticationbody.
*Actualnumbermayvarywithlampmodel.Pleaseconsultlampmanufacturerforlamp-specicdata.
7
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Fluorescent Dimming Ballasts International EcoSystem® H-Series Architectural Dimming
369382D 8 09.21.12
Case Dimensions
M
A 359mm
B 347mm
(mountingcenters)
C 30mm
D 25 mm
D
B
A
C
8
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Fluorescent Dimming Ballasts International EcoSystem® H-Series Architectural Dimming
369382D 9 09.21.12
EcoSystem® H-Series Wiring Diagrams
EcoSystem® Digital Link Overview
•TheEcoSystem
®DigitalLinkwiring(E1andE2)
connects the digital ballasts together to form a
lighting control system
•EachEcoSystem
® Digital Link supports up
to64digitalballasts,64occupancysensors,
16daylightsensors,and64wallstationsorIR
receivers
•E1andE2(EcoSystem
®digitallinkwires)arepolarity
insensitive and can be wired in any topology
•AnEcoSystem
®EnergiSavrNodeTM module,
GRAFIKEye
®QS with EcoSystem® control unit, or
Quantum
® system provides power for the EcoSystem®
Digital Link and supports system programming
•All EcoSystem
® Digital Link programming is completed
by using the Energi Savr App for Apple iPad, iPod
Touch or iPhonemobiledigitaldevices,GRAFIK
Eye
®QS with EcoSystem®, or Quantum® systems
EcoSystem
® Digital Link Wiring
•BallastEcoSystem
® Digital Link terminals accept one
0,75mm
2
to 1,5mm
2
solid copper wire per terminal
•MakesurethatthesupplybreakertotheDigital
BallastandEcoSystem
®DigitalLinkSupplyisOFF
when wiring
•ConnectthetwoconductorstothetwoDigital
BallastterminalsE1andE2asshown
•UsingtwodifferentcolorsforE1andE2willreduce
confusion when wiring several ballasts together
E1
E2
N
L
Digital
Link
E1
E2
N
L
Digital
Link
MAINS
MAINS
BallastTerminals
BallastTerminals
To the EcoSystem
® Digital Link Supply
andupto64totalballasts
Notes
•TheEcoSystem
® Digital Link Supply does not have
to be located at the end of the Digital Link
•EcoSystem
® Digital Link length is limited by the wire
gaugeusedforE1andE2asfollows:
Wire Size Digital Link Length
(max)
4,0mm
2
825 m
2,5 mm
2
515 m
1,5 mm
2
310m
1,0mm
2
205m
0,75mm
2
155 m
Apple,iPad,iPodTouch,andiPhonearetrademarksofAppleInc.,registeredintheU.S.andothercountries.
9
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Fluorescent Dimming Ballasts International EcoSystem® H-Series Architectural Dimming
369382D 10 09.21.12
Wiring to One Lamp (M case shown)
NOTICE
•Maximumballasttolampsocketleadlengthis2m
•Wirecolorsshowncorrespondtotheterminalcolorontheballast,butmayvarydependinguponxture
construction
BLU
BLU
RED
RED
BLU
BLU
RED
RED
YEL
YEL
Blue
Red
Wiring to Two Lamps (M case shown)
Blue
Yellow
Red
EcoSystem® H-Series Ballast Wiring Diagrams — T5, T5HO and T8 linear lamps
10
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Fluorescent Dimming Ballasts International EcoSystem® H-Series Architectural Dimming
369382D 11 09.21.12
EcoSystem® Power Wiring Diagram
E1
E2
N
L
Digital
Link
MAINS
EcoSystem®
H-Series
Ballast
E1
2
Neutral
2, 3
Live
2, 3
E2
2
Earth
1
1
Ballastisearthedviathecase.
2
ColorcodeshownfortheidenticationoflineandneutralconductorsareincompliancewithIEC/EN/BSEN60446,and
BS7671,colormayvarybasedonlocalcodesandstandards.
3
Mustnotbewiredtoaswitchingdeviceorsystemfunctionalitywillbelost.
11
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Fluorescent Dimming Ballasts International EcoSystem® H-Series Architectural Dimming
369382D 12 09.21.12
ATTENTION ELECTRICIANS
AND CONTRACTORS
Ballast/Socket Leads
Lead lengths from ballast to socket must not exceed
2 m for T5, T5HO and T8 linear lamps.
Lamp Sockets
LutronrequiresthatsocketsMUSTcomplywith
IEC60400.Priortoinstallationsocketsmustbe
inspected for marks to ensure compliance with
IEC60400.Twoexamplesofthesemarksare
E
and
Q
.Useonlyrapidstartsockets.DONOTuse
instantstartsockets(seeLutronApplication
Note#122[P/N048122]formoreinformation).
Lamp Mounting
Forproperlampperformance,lampsmustbe
mounted at the correct height from the earthed
metal surface. Having a fluorescent lamp too close
to the earthed metal will make the minimum intensity
too low and reduce lamp life. Having a fluorescent
lamp too far away from the earthed metal will make
thelampickerornotturnonatall.Refertothe
table below for lamp mounting height requirements.
Lamp Mounting Height Requirements
Ballast Operating Temperature
Ballastt
C
mustnotexceed70°C.
Cold Air Flow
Ensurethatnocoldair(fromHVACsystem,etc)is
blowingacrossthelamps.Coolingthelampmay
cause performance issues.
Lamp Type Lamp Mounting Height
T8 Linear 3,2 to 19,1 mm
T5 Linear 1,6 to 9,5 mm
IMPORTANT: Lamps must never touch ground
plane and should be placed without obstruction.
Lamp
Lamp Socket
(side view)
Mounting height
Grounded
metal
Ballast
Wiring and Grounding
Ballastandlightingxturemustbeeffectively
grounded.Ballastsmustbeinstalledpernational
and local electrical codes.
ATTENTION
FACILITIES MANAGERS
PERFORMANCE
Lamp Seasoning
Priortodimminglamps,refertothelamp
manufacturer’s lamp seasoning requirements.
SERVICE
Replacement Ballasts
UseLutron
® replacement ballasts with exact model
numbers.ConsultLutronifyouhaveanyquestions.
Technical Assistance
Forquestionsconcerningtheinstallationor
operation of this product, call the Lutron Technical
SupportCenter.Pleaseprovideexactmodel
number when calling.
Brazil + 55.11.3 257.6745
Monday–Friday 8:30 to 17:30 BRT
Central/South America: +1.610.282.6701
China 10.800.712.1536(Beijing)
10.800.120.1536(Shanghai)
800.901.849(HongKong)
Europe +44.(0)20.7680.4481
Monday–Friday 9:00 to 19:00 GMT
Singapore: 800.120.4491
Other countries: +1.610.282.3800
24 hours per day, 7 days per week
Forfurtherinformation,pleasevisitusat
www.lutron.com/ballasts
12