Specifications
Power
• 120 V~ 50 / 60 Hz 120 mA
• 230 V~ 50 / 60 Hz 80 mA
• Lightning strike protection meets ANSI / IEEE standard
62.31-1980. Can withstand voltage surges of up to
6000 V~ and current surges of up to 3000 A.
• Stand by power: 7 W
• BTUs / hour when fully loaded: 24
• DALI
® bus Output: 16V- 128 mA guaranteed supply
current, 250 mA maximum supply current per bus.
Standards
• Lutron Quality Systems registered to ISO 9001:2015.
• IEC 60669-2-1
• DALI-2
® Certified
• UL
• cUL
• NOM
Environment
• Surrounding Air Temperature Range: 0 ºC to 65 ºC
(32 ºF to 149 ºF).
• Relative Humidity: less than 90% non-condensing.
• Calibration point maximum: 75 ºC (167 ºF)
• For indoor use only.
Terminals
• Mains Wiring: 1.0 mm
2
to 4.0mm
2
(18AWG to 10AWG)
• DALI
® bus Wiring: 0.5 mm
2
to 4.0mm
2
(20AWG to 10AWG)
• QS Link Wiring: 0.5 mm
2
to 4.0mm
2
(20 AWG to 10 AWG)
• Minimum wire temperature rating = 65 °C (149 ºF),
copper wire only
Mounting
• Mount in a Lutron DIN Panel (see spec 369788) or in
an IP20 (minimum) rated consumer panel or breaker
panel with integrated DIN rail.
• Width = 9 DIN modules (161.7 mm or 6
3
⁄8 in).
• For more information on mounting and installation in
panels with integrated DIN rail see Lutron P/N 048466
at www.lutron.com
Programming and Compatibility Requirements
• The LQSE-2DAL-D can only be used with the
HomeWorksQS system.
• Setup and programming of the DALI
® Power Module
is done through the HomeWorksQS programming
software.
DALI
® Buses
• Up to 64 DALI
® compliant loads on each bus can be
addressed and grouped into 16 zones.
• DALI
® Power Module supplies a maximum of 250 mA
to power each bus.
• DALI
® Power Module supplies a guaranteed current
of 128 mA to power each bus.
• DALI
® Power Module has an integrated bus power
supply with polarity indicated on the unit.
• Some DALI
® loads may be polarity sensitive. Refer
to individual manufacturers' specifications for proper
connection to the DALI® bus.
• Short circuit protection with automatic restart.
QS Link Limits
• A QS link in a HomeWorksQS system can have up
to 512 zones (outputs) and 100devices. A DALI
®
compliant digital addressable load counts as 1 zone
unless specifically grouped into zones from the
HomeWorksQS software.
• Each DALI
® Power Module counts as one device
toward the 100 device limit.
• A maximum of 8 fully loaded DALI
® buses may be
connected to a single QS link.
HomeWorks QS Wallstations
• HomeWorks QS wallstations can be configured to
control DALI
® Power Modules with the HomeWorks
QS programming utility.
• LED indicator displays the status of programmed lights.
Troubleshooting and Maintenance
Features
• Maintains redundant memory of control gear
programming for ease of single or multiple control
gear replacement.
• To verify DALI
® lights connected to DALI® bus 1 and
bus 2:
– Enter Test Mode: Press and hold Test button on
the DALI
® Power Module until the Test LED starts
flashing.
– Test: Each press of either the DALI
® version-1 or
DALI-2® button will cycle the lights between
high-end, low-end, flash and off for that bus.
– Exit Test Mode: Press and hold Test button until