SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
3691112g 5 04.27.20
Wallbox ControlsPhase-Selectable Dimmer
Maestro
Multigang and Mixed-Bulb-Type Ratings
Ganging and Derating
When combining controls in the same wallbox, derating is required. See Load Type and Capacity.
No derating is required for companion devices.
Load Type and Capacity
Model
Number
Description Voltage Load Type Minimum Load
Maximum Load
Neutral
Required Phase
Mode
Not Ganged End of Gang Middle of gang
MA-PRO-XX
1,2
Phase-
Selectable
Neutral Optional
Dimmer
120 V~
LED
2
1 bulb 250 W 200 W 150 W Optional
8
Either
CFL
2,3
1 bulb 250 W 200 W 150 W Optional
8
Forward
MLV Transformer
with LED
See Application Note #559 (P/N 048559) at www.lutron.com
No Derating Required
Required
Forward
ELV Transformer
with LED
Reverse
MLV Transformer
with Halogen
4,5,6,
10 W
400 VA
(300 W)
No Derating Required Required Forward
ELV Transformer
with Halogen
4,5
10 W 500 W 400 W 300 W Required Reverse
Incandescent/
Halogen
5 W 500 W 400 W 300 W Optional
8
Either
Dimmable
Fluorescent
Ballast
7
1 ballast 3.3 A (400 VA) No Derating Required Required Forward
Hi-lume 1%
2-Wire (LTE)
LED Drivers
3
1 driver
3.3 A (400 W)
20 drivers max
No Derating Required Required Forward
PHPM-PA / 3F
and GRX-TVI
1 interface 3 interfaces No Derating Required Required Forward
1
Designed for use with permanently installed LED, incandescent, tungsten halogen, or magnetic low-voltage transformers with halogen based lamps.
2
See bulb list at www.lutron.com/ledfinder
3
SSL-7A-2015 compliant when in forward-phase.
4
When using magnetic (core and coil) low-voltage transformers with halogen lamps set the dimmer to forward-phase. When using with dimmable electronic (solid-state) low-voltage
transformers set the dimmer to reverse-phase.
5
Operation of a low-voltage circuit with lamps inoperative or removed may result in transformer overheating and premature failure. Lutron strongly recommends the following:
• Do not operate low-voltage circuits without operative lamps in place.
• Replace burned-out lamps as soon as possible.
• Use transformers that incorporate thermal protection or fused transformer primary windings to prevent transformer failure due to overcurrent.
6
When using the dimmer / switch to control MLV halogen fixtures, the maximum lamp wattage is determined by the efficiency of the transformer, with 70%–85% as typical. For actual
transformer efficiency, contact either the fixture or transformer manufacturer. The total VA rating of the transformer(s) shall not exceed the VA rating of the dimmer / switch.
7
Includes Philips Advance Mark 10® ballasts, Sylvania®, Tu-Wire, and POWERSENSE®.
8
Neutral is recommended for best dimming performance, if available, but is not required for this load type.
Total LED / CFL
Wattage Installed
(Watts per bulb X # of bulbs)
Maximum Allowable
Incandescent / Halogen Wattage
Not ganged End of gang Middle of gang
0 W + 500 W 400 W 300 W
1 W – 50 W + 400 W 300 W 200 W
51 W – 100 W + 300 W 200 W 100 W
101 W – 150 W + 200 W 100 W 0 W
151 W – 200 W + 100 W 0 W N/A
201 W – 250 W + 0 W N/A N/A