SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron® Sivoia® QS Wireless 120V Power Supply Panel
086125 REV C 1 07.31.13
Sivoia QS Wireless | 120 V power supply
Panel
QSPSY-P1-10-60
10 output Power Supply Panel
The Sivoia QS Wireless Power Supply Panel
is a 24 V hardwired power supply that is
used with Lutron® QS Wireless shading
devices. QSPSY-P1-10-60 simplifies the
wiring and organizes installations that require
multiple power supplies. Each panel
contains ten 30 W (60 W peak) power
supplies, designed for use with Lutron QS
Wireless shading devices.
QSPSY-P1-10-60 is designed to be hard
wired into a standard 120 V~ circuit. The
panel contains fuses on each output to
protect the device in the event of a miswire.
Features
24 V supply that provides power to
shades, blinds, and drapery drive units
Simple wiring scheme uses 2-conductor
low voltage link to provide power to
QS Wireless electronic drive units
Terminal block wire connections for easy
installation
10 output panel provides power for 10 to 30
shades based on shade dimensions
LED’s provide output status feedback
1
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron® Sivoia® QS Wireless 120V Power Supply Panel
086125 REV C 2 07.31.13
Specifications
Input Voltage 120 V~
Input current per 8 A (35% duty cycle) or 4.6 A (continuous)
QSPSY-P1-10-60
Output Voltage 24 V
Output Current 2.5 A (35% duty cycle) or 1 A (continuous)
Operating Frequency 60 Hz
ESD Protection (+/-) 16kV
Miswire Protection Fuse on each output
2 spares included
(5x20 mm, 2.5 A fast acting fuse)
Wiring Input wires to 120 V~ supply, output wires to Lutron QS
Wireless shade, blind, or drape drives
Wiring type Input wires: 10-14 AWG (6-2.5 mm²) stranded
Output wires:
2 conductor 12-18 AWG (4-1 mm²) stranded
Connections Terminal blocks
Maximum QSPSY-P1-10-60 1 panel per dedicated 15 A circuit
Note: use only high magnetic breakers
Maximum QSPSY-P1-10-60 2 panels per dedicated 20 A circuit
Note: use only high magnetic breakers
Maximum feed breaker size 30 A
Weight 25 lbs (11.3 kg)
Regulatory Approvals UL Listed: #E42071 (Industrial Control Equipment)
UL Listed: #E135084 (Drapery Operator)
CSA: 1658313
Industrial Control Equipment Limited Voltage/Limited Current Circuit
(NEC® approved class 2 power source)
2
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron® Sivoia® QS Wireless 120V Power Supply Panel
086125 REV C 3 07.31.13
Dimensions
QSPSY-P1-10-60
3.90 in
(99 mm)
17.50 in
(444 mm)
9.50 in (241 mm)
10.30 in (262 mm)
with cover
without cover
18.30 in
(465 mm)
3
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron® Sivoia® QS Wireless 120V Power Supply Panel
086125 REV C 4 07.31.13
System Wiring Overview: QS Panel Power Supply
Sivoia QS wireless
roller shade
QS Wireless Power
Supply Panel
Sivoia QS wireless
skylight shade
Sivoia QS wireless
drapery track
2 Conductor wire length
gauge and number of
shades or drapes
varies. Refer to QS
Wireless Power Supply
Panel Wiring Guide
below
4
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron® Sivoia® QS Wireless 120V Power Supply Panel
086125 REV C 5 07.31.13
QS Power Panel Link Rules
Wiring Guidelines for Power Panel Outputs (x10)
Maximum devices per one output
(panel provides up to 10 outputs)
Maximum distance per one output based on wire gauge***
Shades + Devices
Pins 1 and 2 (Voltage and Common)
12 AWG
4 mm²
16 AWG
1.5 mm²
18 AWG
1 mm²
None
Up to 50 power
draw units**
1250 ft (375 m)*** 500 ft (150 m)*** 250 ft (75 m)***
None
Up to 25 power
draw units**
2000 ft (600 m)*** 1000 ft (300 m)*** 600 ft (175 m)***
1 Sivoia® QS
shade
Up to 1 power draw
unit**
500 ft (150 m)*** 200 ft (60 m)*** 125 ft (35 m)***
2 Sivoia® QS roller 64,
≤ 30 sq ft
(2.75 sq m) each
200 ft (60 m)*** 75 ft (20 m)*** 50 ft (15 m)***
3 Sivoia® QS roller 64,
≤ 20 sq ft
(1.8 sq m) each
2 Sivoia® QS
roller 100, ≤ 50 sq ft
(4.6 sq m) each
The following QS Power Panel Link rules must be observed for proper operation:
1. Maximum 2000 ft (600 m) of cable to devices from each QS Panel power supply (all 10 outputs
combined)
Note: Secondary wiring must be of type CL2, CL2P, CL2R, CL2X or other cable with equivalent
or better electrical, mechanical, and flammability ratings in accordance with local and national
electric code.
Important Notes:
** One Power Draw Unit (PDU) = 1 QS wall station. See document 369-405 for a list of PDUs per product.
*** Maximum 2000 ft (600 m) of cable for all 10 outputs combined.
5