SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node EcoSystem Digital Fixture Controller
369248n 1 04.07.17
Energi Savr Node with EcoSystem
The Energi Savr Node family is a group of intelligent, modular products
for the control of lighting loads. This document describes the Energi
Savr Node unit with EcoSystem, which can control all EcoSystem
compatible products including EcoSystem ballasts and modules and
Hi-lume EcoSystem LED drivers.
•EnergiSavrNode unit with EcoSystem with
1 EcoSystem Digital Loop (QSN-1ECO-S).
•EnergiSavrNode unit with EcoSystem with
2 EcoSystem Digital Loops (QSN-2ECO-S).
Features
•Powersupto2EcoSystemDigitalLoops(QSN-2ECO-S).
•EasysystemprogrammingwithanintuitiveapplicationforApple iPhone or
iPod touch mobile digital devices (required for non-Quantum systems).
•Fouroccupancysensorinputsforautomatedcontroloflights.
•Fourdaylightsensorinputsautomaticallyadjustlightlevelsbasedon
the amount of natural light entering through the windows.
•FourIRreceiverinputsforpersonalcontrol.
•IncludesQScontrollinkforseamlessintegrationoflights,control
stations, and QS sensor modules.
•ExpandthenumberofsensorsandcontrolsusingtheQSSensorModule
(QSM)orsensorsconnectionsonEcoSystem ballasts and modules.
•ConnectdirectlytootherEnergiSavrNodeunits,GRAFIKEyeQS units,
or Quantum systems
toexpandfunctionalityandcontrol.
•BAA-compliantmodelnumbersavailable.Adda“U”prextothemodel
number.
System Example
Wireless
Communication
Wired
Daylight
Sensors
(up to 4)
1,2
Wired
Occupancy
Sensors
(up to 4)
1
Wired EcoSystem
Wallstation
orIRreceivers
(up to 4)
1
IRTransmitter
OR OR
RadioPowrSavr
Occupancy Sensor
(upto10perQSM)
RadioPowrSavr
Daylight Sensor
(upto10perQSM)
PicoWireless
Controller (up to
10perQSM)
Notes:
1
Upto4wiredinputstotal(ofanytype).
2
Upto16wireddaylightsensorstotalperEcoSystem loop.
Apple,iPhone,andiPodtoucharetrademarksofAppleInc.,registeredintheU.S.andothercountries.
QS Link
GRAFIK Eye QS Control Unit
Energi Savr Node
Unit
QSM
Wired Inputs
Sivoia QS
shades / draperies
ControlwithPico
wireless controller
onlythroughQSM
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node EcoSystem Digital Fixture Controller
369248n 2 04.07.17
Specifications
Energi Savr Node with EcoSystem
Regulatory Approvals
•UL® Listed
•CSA
•NOMCertied
•LutronQualitySystemsregisteredtoISO9001.2008
• Complieswithrequirementsforuseinotherspaces
used for environmental air (plenums) per
NEC
® 2014 300.22(C)(3)
•MeetstheCanadianNationalBuildingCodeplenum
requirements for a concealed space used as a plenum
within a floor or roof assembly
•Forcommercialuse,ClassAonly
Power
•ControlPower:120-277V~50/60Hz
•LightningstrikeprotectionmeetsANSI/IEEEstandard
62.31-1980.Canwithstandvoltagesurgesofupto
6000V~ andcurrentsurgesofupto3000A
•Currentdraw:0.5A
•10-yearpowerfailurememory:restoreslightingto
levels prior to power interruption
Environment
•AmbientTemperatureOperatingRange:32ºFto104ºF
(0ºCto40ºC)
•Relativehumidity:lessthan90%non-condensing.
•Forindooruseonly
Terminals
ControlPowerwiring:14AWGto12AWG
(2.5 mm
2
to 4.0 mm
2
)
•EcoSystemDigitalLoopWiring:18AWGto12AWG
(1.0 mm
2
to 4.0 mm
2
)
•InputGroupWiring:22AWGto12AWG
(0.5 mm
2
to 4.0 mm
2
)
•QSLoopWiring:22AWGto12AWG
(0.5 mm
2
to 4.0 mm
2
)
Physical Design
•NEMAType1,IP-20protection.
Mounting
•Surface-mount
Programming Requirements
•AnApple iPod touch or iPhone mobile digital device
with the Energi Savr app is required for programming
Energi Savr Node with EcoSystem systems
•TheEnergiSavrappisavailablefromtheApple App
Store online store
•TheEnergiSavrappcannotbeusedtoprogramthe
Energi Savr Node with EcoSystem units when installed
as part of a Quantum system
•TheApple iPod touch or iPhone communicates
with the Energi Savr Node unit
viaaWiFirouter
(not included)
•See“Wiring:SystemProgrammingConnection”
section for further information
Input Default Associations
•EnergiSavrNodewithEcoSystemunitsare
pre-programmed from the factory to respond to inputs
wired directly to the Energi Savr Node with EcoSystem
unit
•ProgrammableCCIactivatesasceneusinganormally
open momentary closure by default
Apple,iPhone,andiPodtoucharetrademarksofAppleInc.,registeredintheU.S.andothercountries.AppStoreisaservicemarkofAppleInc.
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node EcoSystem Digital Fixture Controller
369248n 3 04.07.17
Specifications (continued)
EcoSystem
•Controlupto64EcoSystem compatible devices
(ballast, modules, or LED drivers) per EcoSystem Digital
Loop(upto128devicesperEnergiSavrNodewith
EcoSystemunit):
– EcoSystem ballasts and modules
– Hi-lume EcoSystem LED drivers
•Digitallydeneareasandzones.
•Congurewiredorwirelesssensorsandcontrolsto
control devices on multiple EcoSystem Digital Loops
and/or multiple Energi Savr Node units.
•Automaticreplacementofasinglefailedballast,
module, or driver.
•Simplemethodofreplacingmultiplefailedballasts,
modules, or drivers.
•EcoSystem
DigitalLoopcanbewiredasClass1orIEC
PELV/NEC®Class2formaximumwiringexibility.
Occupancy Sensors
•UseLutronLOSseriesofwiredoccupancysensorsin
occupancy mode to control one or more areas.
•UseLutronoccupancysensorsinvacancymode
to automatically turn the lights off in an area after it
becomes vacant.
•UseLutronoccupancysensorstoautomaticallyturn
the lights on in area when it becomes occupied and
to automatically turn the lights off in an area after it
becomes vacant.
•Eachofthefouroccupancyinputscanpowerone
Lutron occupancy sensor.
•Eacharea’soccupiedlightlevelandunoccupiedlight
level can be programmed independently.
•UptofouradditionalLutronWiredOccupancy
SensorsortenadditionalRadioPowrSavr
Occupancy/VacancySensorscanbeassignedper
QSSensorModule(QSM)ontheQSlink.
seeTouch QS Controls
•seeTouchQSwallstationscanbeconguredas
azonetoggleorscenewallstation.
•Inzonetogglemode,zonebuttonsareabletoturn
oneormorezonesonandoff.
•Inscenemode,buttonsareabletorecallscenesin
one or more areas.
•Allbuttonsonawallstationwillbeinthesame
mode-zonetoggleorscene.
•LEDindicatordisplayszoneorscenestatus.
•Asinglebuttoncancontrollightsorshades/draperies,
but not both.
IR Wallstation or Receiver Input
•FourinputsforIRreceiversorwallstationsforcontrol
oflightingzonescanbeconnecteddirectlytothe
Energi Savr Node with EcoSystem unit.
•UseLutronCC-4BRL-WHwallstationstocontrolone
ormorezones.
•UseLutron EC-IR-WHorEC-DIR-WHceilingmount
sensorstocontroloneormorezones.
•UptofouradditionalwiredwallstationsorIR
receiverscanbeassignedperQSMontheQSlink
Daylight Sensors
•Lutrondaylightsensorsallowdaylightharvesting
with programmable effect on light output.
•Fourdaylightsensorscanbeconnecteddirectlyto
the Energi Savr Node with EcoSystem unit.
•UseLutronEC-DIR-WHsensorstocontrolone
or more daylight rows.
•Alternatively,uptofouradditionalLutronWired
DaylightSensorsortenadditionalRadioPowrSavr
DaylightSensorscanbeassignedperQSMonthe
QSlink.
•Control4daylightrowsperareawithamaximum
of 2 daylight sensors per area.
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node EcoSystem Digital Fixture Controller
369248n 4 04.07.17
Specifications (continued)
Contact Closure Input (CCI)
•Activatescenesusingmomentaryormaintained
closuresfromanexternaldevicelikeatimeclock.
•StartorstopAfterhoursmodeusingamaintained
closure.
•EnableordisableLoadShedmodetosaveenergy
duringpeakdemandperiodsusingamaintained
closure.
•Theattacheddevicemustprovideadrycontact
closure or solid-state output.
•Congurablefornormallyopen(NO)ornormally
closed (NC) operation.
•Inputismiswire-protectedupto36V-.
Emergency Contact Closure Input
•Bydefault,contactclosureinputfromLutron
EmergencyLightingInterface(LUT-ELI-3PH),security,
orrealarmsystemsturnsallzonesontofulloutput
when emergency state is detected.
•Emergencycontactclosureinputisnormallyclosed
(NC). The Energi Savr Node unit with EcoSystem
isshippedwithajumperpre-installed.
•Responseofeachzoneiscongurable.
•Attacheddevices,bydefault,willgotomaximum
output and ignore control inputs.
•Nooperationswillbealloweduntilemergencysignal
is cleared.
•Theattacheddevicemustprovideanormally-closed
(NC) dry contact closure or solid-state output.
•Inputismiswire-protectedupto36V-.
•EmergencyCCIcannotcontrolotherEnergiSavr
Node units.
•SeeApplicationNote#140,“EcoSystemBallasts
andEmergencyWiring”atwww.lutron.comfor
more details.
Functionality with GRAFIK Eye QS
•EnergiSavrNodewithEcoSystemareasfollow
GRAFIKEye QS unit scene activations when
associated with the
GRAFIKEye QS unit.
•EnergiSavrNodewithEcoSystemareasrespond
tocommandsinitiatedbytheGRAFIKEye QS unit
astronomictimeclockwhenassociatedwiththe
GRAFIKEye QS unit.
•EnergiSavrNodewithEcoSystemareas
operateinAfterhoursmodewhenassociatedwitha
GRAFIKEyeQSunitthatisinAfterhoursmode.
•ZonesonEnergiSavrNodeunitscannotbe
associatedwithzonecontrolsonGRAFIKEye
QS units.
Functionality with QSE-IO
•EnergiSavrNodeunit with EcoSystem responds
toscenecommandsinitiatedbytheQSE-IO,ifthe
QSE-IODIPswitcheshavebeensettoeitherScene
Selectionmode,ZoneTogglemode,Partitionmode,
or Occupancy Sensor mode.
Functionality with QSE-CI-NWK-E
•IntegratetheEnergiSavrNodeunitwithEcoSystem
withtouchscreens,PCs,A/Vsystems,orotherdigital
systems and devices.
•Recallscenesandset/adjustzonelevels.
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node EcoSystem Digital Fixture Controller
369248n 5 04.07.17
Specifications (continued)
QS Sensor Module (QSM)
•UsetheQSMtointegrateRadioPowrSavr
Occupancy/Vacancysensors,RadioPowrSavrDaylight
sensors,andPicoWirelessControllerswithanEnergi
Savr Node unit with EcoSystem.
•Associateupto99QSMsperEnergiSavrNodeunitwith
EcoSystem.
•Assignupto10RadioPowrSavrOccupancy
sensorsperQSM.
•Assignupto10RadioPowrSavrDaylightsensorsper
QSM.
•Assignupto10PicoWirelessControllersperQSM.
•Connectupto100wiredorwirelesssensorsofeach
typeperQSlink.
•Wireandpowerupto4wiredsensorsperQSM:
– Daylight sensors
– Occupancy sensors
–Infrared(IR)receiversorwallstations
•TheRadioPowrSavrsensorsandPicoWireless
ControllersassociatedwiththeQSMshouldbemounted
within60ft(18m)lineofsight,or30ft(9m)through
walls,oftheQSM.
•RefertoQSMSpecicationSubmittalformore
information.
EcoSystem Digital Loop Limits
•Upto64EcoSystem compatible fluorescent ballasts
and/or LED drivers per EcoSystem digital loop.
•Sensorandcontrolcommunicationlimits:
–16daylightsensors
–64occupancysensors
–64infrared(IR)receiversorwallstations
Asensororcontrolcountsasadeviceonthe
EcoSystem digital loop if it is wired to an EcoSystem
ballast on the same loop, or is programmed to
communicate with a fluorescent ballast or LED driver on
the EcoSystem digital loop.
•EcoSystem
compatible fluorescent ballasts and LED
drivers on the EcoSystem digital loop do not count as
QS devices.
QS Link Limits
•EachEnergiSavrNodeunit with EcoSystem can
provideupto30PowerDrawUnitsforotherQS
devices.RefertotheQSLinkPowerDrawUnits
specicationsubmittal(LutronP/N369405)for
moreinformationconcerningPowerDrawUnits.
•TheQSLinkcanhaveupto100devicesand
100zones.
•EachEnergiSavrNodeunit with EcoSystem counts
as 1 device towards the 100 device limit.
•EachEnergiSavrNodeunit with EcoSystem can
countas1to100zonestowardsthe100zonelimit,
dependingonthenumberofzonescreated(upto
512zonesinaQuantumsystem).
•Amaximumof8EcoSystemdigitalloopsmaybe
connectedtotheQSlink.EnergiSavrNodeunit with
EcoSystemcountsasupto64orup
to128ballasts.
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node EcoSystem Digital Fixture Controller
369248n 6 04.07.17
Mechanical Dimensions
Alldimensionsshownasin(mm)
QS LINK
LOOP 2
LOOP 1
RESET
LOOP 2
TEST
GROUP 1
+20V
OCC 1
PHOTO 1
IR 1
COM
+24V
MUX
PWR
TEMPTEST
MUX
COM
GROUP 2
+20V
OCC 2
PHOTO 2
IR 2
COM
GROUP 3
+20V
OCC 3
PHOTO 3
IR 3
COM
GROUP 4
+20V
OCC 4
PHOTO 4
IR 4
COM
CONTACT CLOSURE ETHERNET
CCI
COM
EMERG
COM
LOOP 1
H/LN N/C
11.25
(285.75)
0.20(5.16)
dia.
0.95
(24.13)
1.41
(35.81)
1.80
(45.72)
1.03
(26.16)
Do not
use side
knockouts
0.83
(21.08)
9.25
(234.95)
7.50
(190.50)
3.16
(80.26)
13.25
(336.55)
6
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node EcoSystem Digital Fixture Controller
369248n 7 04.07.17
Power Draw Units (PDUs) on the QS Link
OntheQSlink,therearedevicesthatsupplypoweranddevicesthatconsumepower.Eachdevicehasaspecic
numberofPDUsiteithersuppliesorconsumes.
APowerGroupconsistsofonedevicethatsuppliespowerandoneormoredevicesthatconsumepower;each
PowerGroupmayhaveonlyonepower-supplyingdevice.RefertotheQSLinkPowerDrawUnitsspecication
submittal(LutronP/N369405)formoreinformationconcerningPDU’s.
WithinPowerGroupsontheQSlink,connectall4terminals(1,2,3,and4),shownbytheletterAinthediagram.
BetweendevicesontheQSlinkthatsupplypower,connectonlyterminals1,3,and4(NOTterminal2),shownby
theletterBonthediagram.WiringcanbeT-tappedordaisy-chained.
Power Group Wiring Example
LUTRON
LUTRON LUTRON
LUTRON
LUTRON
LUTRON
Power Group 1
Power Group 2
Power Group 3
A
A
A
B
B
B
(Do not connect
terminal 2: 24 V-)
(Do not connect
terminal 2: 24 V-)
(Do not connect
terminal 2: 24 V-)
Connect all 4 terminals
within a power group:
1: Common
2: 24 V-
3 and 4: Data
Connect only 3
terminals between
power groups:
1: Common
3 and 4: Data
Do not connect
Terminal 2: 24 V-
A
B
GRAFIK Eye QS
control unit
Supplies PDUs
QS Power Supply
Supplies PDUs
Energi Savr Node
QS unit
Supplies PDUs
Control Interfaces
Consume PDUs
Control Interfaces
Consume PDUs
Quantum Panel
Supplies PDUs
Wallstations
Consume PDUs
Wallstations
Consume PDUs
Wallstations
Consume PDUs
QS Sensor Module with
wired Occupancy Sensor
Consumes PDUs
Wireless Occupancy Sensor
does not consume PDUs
Note: EachQSlinkhasalimitof100totaldevices;devicecountcanvarydependingonyoursystemandyourconnecteddevices.
7
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node EcoSystem Digital Fixture Controller
369248n 8 04.07.17
Wiring: QS Link
•QSlinkcommunicationusesIECPELV/NEC® Class 2 wiring.
FollowalllocalandnationalelectricalcodeswheninstallingIEC
PELV/NEC® Class 2 wiring with line voltage wiring.
•ThetotaldistanceoftheQSlinkwiringmustnotexceed2000ft
(610m).
QS Link Wiring
Distance
Wire
Gauge
Available from Lutron
in one cable:
Less than 500ft
(152.4m)
Power (terminals 1 and 2):
1 pair 18AWG (1.0mm
2
)
GRX-CBL-346S (non-plenum)
GRX-PCBL-346S (plenum)
Data (terminals 3 and 4):
1 pair 22AWG (0.5mm
2
),
twisted and shielded*
500ft (152.4m) to
2000ft (610m)
Power (terminals 1 and 2):
1 pair 12AWG (4.0mm
2
)
GRX-CBL-46L (non-plenum)
GRX-PCBL-46L (plenum)
Data (terminals 3 and 4):
1 pair 22AWG (0.5mm
2
),
twisted and shielded*
* AlternateData-onlycable:Useapproveddataloopcable
(22AWG[0.5mm
2
]twisted/shielded)fromBelden,model#9461.
Energi Savr Node unit with
EcoSystem
QS Link Wiring:
•22AWGto12AWG
(0.5mm
2
to 4.0mm
2
)
Drain
2 12 AWG
(4.0 mm
2
)
2 12 AWG
(4.0 mm
2
)
IEC PELV/NEC
® Class 2
control wiring
(2) 18 AWG (1.0 mm
2
)
1: Common
2: 24 V-
Control Link Wiring
Data loop: (1) twisted,
shielded pair
22 AWG (0.5 mm
2
)
3: MUX
4: MUX
Wiring for QS link for 500 ft
(152.4m) to 2000 ft (610 m).
Terminal block will not accept
12 AWG (4.0 mm
2
) directly.
(4) MUX
(3)MUX
(2)24V-
(1)COM
8
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node EcoSystem Digital Fixture Controller
369248n 9 04.07.17
Wiring: QS Link (continued)
Only terminals 1, 3, and 4 connected
betweendevicesthatsupplyPDUs
Terminal 2 NEVER connected
between devices that supply PDUs
Terminal2(+24V)
NEVERconnected*
Devices that
supplyPDUs
Devices that
consumePDUs
COM
+24 V
MUX
MUX
COM
MUX
MUX
Energi Savr
Node unit
Energi Savr
Node unit
QS
Input/
Output
Interface
Wired
QS
Keypad
QSM
QSMQSM
Wired
QS
Keypad
Wired
QS
Keypad
Wired
QS
Keypad
QS
Input/
Output
Interface
QS
Link
power
supply
QSlink;
all 4 terminals
QSlink;
no terminal 2
QSlink;
no terminal 2
QSlink;
all 4 terminals
QSlink;
all 4 terminals
Terminal2(+24V)
NEVERconnected*
Terminal2(+24V)
NEVERconnected*
**
All4terminalsconnectedtoQSlink
devicesthatconsumePDUs
QS Link Wiring Rules
* Terminal2(+24V)shouldNEVERbeconnectedbetweendevicesthatsupplyPDUs.
** ForQSLinkpowersupplywiringconnectiondetails,refertotheinstallationinstructions
for the specific power supply model being used.
9
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node EcoSystem Digital Fixture Controller
369248n 10 04.07.17
Wiring: IEC PELV / NEC® Class 2 Inputs
NOTE: There are four input groups. Each group has
the same inputs as shown in the diagram below.
Note: Maximumwire
run length to each
inputnottoexceed
100 ft (30 m).
Input Group Wiring:
•22AWGto12AWG
(0.5mm
2
to 4.0mm
2
)
* Note:OnlyoneIRdevicemaybeconnectedperinput.IftheIR
signal from a daylight sensor is connected, a wall control may
not be connected to the same input, and vice-versa.
** Connectthegraywireon-Rmodeloccupancysensors.
Occupancy Sensor
EcoSystem
Wallstation or
IRReceiver*
Red
Red
20V
Black
Black COM
Yellow
Blue**
Black
Red
White*
20V:20V-
Occ:OccupancySensor
Daylight:DaylightSensor
IR:IRReceiver*
Com:Common
Group1shown Group2shown
White* IR
LUTRON
Daylight/IRSensor*
LUTRO
N
R
IRTransmitter
10
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node EcoSystem Digital Fixture Controller
369248n 11 04.07.17
Wiring Diagram: EcoSystem Digital Loop
H/LN N/C
LOOP 2
LOOP 1
LOOP 2
LOOP 1
EcoSystem Ballasts
Energi Savr Node unit with EcoSystem
EcoSystem Digital Loop
Optional second EcoSystem Digital Loop
(requires QSN-2ECO-S)
Hi-Lume EcoSystem LED Drivers
Upto64ballasts,modules,orLEDdrivers
Upto64ballasts,modules,orLEDdrivers
Wiring Notes
•CanbewiredasClass1orIECPELV/NEC® Class 2
(seeAppNote#142,“EcoSystemBusClass1and
IECPELV/NEC®Class2Listing”atwww.lutron.com
for more details).
•Polarityfree.
•Topologyfree.
•EcoSystemDigitalLoopsarenotelectricallyisolated
fromeachother.Amiswireorshortonone
EcoSystem Digital Loop will affect both loops.
Wire Gauge
Maximum EcoSystem
Digital Loop Wire Length
12AWG(4.0mm
2
) 2200ft(671m)
14AWG(2.5mm
2
) 1400ft(427m)
16AWG(1.5mm
2
) 900ft(275m)
18AWG(1.0mm
2
) 570ft(175m)
EcoSystem Ballasts
Hi-Lume EcoSystem LED Drivers
11
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node EcoSystem Digital Fixture Controller
369248n 12 04.07.17
Wiring: Control Power
Wiring Notes
•ControlPowerwiringshouldbefromanormal,
non-emergency feed for proper operation of the
Energi Savr Node unit with EcoSystem.
•Powerterminalsaccept(1)or(2)14AWGto
12AWG(2.5mm
2
to 4.0 mm
2
) solid or
stranded wire.
Energi Savr Node unit with EcoSystem
QS LINK
Loop 1
Loop 1
RESET
LOOP 2
TEST
GROUP 1
+20V
OCC 1
PHOTO 1
IR 1
COM
+24V
MUX
PWR
TEMPTEST
MUX
COM
GROUP 2
+20V
OCC 2
PHOTO 2
IR 2
COM
GROUP 3
+20V
OCC 3
PHOTO 3
IR 3
COM
GROUP 4
+20V
OCC 4
PHOTO 4
IR 4
COM
CONTACT CLOSURE ETHERNET
CCI
COM
EMERG
COM
LOOP 1
H/LN N/C
Hot/Line (H/L)
Neutral
(N)
Ground
(
D
)
Do not use (N/C)
QS LINK
Loop 1
Loop 1
RESET
LOOP 2
TEST
GROUP 1
+20V
OCC 1
PHOTO 1
IR 1
COM
+24V
MUX
PWR
TEMPTEST
MUX
COM
GROUP 2
+20V
OCC 2
PHOTO 2
IR 2
COM
GROUP 3
+20V
OCC 3
PHOTO 3
IR 3
COM
GROUP 4
+20V
OCC 4
PHOTO 4
IR 4
COM
CONTACT CLOSURE ETHERNET
CCI
COM
EMERG
COM
LOOP 1
H/LN N/C
12
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node EcoSystem Digital Fixture Controller
369248n 13 04.07.17
Wiring: System Programming Connection
•WirelessrouteronlyrequiredforprogrammingwithanApple iPod touch or iPhone.
•Wirelessroutermayberemovedfornormaloperation.
•LutronrecommendsthatanEnergi Savr Node unit with EcoSystem bewiredtoanEthernetjackinthespace
foreaseofaccessandproximitytopowerforthewirelessrouter.
•Workswithanystandardwirelessrouterthatsupportsmulticastpackets.
•Apple iPod touch or iPhone can program other Energi Savr Node units connected to an Energi Savr Node unit
with EcoSystem
viatheQSLink(exceptwhenpartofaQuantumsystem).
•EnergiSavr appisrequired(exceptwhenpartofaQuantum system) to program Energi Savr Node units with
EcoSystem and is available from the Apple AppStore
onlinemarketplace.
LOOP1LOOP2
N/C
WirelessRouter
(by others)
Apple iPod touch or
iPhone mobile digital
device
QSControlLink
To additional Energi Savr Node units
Dedicated Ethernet connection
for Energi Savr Node units
1,2
Energi Savr Node unit
with EcoSystem
Energi Savr
Node unit
Apple,iPhone,andiPodtoucharetrademarksofAppleInc.,registeredintheU.S.andothercountries.AppStoreisaservicemarkofAppleInc.
1 StandardCAT5/CAT5Ecable:Totallengthnottoexceed300ft(100m).
2 Energi Savr Node with EcoSystemunitsarenotdesignedtoexiston
anopennetwork.Connectiontoanopennetworkcouldresultinreduced
performance and Ethernet connectivity issues.
13
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node EcoSystem Digital Fixture Controller
369248n 14 04.07.17
Wiring: Contact Closure Inputs
Com:Common
Com:Common
CCI:ContactClosureInput
Emerg:EmergencyContactClosureInput
Emergency CCI
•Theattacheddevicemustprovideacloseddry
contact closure or solid-state output.
•Inputismiswire-protectedupto36V-.
•TheEnergiSavrNodewithEcoSystem unit is
shippedwithajumperpre-installedintheEmergency
ContactClosureInput.
•Emergencymodeisactivatedbyopeningthe
EmergencyContactClosure.Pre-installedjumper
mustberemovedtoutilizethisfunction.
•SeeApplicationNote#140,“EcoSystemBallastsand
EmergencyWiring”atwww.lutron.comfor
more details.
•Accepts22AWGto12AWG
(0.5 mm
2
to 4.0 mm
2
) solid or
stranded wires.
•Maximumwirerundistance:
250ft(76m).
Programmable CCI
•Theattacheddevicemustprovideadrycontact
closure or solid-state output.
•Inputismiswire-protectedupto36V-.
Energi Savr Node unit with
EcoSystem
Lutron,Lutron,Hi-lume,Quantum,GRAFIKEye,Sivoia,Pico,
seeTouchandEcoSystemaretrademarksofLutronElectronics
Co.,Inc.registeredintheU.S.andothercountries.
EnergiSavrNodeandRadioPowrSavraretrademarksof
LutronElectronicsCo.,Inc.
14