SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241l 1 03.05.18
Energi Savr Node for 010 V-
Energi Savr Node with Softswitch
The Energi Savr Node (ESN) family is a group of modular
products for the control of lighting and other loads. This
document describes the following products:
•ESN unit
for 0 10 V- (models QSN-4T16-S and
QSN-4T16-S-347 — 0 10 V- Control / Softswitch)
•Softswitch ESN unit (models QSN-4S16-S and
QSN-4S16-S-347 — Softswitch)
Features
•Defaultcongurationrequiresnocommissioning.
•ProgrammingusingintegralinterfaceontheESN unit.
•Fouroccupancysensorinputsforautomatedcontrolof
lights in 4 zones.
•Fourdaylightsensorinputsautomaticallyadjustlight
levels based on the amount of natural light entering
through the windows.
•FourIRreceiverinputsforpersonalcontrol.
•FourinputsforIECPELV/NEC® Class 2 dry contact
switches.
•IncludesQScontrollinkforseamlessintegrationoflights,
controlstations,andQSsensormodules.
•Softswitchtechnologyyields1,000,000cyclerelay
lifetime.
•ContactLutronforcompatibilitywithQuantumsystem.
System Example
QSlink
ControlPower
120–277 V~
LoadInputFeeds (4)
120–277 V~; 347 V~
3
0–10 V Channels (4)
QSN-4T16-S and QSN-4T16-S-347
Emergency
Contact
Closure
Input
Contact
Closure
Input
SwitchedLoadOutputs (4)
16 A Softswitch 120–277 V~; 347 V~
3
Wireless
Communication
WiredDaylight
Sensors (up to 4)
2
Wired
Daylight
Sensors
(up to 4)
1,2
WiredOccupancy
Sensors (up to 4)
Wired
Occupancy
Sensors
(up to 4)
1
Wired Wallstation
orIRreceivers(upto4)
Wired
Wallstation
orIRReceivers
(up to 4)
1
IECPELV/
NECR Class 2
DryContact
Switch (up to 4)
(by others)
IRTransmitter
IRTransmitterOR OR
OR OR
Notes:
1 Up to 4 wired sensors total (of any type).
2 The maximum number of daylight sensors (wired and
wireless) that an ESN unit can support is
four (1 per zone).
3 For347V~ models only.
QSM
seeTouch QS
Wallstation
ESN
Programming
Interface
RadioPowrSavr
Occupancy
Sensor (up to 10
per QSM)
RadioPowrSavr
DaylightSensor
(up to 10 per QSM)
2
PicoWireless
Controller
(up to 10 per
QSM)
1
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241l 2 03.05.18
Specifications
Regulatory Approvals
•UL
Listed
•CSA
•NOM
•LutronQualitySystemsregisteredtoISO9001:2015
• Complieswithrequirementsforuseinotherspaces
used for environmental air (plenums) per
NEC
® 2014 300.22(C)(3)
•MeetstheCanadianNationalBuildingCodeplenum
requirementsforaconcealedspaceusedasaplenum
within a floor or roof assembly
•Forcommercialuse,ClassAonly
Power
•ControlPower:120V~; 220–240 V~; 277 V~
50/60Hz
•LightningstrikeprotectionmeetsANSI/IEEEstandard
62.41-1991.Canwithstandvoltagesurgesofupto
6,000V~andcurrentsurgesofupto3,000A
•Currentdraw:0.5Amax
•10-yearpowerfailurememory:restoreslightingtolevels
prior to power interruption
•Latchingrelayskeeppreviouslyilluminatedzoneson
when control power feed is lost
Environment
•AmbientTemperatureOperatingRange:32ºFto104ºF
(0ºCto40ºC)
•Relativehumidity:lessthan90%non-condensing
•Forindooruseonly
•Thermaldissipation:40BTU/hr
Terminal Wiring
•ControlPowerWiring:14AWGto12AWG(2.5mm
2
to
4.0mm
2
)
•LoadWiring:14AWGto12AWG(2.5mm
2
to4.0mm
2
)
• 010V-Wiring:20AWGto12AWG(0.5mm
2
to4.0mm
2
)
•InputGroupWiring:20AWGto12AWG(0.5mm
2
to
4.0mm
2
) — maximum wire run length to each input not
toexceed150ft(46m)
•QSLinkWiring:22AWGto12AWG(0.5mm
2
to
4.0mm
2
)
•ContactClosureWiring:20AWGto12AWG(0.5mm
2
to4.0mm
2
)
Physical Design and Mounting
•NEMAType1,IP-20protection
•Surfacemount
Load Types (relay ratings)
•16ATungsten,120to277V~
•16AACGeneralUse,120to277V~
•16AElectricDischargeLamp(ballast),120to
277 V~
,347V~ (347 V~ models only)
•16AInductive,120to277V~
•0.5HP,120V~
•1.5HP,220to277V~
•Workswithallballastsanddriversthatprovideacurrent
sourcethatiscomplianttoIEC60629
AnnexE.2,andwhoseinrushcurrentdoesnotexceed
NEMA410 standards for electronic ballast/driver
Input Default Associations
Inputs/Outputs Zone 1 Zone 2 Zone 3 Zone 4
Group 1
Occ X
Photo X
IR X
Switch X
Group 2
Occ X
Photo X
IR X
Switch X
Group 3
Occ X
Photo X
IR X
Switch X
Group 4
Occ X
Photo X
IR X
Switch X
CCI X X X X
EmergencyCCI X X X X
Softswitch: 120 V~ to 277 V~,
347 V~ (347 V~ models only)
•Softswitch relay is rated for 16 A continuous use per
channel,whichisthemaximumcontinuousloadfora
20AOvercurrentProtectionDevice(BranchBreaker).
•PatentedSoftswitch circuit eliminates arcing at
mechanical contacts when loads are switched.
Extendsrelaylifetoanaverageof1,000,000cycles
(on/off)forresistive,capacitive,orinductivesources.
•Relayismechanicallyheld.
2
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241l 3 03.05.18
Specifications (continued)
010 V- Product Ratings
(QSN-4T16-S and QSN-4T16-S-347)
•Eachoutputsinksupto50mAmaximum.
•Eachoutputsinkscurrentonly(loaddevicemust
provide 10 V- supply).
•ProvidesanIECPELV/NEC® Class 2 isolated 010 V-
outputsignalthatconformstoIEC60929.
Occupancy Sensors
•Upto16occupancysensorscanbeprogrammedto
the ESN device.
•ManualProgramming:upto4occupancysensorswired
directlytotheESNdevice,upto4occupancysensors
wiredtoaQSSensorModule(QSM),andupto10
wireless occupancy sensors through the same QSM; the
total programmed to the ESN device cannot exceed 16.
•HHD(iPod / iPhone)Programming:upto16occupancy
sensors from any source (wired directly to the ESN
device,wiredtoanyotherESNdevice,orwired/wireless
fromanyQSMontheQSlink);thetotalprogrammedto
the ESN device cannot exceed 16.
•UseLutronoccupancysensorstocontroloneormore
zones.
•UseLutronoccupancysensorsinvacancymode
to automatically turn the lights off in an area after it
becomes vacant.
•Eachzonecanbeprogrammedtoautomaticallyturn
the lights on when occupied and turn the lights off when
vacant.
•EachwiredoccupancyinputcanpoweroneLutron
occupancy sensor.
•Eachoccupiedsceneandunoccupiedscenecanbe
programmed independently.
•Lutron occupancy sensors can be programmed to
automatically turn the lights on in area when it becomes
occupied and turn the lights off in an area after it
becomes vacant.
•EachofthefouroccupancyinputscanpoweroneLutron
occupant sensor.
•Eacharea’soccupiedsceneandunoccupiedscenecan
be programmed independently.
•Occupancysensormustprovideadrycontact
closure or solid-state output.
•Additionaloccupancysensorscanbeusedwiththe
ESNdevice.Refertothe“ProgrammingOptionsand
Features”tableforsystemrules.
seeTouch QS Controls
•seeTouchQSwallstationscanbeconguredto
control ESN unit scenes or zones.
• Inzonetogglemode,zonebuttonscanbeassignedtoone
or more zones on any ESN unitconnectedtotheQSLink.
•Inscenemode,wallstationscanbeassignedtoone
or more ESN unitsconnectedtotheQSLink.
•LEDindicatordisplayszoneorscenestatus.
Table 1: seeTouch QS Wallstation Configurations
# Buttons
Wallstation Function
1 2 3 5 7
Zone Toggle
Scene 1,Off
(toggle)
1,Off 1,2
Off
1-4,
Off
N/A
IR Wallstation or Receiver Input
•FourinputsforIRreceiversorwallstationsforcontrolof
lighting zones can be connected directly to the ESN unit.
•UseLutronCC-1BRL-WHorCC-4BRL-WH
wallstations to control one or more zones.
•UseLutron EC-DIR-WHorEC-IR-WHceilingmount
sensors to control one or more zones.
•UptofouradditionalwiredwallstationsorIRreceivers
can be assigned when associated with a QSM.
•AssociateadditionalQSMsandsensors/controls
with ESN unit when programming with an Apple iPod
touch or iPhone
.Referto"ProgrammingOptions"
section for details.
Apple,iPhoneandiPodtoucharetrademarksofAppleInc.,registeredintheU.S.andothercountries.
3
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241l 4 03.05.18
Specifications (continued)
Daylight Sensors
•Lutrondaylightsensorsallowdaylightharvestingwith
programmable effect on light output.
•Fourdaylightsensorscanbeconnecteddirectlytothe
ESN unit.
•UseLutronEC-DIR-WHsensorstocontroloneormore
zones.
•Alternatively,uptofoursensors(LutronWiredDaylight
SensorsorRadioPowrSavrDaylightSensors)canbe
assigned when associated with a QSM.
•ThemaximumnumberofLutrondaylightsensors(wired
orwireless),eitherwireddirectlytotheunitorindirectly
(associated with a QSM) cannot exceed four.
•AssociateadditionalQSMsandsensors/controlswith
ESN unit when programming with an Apple iPod touch
or iPhone
.Referto"ProgrammingOptions"sectionfor
details.
Contact Closure Input (CCI)
Default behavior:
•Activatescenesusingmomentaryormaintainedclosures
fromanexternaldevicesuchasatimeclock.
•StartorstopAfterhoursModeusingamaintained
closure.
•Theattacheddevicemustprovideadrycontactclosure
or solid-state output.
•CongurableforNormally-Open(NO)orNormally-Closed
(NC) operation.
•Inputismiswire-protectedupto36V-.
Emergency Contact Closure Input
•Bydefault,contactclosureinputfromLutron
EmergencyLightingInterface(LUT-ELI-3PH),security,
orrealarmsystemsturnsallzonesontofulloutput
when emergency state is detected.
•Emergencycontactclosureinputisnormallyclosed
(NC). The ESN unitisshippedwithajumperpre-
installed.
•Responseofeachzoneiscongurable.
•Attacheddevices,bydefault,willgotomaximum
output and ignore control inputs.
•Nooperationswillbealloweduntilemergencysignal
is cleared.
•Theattacheddevicemustprovideadrycontact
closure or solid-state output.
•Inputismiswire-protectedupto36V-.
•EmergencyCCIcannotcontrolotherESNunits.
Functionality with GRAFIK Eye QS
•ESN
unitfollowsGRAFIKEye QS scene activations
whenassociatedwiththeGRAFIKEye QS.
•ESN unit responds to commands initiated by the
GRAFIKEyeQS astronomictimeclockwhen
associatedwiththeGRAFIKEyeQS.
•ESN unit operates in afterhours mode when
associatedwithaGRAFIKEyeQSthatisinafterhours
mode.
Functionality with QSE-IO
•ESN unit responds to scene commands initiated by
theQSE-IO,iftheQSE-IODIPswitcheshavebeenset
toeithersceneselectionmode,zonetogglemode,
partitionmode,oroccupancysensormode.
Functionality with QSE-CI-NWK-E
•IntegrateESN unitwithtouchscreens,PCs,A/V
systems,orotherdigitalsystemsanddevices.
•Recallscenesandset/adjustzonelevels.
Apple,iPhoneandiPodtoucharetrademarksofAppleInc.,registeredintheU.S.andothercountries.
4
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241l 5 03.05.18
Specifications (continued)
IEC PELV / NEC® Class 2 Dry Contact Switches
•FourinputsforIECPELV/NEC® Class 2 dry contact
switches can be assigned to turn on and off one or
more zones.
•Congureformomentaryormaintainedoperation.
QS Link Limits
•EachESN unitcanprovideupto14PowerDrawUnits
(PDUs)forotherQSdevices.RefertotheQSLink
PowerDrawUnitspecicationsubmittal(Lutron
P/N369405)formoreinformationconcerningPDUs.
•TheQSLinkcanhaveupto100devicesand100zones.
•EachESN unit counts as 1 device towards the
100 device limit.
•EachESN unit counts as 4 zones towards the
100 zone limit.
QSM (QS Sensor Module)
•UsetheQSMtointegrateRadioPowrSavr
Occupancysensors,RadioPowrSavr Daylight
sensors,andPicoWirelessControllerstocontrol
zones on the ESN unit.
•Associate1QSMperESN unit with manual
programming.
•AssociatemultipleQSMsperESN unit with Apple
iPod touch or iPhone
programming(requires
QSE-CI-AP-DandWi-Firouter).See"Programming
Options"fordetails.
•Assignupto10RadioPowrSavrOccupancysensors
per ESN unit via QSM.
•Assignupto4RadioPowrSavrDaylightsensorsper
ESN unit via QSM.
•Assignupto10PicoWirelessControllersperESN
unit via QSM.
•ThesensorsandPicoWirelessControllersassociated
with the QSM should be mounted within 60 ft (18 m)
lineofsight,or30ft(9m)throughwalls,oftheQSM.
•Wireandpowerupto4wiredsensorsperQSM
–DaylightSensors
–OccupancySensors
–Infrared(IR)ReceiversorWallstations
•RefertoQSMSpecicationSubmittalformore
information.
Apple,iPhoneandiPodtoucharetrademarksofAppleInc.,registeredintheU.S.andothercountries.
5
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241l 6 03.05.18
Programming Options
Manual Programming:
•Use buttons on the front of the ESN unit.
•
UsemanualprogrammingininstallationswithonlyoneESNunitandwithoneQSMorfewerontheQSlink.
HHD Programming
•
RequiresESNProgrammingInterface(QSE-CI-AP-D).
•RequiresApple iPod touch or iPhone mobile digital device.
•Use the intuitive programming application for the Apple iPod touch or iPhone to program systems with multiple
ESN
unitsandQSMsintheQSlink.
•WirelessrouteronlyrequiredforprogrammingwithanApple iPod touch or iPhone.
•Wirelessroutermayberemovedfornormaloperation.
•EthernetconnectionmaybemadeviaanESNProgrammingInterface(QSE-CI-AP-D)oranESNQSunitwith
integralEthernetjack.
•LutronrecommendsthatanESNProgrammingInterface(orESNQSunitwithEthernetjack)bewiredtoan
Ethernetjackinthespaceforeaseofaccessandproximitytopowerforthewirelessrouter.
•Workswithanystandardwirelessrouterthatsupportsmulticastpackets.
•Apple iPod touch or iPhone can program all ESN QSunitsconnectedtoanESNProgrammingInterfaceviatheQS
Link(exceptwhenpartofaQuantumsystem).
•ESNappisrequiredandisavailablefromtheApple iTunes Storeonlinemarketplace.
QSLink
QSM QSM QSM
ESN Unit
Apple
iPod touch or
iPhone mobile
digital device
Wireless
Router
(by others)
ESN Programming
Interface
QSE-CI-AP-D
DedicatedEthernet
Connection for ESN
units
1,2
ESN Unit ESN Unit
QSLink
1 StandardCAT5/CAT5Ecable:Totallengthnottoexceed300ft(100m)
2 Note:ESNunitsarenotdesignedtoexistonanopennetwork.
Connectiontoanopennetworkcouldresultinreducedperformanceand
Ethernet connectivity issues.
Apple,iPhone,iPodtouchandiTunesStorearetrademarksofAppleInc.,registeredintheU.S.andothercountries.
6
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241l 7 03.05.18
Programming Options and Features
Manual Programming
HHD Programming:
Requires ESN Programming Interface
QSE-CI-AP-D
Requires Apple iPod touch or iPhone mobile
digital device
ESN units connected to 1 QS
Link
Not more than 1 Multiple—100 QS devices and 100 zone limits apply
QSMs connected to 1 QS link Not more than 1 Multiple—100 QS devices limit applies
Wired Occupancy Sensors
System Limits 4 connected directly to ESN unit
Up to 4 wired to QSM
Up to 100 total occupancy sensors per QS link
(wired + wireless)
Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same
QS link
Occupancy Dependency
Supported
No Yes
Wireless Occupancy Sensors
System Limits Associate 10 occupancy sensors to QSM
to control zones on the ESN unit
Up to 100 total occupancy sensors per QS link
(wired + wireless)
Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same
QS link
Occupancy Dependency
Supported
No Yes
Wired Daylight Sensors
System Limits Maximum of 1 daylight sensor per zone
4 connect directly to the ESN unit
Additional daylight sensors can connect to
the QSM
Maximum of 2 daylight sensors per zone
Up to 100 total daylight sensors per QS link
(wired + wireless)
Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same
QS link
Disable daylighting in Scenes No Yes
Wireless Daylight Sensors
System Limits Maximum of 1 daylight sensor per zone
Associate wireless daylight sensors to the
QSM
Maximum of 2 daylight sensors per zone
Associate up to 10 wireless daylight sensors per QSM
Up to 100 total daylight sensors per QS link
(wired + wireless)
Can be assigned to… Any zone(s) on the ESN unit Zones on ESN unit or share to other ESN units on same
QS link
Disable daylighting in Scenes No Yes
Apple,iPhone,andiPodtoucharetrademarksofAppleInc.,registeredintheU.S.andothercountries.
7
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241l 8 03.05.18
Programming Options and Features (continued)
Manual Programming
HHD Programming:
Requires ESN Programming Interface
QSE-CI-AP-D
Requires Apple iPod touch or iPhone mobile
digital device
Pico Wireless Controllers
System Limits Associate 10 Pico wireless controllers to
QSM to control zones on the ESN unit
Up to 100 total controls per QS link (wired wallstations,
Pico wireless controllers, IR receivers)
Can be assigned to… Any zone on the local ESN unit Zones on ESN unit or share to other ESN units on
same QS link
IR Receivers and Wallstations
System Limits 4 connect directly to the ESN unit
Up to 4 wired to the QSM
Up to 100 total controls per QS link (wired wallstations,
Pico wireless controllers, IR receivers)
Can be assigned to… Any zone on the local ESN unit Zones on ESN unit or share to other ESN units on
same QS link
NEC
® dry contact Switches Inputs
Can be assigned to… Any zone(s) on the connected ESN Any zone(s) on the connected ESN
Contact Closure Input
Can be assigned to… Any zone(s) on the ESN unit Any or all local ESN unit zones
Functions • Sweep to off
• Enable/disable afterhours
Turn on to preset and turn off
• Sweep to off
• Enable/disable afterhours
Turn on to preset and turn off
Afterhours Conguration afterhours timeout – 15 minutes
blink-warn timeout – 5 minutes
Afterhours timeout and blink-warn
timeouts are congurable
Emergency Contact Closure Input
Can be assigned to… Any zone(s) on the ESN unit Any or all local ESN zones
Emergency Light level Congurable Congurable
Apple,iPhone,andiPodtoucharetrademarksofAppleInc.,registeredintheU.S.andothercountries.
8
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241l 9 03.05.18
Programming Options and Features (continued)
Manual Programming
HHD Programming:
Requires ESN Programming Interface
QSE-CI-AP-D
Requires Apple iPod touch or iPhone mobile
digital device
seeTouch QS wallstations
Scene Keypads assigned to… Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link
Scene + off keypads assigned
to…
Any zone(s) on the ESN unit Any zone(s) on one or more ESN units on the QS link
Zone toggle keypad buttons
assigned to…
Any zone(s) on the ESN unit Any zone(s) on on or more ESN units on the link
Change Keypad to Scene or
Zone
Yes Yes
Changing keypads to shade,
panic, ne tune
No Yes
Zone Configuration Parameters
Load type 0-10, 10-0, or switched 0-10, 10-0, or switched
High-end trim Adjustable Adjustable
Low-end trim Adjustable Adjustable
Absolute minimum level Adjustable Adjustable
Scenes
Available scenes Scenes 1-16 Scenes 1-16
GRAFIK Eye QS N/A Share scenes, timeclock events, or afterhours events
to ESN units on QS Link
QSE-IO Scene, zone toggle, occupancy Scene, zone toggle, occupancy
QSE-CI-NWK-E Yes Yes
Apple,iPhone,andiPodtoucharetrademarksofAppleInc.,registeredintheU.S.andothercountries.
9
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241l 10 03.05.18
Mechanical Dimensions
All dimensions shown as in (mm)
11.25
(285.75)
0.20(5.16)
diameter
1.00
(25.40)
1.22
(30.99)
1.66
(42.16)
1.31
(33.27)
0.88
(22.35)
9.25
(234.95)
7.50
(190.50)
3.16
(80.26)
13.25
(336.55)
Donot
use side
knockouts
Line Voltage Shield
10
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241l 11 03.05.18
Wiring: QS Link
Onlyterminals1,3,and4connected
betweendevicesthatsupplyPDUs
Terminal 2 NEVER connected
between devices that supply PDUs
Terminal 2 (+24 V)
NEVERconnected*
Devicesthat
supplyPDUs
Devicesthat
consumePDUs
COM
+24 V
MUX
MUX
COM
MUX
MUX
ESN QS unit
ESN QS unit
QS
Input/
Output
Interface
Wired
QS
Keypad
QSM
QSMQSM
Wired
QS
Keypad
Wired
QS
Keypad
Wired
QS
Keypad
QS
Input/
Output
Interface
QS
Link
power
supply
**
QSLink;
all 4 terminals
QSLink;
no terminal 2
QSLink;
no terminal 2
QSLink;
all 4 terminals
QSLink;
all 4 terminals
Terminal 2 (+24 V)
NEVERconnected*
Terminal 2 (+24 V)
NEVERconnected*
All4terminalsconnectedtoQSlink
devicesthatconsumePDUs
QS Link Wiring Rules
* Terminal2(+24V)shouldNEVERbeconnectedbetweendevicesthatsupplyPDUs.
** ForQSLinkpowersupplywiringconnectiondetails,refertotheinstallationinstructions
for the specific power supply model being used.
11
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241l 12 03.05.18
Wiring: IEC PELV / NECR Class 2 Inputs
Occupancy
Sensor
Daylight/
IRSensor*
IR
Transmitter
IR
Transmitter
Note: Maximum wire
run length to each
input not to exceed
150ft(46m).
IRReceiver
or Wired
Wallstation*
IECPELV/NEC®
Class 2
DryContact
Switch
Red
Black
Yellow
Blue/Gray**
Black
Red
20 V – 20 V-
Occ–OccupancySensor
Daylight–DaylightSensor
IR–IRReceiver*
Switch – IECPELV/NEC® Class 2
Com – Common
LUTRON
Input Group Wiring:
•20AWGto12AWG
(0.5mm
2
to4.0mm
2
)
•Striplength:1/4in(6mm)
•Torque:5in
lb(0.5N
m)
NOTE: There are four input groups. Each group has the
same inputs as shown in the diagram below.
* Note:OnlyoneIRdevicemaybeconnectedperinput.If
theIRsignalfromadaylightsensorisconnected,awall
controlmaynotbeconnectedtothesameinput,and
vice-versa.
** Connectthegraywireon-Rmodeloccupancysensors.
Group1shown Group2shown
Red
20V
Black COM
White
IR
12
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241l 13 03.05.18
Wiring: Contact Closure Inputs (CCI and Emerg)
Com – Common Emerg – Emergency
CCI–ContactClosureInput
Com – Common
Contact Closure Wiring:
•20AWGto12AWG
(0.5mm
2
to4.0mm
2
)
•Striplength:1/4in(6mm)
•Torque:5in
lb(0.5N
m)
13
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241l 14 03.05.18
Wiring Diagram: Example A – 4 circuits, multiple feeds
Zone Switching:
120–277 V~;
347 V~*
0–10 V- Zones:
(QSN-4T16-S and
QSN-4T16-S-347)
Switched Hot (1B)
Hot Feed (1A)
Hot Feed (2A)
Hot Feed (3A)
Hot Feed (4A)
Switched Hot (2B)
Switched Hot (3B)
Switched Hot (4B)
Ground
Lug
Neutral Wires
Distribution
Panel
LOAD
LOAD
LOAD
LOAD
Load Wiring:
•Two(2)14AWGto
12AWG(2.5mm
2
to4.0mm
2
)
•Striplength:3/8in
(8.5mm)
•Torque:7in-lb
(0.79N
m)
0–10 V- Wiring
(QSN-4T16-S and
QSN-4T16-S-347)
Hot
Hot
Hot
Hot
Hot
Neutral
Neutral
Neutral
Neutral
Neutral
Neutral
Ground
Hot
*For347V~
models only.
0-10 V- Wiring (QSN-4T16-S and QSN-4T16-S-347)
•20AWGto12AWG(0.5mm
2
to4.0mm
2
)
•Striplength:1/4in(6mm)
•Torque:5in
-
lb(0.5N
m)
•ConnectonlyIECPELV/NEC® Class 2 circuits or connect only
non-IECPELV/NEC® Class 2 circuits to 0-10 V zones 1-4.
•0-10V- zones 1-4 are not isolated from each other.
•Negative(–)terminalsarenotinternallyconnectedtoeach
other - both positive (+) and negative (–) connections must
be made.
•Followallnationalandlocalcodesforseparation
requirements.
14
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Energi Savr Node QSN 0–10V-/Softswitch Fixture Controllers
369241l 15 03.05.18
Wiring Diagram: Example B – 4 circuits, single feed
0-10 V Wiring (QSN-4T16-S and QSN-4T16-S-347)
•20AWGto12AWG(0.5mm
2
to4.0mm
2
)
•Striplength:1/4in(6mm)
•Torque:5in
-
lb(0.5N
m)
•ConnectonlyIECPELV/NEC® Class 2 circuits or
connectonlynon-IECPELV/NEC® Class 2 circuits to
0-10 V- zones 1-4.
•0-10V- zones 1-4 are not isolated from each other.
•Negative(–)terminalsarenotinternallyconnected
to each other - both positive (+) and negative (–)
connections must be made.
•Followallnationalandlocalcodesforseparation
requirements.
Zone Switching:
120-277 V~;
347 V~*
0-10 V- Zones:
(QSN-4T16-S and
QSN-4T16-S-347)
Hot
Neutral
Ground
Hot
Neutral
Ground
Ground
Lug
“A” Terminals Jumpered
Neutral Wires
Distribution
Panel A
Distribution
Panel B
LOAD
LOAD
LOAD
LOAD
Load Wiring:
Two(2)14AWGto
12AWG(2.5mm
2
to4.0mm
2
)
•Striplength:3/8in
(8.5mm)
•Torque:7in-lb
(0.79N
m)
0-10 V- Wiring
(QSN-4T16-S and
QSN-4T16-S-347)
Switched Hot (1B)
Hot Feed (1A)
Switched Hot (2B)
Switched Hot (3B)
Switched Hot (4B)
*For347V~
models only.
)Lutron,Lutron,Softswitch,seeTouch,Pico,
QuantumandGRAFIKEyearetrademarksofLutron
ElectronicsCo.,Inc.registeredintheU.S.andother
countries.
EnergiSavrNodeandRadioPowrSavrare
trademarksofLutronElectronicsCo.,Inc.