SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241l 3 03.05.18
Specifications (continued)
0–10 V- Product Ratings
(QSN-4T16-S and QSN-4T16-S-347)
•Eachoutputsinksupto50mAmaximum.
•Eachoutputsinkscurrentonly(loaddevicemust
provide 10 V- supply).
•ProvidesanIECPELV/NEC® Class 2 isolated 0–10 V-
outputsignalthatconformstoIEC60929.
Occupancy Sensors
•Upto16occupancysensorscanbeprogrammedto
the ESN device.
•ManualProgramming:upto4occupancysensorswired
directlytotheESNdevice,upto4occupancysensors
wiredtoaQSSensorModule(QSM),andupto10
wireless occupancy sensors through the same QSM; the
total programmed to the ESN device cannot exceed 16.
•HHD(iPod / iPhone)Programming:upto16occupancy
sensors from any source (wired directly to the ESN
device,wiredtoanyotherESNdevice,orwired/wireless
fromanyQSMontheQSlink);thetotalprogrammedto
the ESN device cannot exceed 16.
•UseLutronoccupancysensorstocontroloneormore
zones.
•UseLutronoccupancysensorsinvacancymode
to automatically turn the lights off in an area after it
becomes vacant.
•Eachzonecanbeprogrammedtoautomaticallyturn
the lights on when occupied and turn the lights off when
vacant.
•EachwiredoccupancyinputcanpoweroneLutron
occupancy sensor.
•Eachoccupiedsceneandunoccupiedscenecanbe
programmed independently.
•Lutron occupancy sensors can be programmed to
automatically turn the lights on in area when it becomes
occupied and turn the lights off in an area after it
becomes vacant.
•EachofthefouroccupancyinputscanpoweroneLutron
occupant sensor.
•Eacharea’soccupiedsceneandunoccupiedscenecan
be programmed independently.
•Occupancysensormustprovideadrycontact
closure or solid-state output.
•Additionaloccupancysensorscanbeusedwiththe
ESNdevice.Refertothe“ProgrammingOptionsand
Features”tableforsystemrules.
seeTouch QS Controls
•seeTouchQSwallstationscanbeconguredto
control ESN unit scenes or zones.
• Inzonetogglemode,zonebuttonscanbeassignedtoone
or more zones on any ESN unitconnectedtotheQSLink.
•Inscenemode,wallstationscanbeassignedtoone
or more ESN unitsconnectedtotheQSLink.
•LEDindicatordisplayszoneorscenestatus.
Table 1: seeTouch QS Wallstation Configurations
# Buttons
Wallstation Function
1 2 3 5 7
Zone Toggle
Scene 1,Off
(toggle)
1,Off 1,2
Off
1-4,
Off
N/A
IR Wallstation or Receiver Input
•FourinputsforIRreceiversorwallstationsforcontrolof
lighting zones can be connected directly to the ESN unit.
•UseLutronCC-1BRL-WHorCC-4BRL-WH
wallstations to control one or more zones.
•UseLutron EC-DIR-WHorEC-IR-WHceilingmount
sensors to control one or more zones.
•UptofouradditionalwiredwallstationsorIRreceivers
can be assigned when associated with a QSM.
•AssociateadditionalQSMsandsensors/controls
with ESN unit when programming with an Apple iPod
touch or iPhone
.Referto"ProgrammingOptions"
section for details.
Apple,iPhoneandiPodtoucharetrademarksofAppleInc.,registeredintheU.S.andothercountries.