SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Adaptive Power Module HomeWorks QS Phase Adaptive Fixture Controller
369583f 2 07.23.18
Specifications
Adaptive Power Module
Power
• 220–240 V~ 50/60 Hz
• 10 A maximum total input current
• Lightning strike protection meets ANSI/IEEE standard
62.31-1980. Can withstand voltage surges of up to
6 000 V and current surges of up to 3 000 A.
Standards
• RoHS Compliant
• IEC/EN 60669-2-1
• CE marked
• Lutron Quality Systems registered to ISO 9001.2015
Environment
• See Mounting on page 4 for thermal specifications
• Relative humidity: less than 90% non-condensing
• For indoor use only
Output Zone Ratings
•
No Derating is required if all the conditions below are met:
– Calibration point maximum is 70 ºC
– Room ambient temperature is between 0 ºC and 30 ºC
– Panel ambient temperature is between 0 ºC and 50 ºC
• 100 W Derating is required on all zones for a single
module in a single non-ventilated DIN enclosure if:
– The room ambient temperature is between
30 ºC and 40 ºC.
• 200 W Derating is required on all zones for multiple
row non-ventilated DIN enclosure if:
–
The room ambient temperature is between 30 ºC and
40 ºC.
Output Zone Ratings (continued)
• Each zone has no minimum load requirement.
• When programmed to "auto" mode, the unit starts in
trailing edge and if an incompatible load is detected, it
will convert to leading edge.
• Internal relay provides an air gap off when all zones
are off.
• One load type per zone.
• Output must not be used to control receptacles,
including plug-in lamps.
•
Output must be directly connected to the load.
Output breakers or switches must not be used.
• Run a separate neutral for each load circuit. A
common neutral connection is not recommended.
• Maximum wire length between the Energi Savr Node
unit and the load must be less than 30.5 m.
• Unit may be powered by Ground Fault Interrupter (GFI)
or Residual Current Circuit Breaker with Overload
(RCBO) protected circuit if required. Load circuit wiring
(from breaker to unit to load) must be run in its own
non-metallic conduit, or nuisance tripping may occur.
• For applications requiring 0–10 V- control, use Ten
Volt Interface (GRX-TVI) or the LQSE-4T10-D.
• For applications requiring higher wattage ratings, use a
power booster (NGRX-PB, NGRX-ELVI, NGRX-FDBI).
Each zone is rated for the following wattage and load types
A, B
:
Load Type
Zone 1 Rating Zone 2, 3 and 4 Rating (per zone)
No Derating
100 W
Derating
200 W
Derating No Derating
100 W
Derating
200 W
Derating
Incandescent / Halogen 800 W 700 W 600 W 500 W 400 W 300 W
Electronic Low Voltage 800 W 700 W 600 W 500 W 400 W 300 W
Magnetic Low Voltage
D
800 VA (600 W
C
) 700 VA (525 W
C
) 600 VA (450 W
C
) 500 VA (375 W
C
) 400 VA (300 W
C
) 300 VA (225 W
C
)
Neon / Cold Cathode
D
800 VA (600 W
C
) 700 VA (525 W
C
) 600 VA (450 W
C
) 500 VA (375 W
C
) 400 VA (300 W
C
) 300 VA (225 W
C
)
A
Additional load type options are available in the HomeWorks QS software suite, some may require an interface. Contact Lutron for details.
B
Refer to Lutron P / N 048478 on www.lutron.com for compatibility with dimmable CFL / LED light sources.
C
Actual lamp wattage.
D
Only use iron core transformers intended for use with an electronic switch or dimmer per Clause 8.3 of IEC / EN 60669-2-1